HB Products HBSC HB Switches with Circular Electronic Unit Instruction Manual
- June 9, 2024
- HB Products
Table of Contents
HBSC HB Switches with Circular Electronic Unit
Instruction Manual WE INCREASE UPTIME, SAFETY AND
EFFICIENCY
Instruction manual
HB switches with circular electronic unit
Covers: HBSC, HBSR, HBSR-HFC, HBSO-LT, HBSO1, HBSO2, HBOR, HBSO1-MT & HBSO2-MT
Functionality
The switches are used for detecting liquid in gas or air (HBOR detect oil in
liquid ammonia). The mechanical elements have different design because they
are optimized to different liquids. The switches use the capacitive measuring
principle and react to the difference in dielectric constant between liquid
and gas.
The switches have different calibration and parameter settings in the
electronic unit, but unit is the same. The settings cannot be changed by the
user, and it must match the mechanical part. Switches delivered after
September 2020 has a build in heater which will be in operation below 5°C to
keep the sensor dry
Standard switches available from HB-products
Switches from HB-products are suited for different fluids, different
temperature ranges and supply voltages. There is a special program for oil
switches. The two tables show the recommended products.
Oil switches
Supply voltage and recommended oil temperature
Allowed temperature is typically higher| PAO Mineral| POE
PAG| Application
Available in special EX| Design| Settings NO/NC NPN/PNP
version (different electronic unit)
---|---|---|---|---|---
24 V AC/DC low temp -30-40 °C (-22-104 °F)| HBSO-LT| Refrigeration| | Preset
90-240 V AC – low temp -30-40 °C (-22-104 °F)| HBSO-SSR-2-LT| Refrigeration| |
Preset
Relay output
24 V AC/DC – normal temp 0-60 °C (32-140 °F)| HBSO1| HBSO2| Refrigeration| |
Preset
90-240 V AC – normal temp 0-60 °C (32-140 °F)| HBSO1-SSR-2| HBSO2-SSR-2|
Refrigeration| | Preset
Relay output
24 V AC/DC – medium temp 40-100 °C (104-212 °F)| HBSO1-MT| HBSO2-MT| Heat
pump| | Preset
24 V AC/DC high or all temp 90-145 °C (194-293 °F)
0-145 °C (32-293 °F) changed settings| HBSO-SSR-1-HT| Oil separator or
universal| | Can be changed Relay output
24 V AC/DC- Oil return switch -30-80 °C (-22-176 °F)| HBOR| Oil return system
NH3| | Preset
Liquid switches
Liquid
Supply voltage, recommended liquid temperature and IP class Specified
temperature range is typically wider| R744 CO2 R600 Butane R600a Isobutane
R290 Propane| R507, R410a, R407c R404a, R22, R32, R134a, R1234yf, R1234ze
Other HFC/HFO| R717 NH3, R718 Water, Alcohols| Electronic part
design| Settings NO/NC NPN/PNP EX version (different electronic unit)
---|---|---|---|---|---
24 V AC/DC – dry conditions -40-50 °C (-40-122 °F) IP54| HBSC2| HBSR-HFC HBSR|
HBSR| | Preset
24 V AC/DC – elevated temp. 50-80°C 122-176 °F) IP54| HBSC2| HBSR-HFC| HBSR-
HP| | Preset
24 V AC/DC – for wet and condensing applications IP66| HBSC2-U| HBSR-HFC-U
HBSR-U| HBSR-U| | Preset
90-240 V AC – normal temp -55-80 °C (-67-86 °F) IP54| HBSC2-SSR-2| HBSC-HFC-
SSR-2
HBSC-HFC-SSR-2| HBSR-SSR-2| | Preset
Relay output
24 V AC/DC low ambient temp -55-30 °C (-67-86 °F) IP66| HBSC2-SSR-1/IP| HBSR-
HFC-SSR-1/1P HBSR-SSR-1/IP| HBSR-SSR-1/1P| | Can be changed
Mechanical part design| | | | |
What can happen if the switch is installed outside the recommended temperature
range
The HB-products web page has temperature specifications for the switches, and
these will be different from the recommended temperature specifications. The
switches will operate outside the recommended range but will not be optimal.
For oil switches the switch point will change with temperature and this means
there is a risk that the switch will not detect oil or detect without oil. For
sensors installed in low temperatures condensation might occur and water run
into the connection between the mechanical and electrical unit. This might
disturb the measurement. Sensors designed for low temperatures has treaded
union which is waterproof.
Labelling:
The switches are delivered as NO/NC and NPN/PNP connection. The switches
setting is printed on the small silver label on the switch together with the
type code. On the same label you find a combined version number and
manufacturing date and in second row a unique production number.
Safety Instructions
CAUTION! Read the instruction manual before commencing work! Heed all
warnings. Installation of HBSR requires technical knowledge of both
refrigeration and electronics. Only qualified personnel should work with the
product. The technician must be aware of the consequences of an improperly
installed sensor and must be committed to adhering to the applicable local
legislation.
If changes are made to type-approved products, this type approval becomes
void. The product’s input and output as well as its accessories may only be
connected as shown in this guide. HB Products assumes no responsibility for
damages resulting from not adhering to the above.
Intended use, conditions of use. The switch is manufactured to detect liquid.
If the switch is to be used in a different way or for another purpose, and if
the operation of the product in this function is determined to be problematic,
prior approval must be obtained from HB Products.
Prevention of collateral damage. Make sure that qualified personnel assess any
faults and take necessary precautions before attempting to make replacements
or reparations, to avoid collateral damage.
Disposal instructions: The switch is built so the modules can easily be
removed and sorted for disposal.
Electrical connections
The switch can be supplied with 24V±10% AC or DC. A standard ISO 4400 connector is used. The power consumption will depend on the temperature due to a built-in heater. Wiring is done according to the drawings below depending on the version PNP or NPN. For the PNP versions a relay can be applied between pin 2 and pin 3.The switch is predefined as NO (normally open) or NC (normally closed) and this refers to the contact in the switch, in dry condition.
Switching
All switches except HBOR switch on when liquid is detected. This means a NO
switch close the contact when liquid is detected, and a NC open the contact
when in liquid
HBOR is different: it switches off when oil is detected
LED indication
4 x red LED´s indicate liquid/oil detection.
4 x green LED´s flashing indicate no detection, but sensor is active.
4 x red flashing LED´s indicate no connection to mechanical unit.
Irrespective of the output function (NO/NC) LED´s are activated when liquid is
detected.
Mechanical installation
The switch is installed in a vessel or compressor, using Teflon tape or liquid
sealant, for those with NPT thread.
Switches with a straight tread is delivered with a washer kept in place by an
O-ring or a plastic spring. The O-ring or a plastic spring should be removed
before installation.
Switches installed in ammonia, water and alcohol has a mechanical element
covered with PTFE. This is a part of the switch and should remain on when
installed.
All switches can be installed horizontally except for switches in cold
conditions, where the liquid has high viscosity. For these switches, make sure
liquid can drain from the switch. This can be done by sloping the switch 0- 5
degrees downwards.
Long weld adapters should be avoided because gas pockets can build up and
disturb the measurement.
Switches pointing upwards can collect liquid which disturb the measurement.
Disconnect
the electronic unit by loosening the treaded union or the two set screws. In
cold conditions the switches can be installed with a downward slope.Apply Teflon
tape or liquid gasket on sensors with a conical thread. For other thread
types, a washer is used.Fasten the mechanical part with the shifting
spanner (tightening torque 80-150 Nm, depending on thread type).
Mounting the electronic unit
The electronic unit is mounted with either a threaded union or with two set of
screws in a V-track. The threaded union is mainly used for switches operating
in cold conditions. The set screws are tightened with a torque of 5 Nm and the
threaded union is tightened firmly by hand or by using pliers to secure a good
electrical connection. For cold installations where condensation occur the
treaded union should be used to avoid poor contact between electrical contact
between mechanical and electrical unit.
Fault detection
In case of fault, it is normally enough to replace the electronic part.
Fault | Possible Reason | Correction of fault |
---|
No LED is on when the sensor is
in the medium.| No supply to the sensor or defective cable/plug.| Check the
power supply or replace the power supply cable.
Output and 4xLEDs are constantly activated, even though liquid is not in
contact with the sensor.| Water or moisture shortcut the sensor between the
mechanical and electrical part| Use a sensor with treaded union or dry the
parts and make a suitable cover against water
Sensor repair:
The sensor electronics are completely embedded and can therefore not be
repaired.
In case of faults with the sensor, it will typically only be necessary to
replace the electronics.
If you have a faulty product, please contact the HB Products
dealers/distributors.
Their complaints procedures must be followed before returning the sensor.