HB Products HBSC2 Liquid Level Switch User Guide

June 9, 2024
HB Products

WE INCREASE UPTIME,
SAFETY AND EFFICIENCY
Quick guide

All liquid level switches with circular electronic unit HBSC2, HBSR, HBOR & HBSO

HB Products HBSC2 Liquid Level Switch - liquid level
switches

Functionality and labelling:

The switches are used for detecting liquid in gas or air (HBOR detect oil in liquid ammonia). The mechanical elements have different design because they are optimized to different liquids. The switches use the capacitive measuring principle and react to the difference in dielectric constant between liquid and gas.
The switches have different calibration and parameter settings in the electronic unit, but unit is the same. The settings cannot be changed by the user, and it must match the mechanical part. Switches delivered after September 2020 has a build in heater which will be in operation below 5°C to keep the sensor dry
The switches are delivered as NO/NC and NPN/PNP connection. The switches setting is printed on the small silver label on the switch together with the type code. On the same label you find a combined version number and manufacturing date and in second row a unique production number.

HB Products HBSC2 Liquid Level Switch - switches

LED indication

4 x red LED´s indicate liquid/oil detection.
4 x green LED´s flashing indicate no detection, but sensor is active.
4 x red flashing LED´s indicate no connection to mechanical unit.
Irrespective of the output function (NO/NC) LED´s are activated when liquid is detected.

Mechanical installation

The switch is installed in a vessel or compressor, using Teflon tape or liquid sealant, for those with NPT thread.
When installing the switch in cold conditions, where the liquid has high viscosity, make sure liquid can drain from the switch. This can be done by sloping the switch 5 degrees downwards.
Long weld adapters should be avoided because gas pockets can build up and disturb the measurement Switches pointing upwards can collect liquid which disturb the measurement

Mounting the electronic unit

The electronic unit is mounted with either a threaded union or with two set of screws in a V-track. The threaded union is mainly used for switches operating in cold conditions. The set screws are tightened with a torque of 5 Nm and the threaded union is tightened firmly by hand or by using pliers to secure a good electrical connection. For cold installations where condensation occur the treaded union should be used to avoid poor contact between electrical contact between mechanical and electrical unit.

Standard switches available from HB-products

Liquid switches

Liquid

Supply voltage, recommended liquid temperature and IP class Specified temperature range is typically wider.
24 V AC/DC – dry conditions -40-50 °C (-40-122 °F) IP54| R744 CO2
R600 Butane
R600a Isobutane R290 Propane| R507, R410a, R407c R404a, R22, R32, R134a, R1234yf, R1234ze Other HFC/HFO| R717 NH3,
R718 Water, Alcohols| Electronic part
design| Settings NO/NC NPN/PNP EX version (different electronic unit)
HBSC2| HBSR-HFC HBSR| HBSR| | Preset
24 V AC/DC – elevated temp. 50-80°C 122-176 °F) IP54| HBSC2| HBSR-HFC| HBSR- HP| | Preset
24 V AC/DC – for wet and condensing applications IP66| HBSC2-U| HBSR-HFC-U HBSR-U| HBSR-U| | Preset
90-240 V AC – normal temp -55-80 °C (-67-86 °F) IP54| HBSC2-SSR-2| HBSC-HFC- SSR-2
HBSC-HFC-SSR-2| HBSR-SSR-2| | Preset
Relay output
24 V AC/DC low ambient temp -55-30 °C (-67-86 °F) IP66| HBSC2-SSR-1/IP| HBSR- HFC-SSR-1/IP HBSR-SSR-1/IP| HBSR-SSR-1/IP| | Can be changed
Mechanical part design| | | |  |

Oil Switches

Supply voltage and recommended oil temperature
Allowed temperature Irs typically higher| PAO Mineral| POE PAO| Application| Design| Settings NO/F1C NPN/PNP
Available in special LX venom se….. web….1
---|---|---|---|---|---
24 V AC/DC low temp -30-40 ‘C (-22-104’F)| HBSO-LT| Refrigeration| | Preset
90-240V AC- low temp -30-40’C (-22.104’F)| HBSO-SSR-2-LT| Refrigeration| | Preset
Relay output
24 V AC/DC- normal temp 0-60’C (32-140’F)| HBSOI| HBSO2| Refrigeration| | Preset
90-240 V AC – normal temp 0-60 t (32-140 ‘F)| H8SO1-SSR-2| HBSO2-SSR-2| Refrigeration| | Preset
Relay output
24 V AC/DC- medium temp 40-100’C (104.212’F)| HBS01- MT| HI3S02, MT| Heat pump| | Preset
24 V AC/DC high or all temp
90-145 ‘C (194-293’0
0.145’C (32.293’F) tango.  6,| HBSO-SSR-1-HT| 071 separator or universal| | Can be changed Relay output
24 V AC/DC- Oil return switch -30.80’C (-22-176’F)| HBOR| 011 return system Pli13| | Preset

Electrical connection

The switch is predefined as NO (normally open) or NC (normally closed) and this refers to the contact in the switch, in dry condition.
The switch is either PNP or NPN type and the connection must be done according to the drawing. Switches can be supplied with AC, but the output will be DC

HB Products HBSC2 Liquid Level Switch - Electrical
connection

Switching

All switches except HBOR switch on when liquid is detected. This means a NO switch close the contact when liquid is detected, and a NC open the contact when in liquid. HBOR is different: it switches off when oil is detectedHB
Products HBSC2 Liquid Level Switch - Switching

Electrical specifications

Connector: DIN 43650/ISO4400
Relay current max 50 mA
Supply AC/DC 24V ± 10 %

More information
For further information please download the instruction manual from our
homepage:www.hbproducts.dk.
December 2021

Documents / Resources

| HB Products HBSC2 Liquid Level Switch [pdf] User Guide
HBSC2 Liquid Level Switch, HBSC2, Liquid Level Switch, Level Switch, Switch
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals