Triangle Tube EB073 Instinct Solo Wall Instruction Manual
- June 9, 2024
- Triangle Tube
Table of Contents
Tube EB073 Instinct Solo Wall
Instruction Manual
ENGINEERING BULLETIN
EB073 Instinct Solo Wall
Subject:
Gas Valve Adjustment Instructions for Natural Gas and Propane
The following instructions address the adjustment of the appliance gas valve for Natural Gas and Propane. Be sure to review and comply with all SAFETY WARNING labels as noted below.
- Instructions are intended for a qualified installer or service technician only.
- Read all instructions before proceeding.
- Follow instructions in proper order.
If an analyzer is not available, DO NOT make any adjustment to the gas valve. Recommended Tools:
- Flat Head Screwdriver
- T40 Torques key
- Calibrated Combustion Analyzer
DEFINITIONS
The following terms are used throughout this manual to bring attention to the
presence of potential hazards or to important information concerning the
product.
DANGER
Indicates the presence of a hazardous situation which, if ignored, will result
in substantial property damage, serious injury, or death.
WARNING
Indicates a potentially hazardous situation which, if ignored, can result in
substantial property damage, serious injury, or death.
CAUTION
Indicates a potentially hazardous situation which, if ignored, can result in
minor property damage, or injury.
NOTICE
Indicates special instructions on installation, operation or maintenance,
which are important to the equipment but not related to personal injury
hazards.
Indicates recommendations made by Triangle Tube for the installers, which will
help to ensure optimum operation and longevity of the equipment
Carbon Monoxide gas can cause serious injury or death. Obey all PPE requirements at all times, and if evacuation is required, vacate immediately Triangle Tube accepts no liability for any damage, injury, or loss of life resulting from incorrect installation, alteration of any factory supplied parts, or the use of parts or fittings not specified by Triangle Tube. If there is a conflict or doubt about the proper installation of the unit or any factory supplied replacement parts please contact Triangle Tube Technical Support.
A. Low Fire (Offset) Cap & Adjustment Screw
B. Reference Pressure Connection
C. High Fire Adjuster (Throttle)
D. Low Fire Pressure (Offset Pressure)
E. Gas Inlet Pressure
Diagram 1 – Gas Valve Diagram
| | Natural Gar. 110, 155| Natural Gas 199| Propane 110.155| I Propane 199
---|---|---|---|---|---
LOW FIRE I HIGH FIRE| CO2 Range| 9.0 to 10.5%| 8.5 to 10.5%| 10.0 to 11.0%
CO2 Target| 10.%| 11.%
02 Range| 4.85 to 2.15 %| I 5.75 to 2.15 %| 5.7 to 4.2 %
02 Target| 4.%| 5.%
CO Max| <150 ppm| @ 9.5% CO2| s200 ppm @ 10.8% CO2
| | |
CO2 Range| 9.0 to 10.0%| 8.5 to 10.0%| 10.0 to 11.0%
CO2 Target| 10.%| 9%| 11.%| 110.%
| Target values are equivalent to High Fire values, ensure
CO2 values measured are less than or equal to High Fire
CO2 measurements| Target values are equivalent to High Fire values, ensure
CO2 values measured are less than or equal to High Fire
CO2 measurements
02 Range| 4.85 to 3.0 %| 5.75 to 3.0 %| 5.7 to 4.2 %
02 Target| 4.%| 5.%| 5.%| I 5.1%
| Target values are equivalent to High Fire values, ensure
02 values measured are higher than or equal to High
Fire 02 measurements| Target values are equivalent to High Fire values, ensure
02 values measured are Where than or equal to High
Fire 02 measurements
CO Max| 10 ppm| 10 ppm
1. Preliminary Checks
a. Sample probe must be inserted sufficiently, and ensure sampling is correct
when CO2/O2 readings are measured (refer to Fig.1 for probe position and
insertion).
b. Appliance must be operating in service mode at 100% for high fire and 1%
for low fire when CO2/O2 values are measured (Fig.2 / 3). Heating circuit
should have all circulation pumps operating, providing sufficient flow
through the appliance.
a. Touch simultaneously on the and soft keys for 3 seconds to access the
functions for the installer. Reference
b. Menthe in alter access code “054* by using the and . keys to select a digit
location and the and soft keys to change the digit. Touch the soft key to
enter the access code.
c. Touch the soft key to highlight the Manual Operation icon then touch the
soft key.
d. Touch the soft key while the FAN ‘con is highlighted to manually fire the
burner and power the CH circulator(s).
e. Touch the soft key to adjust ch.% firing rate from 1% to 100%. Hold down
the soft key to rapidly increase the firing rate.
Once the combustion level is set at high fire (100%), manually place the
boiler into low fire (1%) mode by touching the soft key to adjust firing rate
down.c. Ensure appliance gas valve
reference tube is correctly installed and connected with no kinks or splits
(Fig.4).
d. Replace fiber washers with the new ones provided (hardware box) (Fig.4).
e. Ensure gas pipe connections are tight and leak free. See Section 10.5 on
page 62 from installation guide.
f. Check the incoming gas pressure at the unit (fig.5) is in accordance with
table 2 with all gas appliances in operation and standby.
| Minimum| Maximum
---|---|---
Natural Gas| 5 in w.c.| 13 in w.c.
Propane (LP)| 8 in w.c.| 12 in w.c.
Table 2 – Gas Pressure (inches water column)
g. If CO2 is below specified tolerance (as per table 1) record High fire
CO2/O2 in Table 4 – Section 1A & 1B, then follow section 2 and 3 to adjust
High and Low fire Combustion.
Triangle Instinct Solo/Combi Gas Valve Adjustment Instructions
2. High Fire Adjustment (Throttle)
a. Operate boiler to High Fire 100% in service mode (Fig.6).
b. Alter High Fire adjuster (throttle) (fig.7) in ¼ incremental steps until
CO2 is within specified tolerance (as per table 3).
c. Wait for stable combustion reading between each adjustment.
Direction | INSTINCT Solo/Combi |
---|---|
Clockwise | Decrease CO2 / Increase O2 |
Counter-Clockwise | Increase CO2 / Decrease O2 |
Table 3 – High Fire Adjuster (Throttle)
d. If CO2 levels have reached the limit or high fire adjustment screw
(throttle) is fully open, record High fire CO2/O2 in Table 4 – Section 2A).
if no stop can be felt remove gas valve and ensure butterfly valve is open all the way (no white seen) (fig.8).e. Operate appliance to Low fire 1% (fig.9).
f. If CO2 at low fire is below specified tolerance (as per table 1) move to
section 3. Low Fire Adjustment.
g. If combustion is within tolerance (as per Table 1) Record Low Fire CO2/O2
in Table 4 – Section 2B and do not adjust low fire Adjuster
(offset).
3. Low Fire Adjustment (Offset)
a. Operate appliance at low fire 1% in service mode (Fig.9).
b. Ensure the boiler is at low fire under a stable operating condition whilst
monitoring CO2/O2 values.
c. If low fire CO2/O2 values are still below tolerance, record Low Fire CO2/O2
in Table 4 – Section 2B
Direction | INSTINCT Solo/Combi |
---|---|
Clockwise | Increase CO2 / Decrease O2 |
Counter-Clockwise | Decrease CO2 / Increase O2 |
Table 4 – Low Fire Adjuster (Offset)
Using “T40” torques key/bit (fig 10), unscrew, and remove cap of the gas valve
low fire adjustment (offset) (Fig.11).
d. Adjust low fire screw (offset) clockwise in small 1/10 the of a turn
adjustments until the CO2 measurement is within the tolerance band but no
greater than 1% CO2 increase than the combustion reading after throttle
adjustment at low fire (Fig.12). Refer to result recorded in Table 4 – Section
2B.
1% CO2 = 1.8% less O2 on Natural Gas
1% CO2 = 1.5% less O2 on Propane
Valve responds slowly so make smalt 1/10 adjustment to the low fire adjustment screw (offset) and wait for stable combustion reading before repeating.
CO2 measurement should be increased no greater than 1% via low fire adjustment
screw (offset) adjustment from previous reading at low fire Refer to result
recorded in Table 2 – Combustion Results summary (column 2-Low fire.)
e. Record Low Fire CO2/O2 in Table 3 – section 3.B.
f. If minimum CO2/O2 is still below allowed specification tolerance contact
triangle tube technical support. Tel: (856) 228 8881
g. Operate appliance to High Fire 100% (Fig.6) Record High Fire CO2/O2 in
Table 3 – 3.A).
h. Table 2 – Combustion Results summary should be submitted to Triangle Tube
technical support
Instinct model Number:
Serial Number:
Date of Installation:
Fuel: | Natural gas | Propane |
---|---|---|
1.Combustion Readings Before Adjustment | 2.Combustion Readings After high fire | |
Adjustment | 3.Combustion Readings After Low Fire Adjustment |
CO2
measurement should be increased no greater than 1% via offset adjustment from
previous reading at low fire (column 2. After Throttle Adjustment)
Table
4 – Combustion Results summary
1% CO2 = 1.8% less O2 on Natural Gas
1% CO2 = 1.5% less O2 on Propane
QR codes to refer to Videos of combustion analyzer / gas valve adjustment /
sensing lines + connections
Please contact technical support at techsupport@triangletube.com 856-228-8881 x575 with any questions.
Triangle Tube – 1240 Forest Parkway,
Suite 100 – West Deptford, NJ 08066
Tel: 856-228-8881 –
Fax: 856-228-3584 –
e-mail: info@triangletube.com