Triangle Tube Instinct-FSB Solo Floor Standing User Guide
- June 12, 2024
- Triangle Tube
Table of Contents
Application
Guide Instinct FSB
SOLO 110-155-199 & COMBI 155-199
Instinct-FSB Solo Floor Standing
NOTICE
- This manual is applicable to all Instinct floor standing boilers with display software version 0.40 or later.
- If this guide does not apply to your boiler, Please visit triangletube.com to obtain the correct application guide.
WARNING
This document is intended to be used by a factory trained and qualified
heating contractor or service technician only. Read all Instructions within
this document and within the relevant Boiler Installation and Maintenance
Manual before proceeding. It is recommended o follow the procedures in the
steps given. This guide does not replace the Installation and Maintenance
manual. Skipping or missing procedural steps could result in substantial
property damage, serious injury, or death.
NOTICE
- When receiving the Instinct unit, any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
- Customer must register unit within sixty (60) days of installation in order to gain warranty coverage. See Warranty Card for details.
- Leave all documentation received with appliance with the owner for future reference.
- Installation and service should only be performed by a qualified installer or service technician.
- Installations and service should be performed by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.
Boiler Pump Presets
The boiler comes preconfigured for several preset pump outputs.
- To access the Installer screen, touching simultaneously the up and down soft keys for 3 seconds as shown in Fig. 1.
- Enter the installer access code “054” by using the LEFT and RIGHT buttons to select a digit and the UP and DOWN buttons to change the digit. Press the OK button to enter the access code.
- Press the OK button while the CH & DHW Settings icon is highlighted.
- Press the OK button while the Boiler Settings icon is highlighted.
- Press the OK button while the Pump Settings option is highlighted.
- Press the OK button while the Pump Settings option is highlighted.
- Scroll down the preset pump list and select one of the following options shown in Table 1.
Table 1: Instinct Preset Pump Configurations
Preset
Configuration| Boiler Pump
Flex 1| CH1 Pump
Flex 5| CH2 Pump
Flex 3| DHW Pump
Flex 2
---|---|---|---|---
A| CHI Call
CH2 Call
DHW Call| CHI Call
CH2 Call| | DHW Call
B & C
Out of the box setting| CH1 Call
CH2 Call
DHW Call| CH1 Call| CH2 Call| DHW Call
D| CH1 Call
CH2 Call DHW Call| CH1 Call
CH2 Call| CH1 Call
CH2 Call| DHW Call
E| CH1 Call
CH2 Call| CH2 Call| CH2 Call| DHW Call
F| CH1 Call
CH2 Call| CH1 Call
CH2 Call| CH1 Call
CH2 Call| DHW Call
Note: Other Presets are shown as availble. These are non functional in the Instinct BoilersFig. 8: Piping Layout Legend
Flexible Pump Configuration
This allows the installer to customize the flexible Pump Output (relays) to a specific installation arrangement that is not addressed in the Preset Pump Configuration options. There are a total of four Pump Output(relays) that must be set.
-
To access the Installer screen, touching simultaneously the up and down soft keys for 3 seconds as shown in Fig. 9.
-
Enter the installer access code “054” by using the LEFT and RIGHT buttons to select a digit and the UP and DOWN buttons to change the digit. Press the OK button to enter the access code.
-
Press the OK button while the CH & DHW Settings icon is highlighted.
-
Press the OK button while the Boiler Settings icon is highlighted.
-
Press the OK button while the Pump Settings option is highlighted.
-
Press the OK button while Flexible Pump Config option is highlighted.
-
A list of 4 Flex Relays are clickable. These are the Boiler actions to be edited. • When selecting Flex Relay 1, the boiler pump actions are being edited.
• When selecting Flex Relay 2, the DHW pump actions are being edited.
• When selecting Flex Relay 3, the CH2 pump actions are being edited.
• When selecting Flex Relay 5, the CH1 pump actions are being edited. -
Select the relay to be changed. Choose whether the relay will be on or off for any of the following calls: CH1, CH2, DHW, MIX OPEN, MIX CLOSE, ERROR, FLAME.
• When selecting CH1, the relay is activated at CH1 demand.
• When selecting CH2, the relay is activated at CH2 demand.
• When selecting DHW, the relay is activated at DHW demand.
• Mix Open is not functional in the Instinct Boilers.
• Mix Close is not functional in the Instinct Boilers.
• When selecting ERROR, the relay is activated on error.
• When selecting FLAME, the relay is activated when appliance is running and a flame signal has been detected. -
Once the Relay’s actions have been selected, scroll down and hit enter on the Save and Exit option at the bottom. This relay shown in Fig. 16 is set to turn on the pump wired to the CH1 terminal only for CH1 calls.
NOTICE
The options will not be saved when quick exiting (hitting the house or back
arrow at the bottom of the menu.
Instinct Solo Piping Diagrams
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the box
NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the box
NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset A or D Pump Configuration (D Shown)
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| ON| OFF
CH2| ON| ON| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler pump settings must be changed for this
arrangement NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the
box NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the
box NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Instinct Combi Piping Diagrams
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the
box NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the
box NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Note: the boiler is set up in this configuration out of the
box NOTICE
Layout is shown with separate Circulator and check valve. If using a
circulator with internal check valve, the corresponding check valve is
unnecessary.
Preset A or D Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| ON| OFF
CH2| ON| ON| ON| OFF
DHW| ON| OFF| OFF| ON
Preset B Pump Configuration
Heat Call| Boiler Pump| CH1 Pump| CH2 Pump| DHW Pump
CH1| ON| ON| OFF| OFF
CH2| ON| OFF| ON| OFF
DHW| ON| OFF| OFF| ON
Triangle Tube – 1240 Forest Parkway, Suite 100, West Deptford NJ 08066
Tel: (856) 228 8881 –
Fax: (856) 228 3584 –
E-mail: info@triangletube.com
2021-13B – Instinct FSB Application Book
229023 A02
January 3, 2022