Triangle Tube INSFS199S Instinct Floor Standing 199 Solo Instructions
- June 12, 2024
- Triangle Tube
Table of Contents
Triangle Tube INSFS199S Instinct Floor Standing 199 Solo
Product Information
The Instinct Floor Standing 199 Solo is a boiler designed for heating purposes. It has a model number of INSFS199S and an input capacity of 24.875 MBH. The heating net AFUE (Annual Fuel Utilization Efficiency) is 199 MBH, and the boiler has a maximum capacity of 185 MBH. It has an air vent and operates on gas. The shipping weight of the boiler is 225 lbs.
Boiler Dimensions
- A: 21 5/8 [550]
- B: 19 [482]
- C: 3 1/2 [90]
- D: 2 1/4 [58]
- E: 5 1/8 [130]
- F: 40 3/4 [1036]
- G: 8 5/8 [220]
- H: 12 5/8 [320]
- J: 30 3/8 [771]
- K: 7 3/4 [198]
- L: 6 [150]
- M: 2 5/8 [68]
- N: 9 1/8 [233]
- P, Q: 7 3/4 [198]
- S: 2 1/2 [62]
- T: 21 5/8 [548]
Product Usage Instructions
- Ensure that the boiler is placed on a stable and level surface.
- Connect the necessary inlet and outlet connections to the boiler. Use 3/4-inch connections.
- Properly ventilate the boiler by installing an air vent.
- Make sure the gas supply is connected to the boiler.
- Refer to the provided user manual for detailed instructions on how to operate and control the boiler.
- In case of any errors or issues, refer to the “Last 8 Errors” section in the manual for troubleshooting guidance.
Note: It is recommended to consult with a consulting engineer, architect, or mechanical contractor when installing or servicing the Instinct Floor Standing 199 Solo boiler.
Features
Instinct Floor Standing 199 Solo Features
- Heavy duty construction for floor standing installation
- Approved for zero clearance to combustibles
- 3” PVC, CPVC, PP, or AL29-4C venting up to 100 equivalent feet
- Left or Right side optional boiler connections
- Left, Right, Top, or Back gas connections
- 10 year limited warranty on heat exchanger
- Up to 6 year limited warranty on parts, except igniter
- Up to 3 year labor allowance
Approvals
- 95% AFUE Efficiency
- ENERGY STAR Qualified
- ANSI Z21.13 and CSA 4.9 Boiler Standards Compliance
- ASME Boiler Certification – ASME “H” Stamp
- SCAQMD Rule 1146.2 Low NOx Certification
Stainless Steel Fire Tube Heat Exchanger
- 439 Stainless Steel heat exchanger construction for corrosion resistance
- High water content provides stable temperature control
- Self cleaning flue ways reduce maintenance
- Suitable for use with propylene glycol up to 50%concentration
CTRL Max Control System
- Graphical display with 5 navigation buttons
- EZ Setup allows quick and easy boiler settings adjustment
- Flexible configuration of 4 circulator outputs for custom applications
- Outdoor temperature reset to maximize efficiency
- Accepts two space heating call inputs with independent outdoor reset curves
- Domestic hot water priority with optional time-out
- Integrated cascade control for up to 6 Instinct boilers
- 0-10 VDC Modulation input
- Modbus building management system (BMS) interface, LonWorks® and BACnet® interface optional
- Adjustable warm weather shutdown
- Adjustable boiler freeze protection
- Logging function records sensor readings for system optimization and troubleshooting
- Describes lockouts in plain English and suggests solutions while storing last 8 errors
Standard Equipment
- Factory fitted remote Wifi monitoring
- Stainless steel premix burner
- Direct spark ignition with variable speed blower
- Full modulation with turndown ratio of 8:1
- Hydraulic Separator with dirt and air separation
- Automatic air vent
- ASME 30 PSI pressure relief valve
- Temperature and Pressure gauge
- Outdoor temperature sensor
- Automatic low water cutoff feature with early warning
- High temperature manual reset limit safety control
- Terminal block for circulator output
- Low voltage terminal strip with removable jumpers for manual or automatic reset limits
- Swing up control for easy access and servicing
- Polypropylene condensate pan and internal flue pipe
- 3 in 1 Universal vent adapter directly accepts PVC/CPVC, Polypropylene, Stainless steel connections with test ports
- Additional external 110V socket
- Project / Location: ___
- Date:
- Consulting Engineer / Architect: __
- Mechanical Contractor: _____
Boiler Dimensions
Boiler Performance
Instinct Floor Standing Boiler | Details |
---|---|
Model Number | Input, MBH |
Rating,
MBH
| AFUE| Boiler Connections| Air Inlet| Vent Outlet| Gas Connections| Shipping
Weight
Min| Max
INSFS199S| 24.875| 199| 185| 161| 95%| 1”| 3”| 3”| 3/4″| 225 lbs
- The Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15.
- Triangle Tube should be consulted before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
- The ratings have been determined under the provisions governing forced draft burners.
Boiler Dimensions
Dimensions – In [mm]
A| B| C| D| E| F| G| H| J| K| L| M| N| P, Q| S| T
21 5/8”| 19”| 3 1/2”| 2 1/4″| 5 1/8”| 40 3/4”| 8 5/8| 12 5/8”| 30 3/8″| 7
3/4″| 6″| 2 5/8″| 9 1/8″| 7 3/4″| 2 1/2″| 21 5/8″
[550]| [482]| [90]| [58]| [130]| [1036]| [220]| [320]| [771]| [198]| [150]|
[68]| [233]| [198]| [62]| [548]