Honeywell VR8300 Continuous Pilot Combination Control Owner’s Manual
- June 4, 2024
- Honeywell
Table of Contents
VR8300/VR8301
Continuous Pilot Combination
Gas Control
Application
These continuous pilot gas controls are used in gas-fired appliances with
capacities up to 200 cu ft/hour at 1 in. WC pressure drop [5.7 cum/hour at
0.25 kPa] on natural gas. They include a manual valve, safety shutoff, single
automatic operators, and a pressure regulator. See Table 3 for temperature
ranges and regulator types.
BODY PATTERN: Straight-through body pattern. INLET X OUTLET SIZES AVAILABLE:
la x 1/2 in., 1/2 x 3/4 in., and 3/4 x 3/4 in. (factory-installed inlet
flange). ADAPTERS: Adapters available for 1/2 and 3/4 inch straight and angle
connections. Refer to Table 4. ELECTRICAL RATINGS: Voltage and Frequency: 24
Vac, 50/60 Hz. Current Draw: 0.70A. CAPACITY: See Table 1.
TABLE 1: CAPACITY OF VRR300NRR301
Size
(Inlet x Outlet)
| Capacity (at pressure
drop)a 1 in. we| Minimum
Regulated Capacity|
Maximum
Regulated Capacity
---|---|---|---
1/2 x 1/2| 180 cu ft/hr
[5.1 cu m/hr]| 30 cu ft/hr
[0.8 cu m/hr]| 225 cu ft/hr
[6.4 cu m/hr]
1/2 x 3/4| 190 cu ft/hr
[5.4 cu m/hr]| 30 cu ft/hr
[0.8 cu m/hr]| 290 cu ft/hr
[8.2 cu m/hr]
3/4 x 3/4| 200 cu ft/hr
[5.7 cu m/hr]| 30 cu ft/hr
[0.8 cu m/hr]| 300 cu ft/hr
[8.5 cu m/hr]
a Capacity based on 1000 Btu/cu ft, 0.64 specific gravity natural gas at
1 in. WC pressure drop [37.3 MJ/cu m, 0.64 specific gravity natural gas at
0.25 kPa pressure drop.
Use conversion factors in Table 2 to convert capacities for other gasses.
TABLE 2—GAS CAPACITY CONVERSION FACTORS.
Gas | Specific Gravity | Multiply Listed Capacity By |
---|---|---|
Manufactured | 0.60 | 0.516 |
Mixed | 0.70 | 0.765 |
Propane | 1.53 | 1.62 |
TABLE 3—TEMPERATURE RANGES AND REGULATOR TYPES.
Model Number | Ambient Temperature Range | Regulator Type |
---|---|---|
VR8300A | 0° F to 175° F [-18° C to +79° C] | Standard-opening |
VR8300C | 0° F to 175° F [-18° C to +79° C] | Step-opening |
VR8300H | 0° F to 175° F [-18° C to +79° C] | Slow-opening |
VR8300K | -40° F to 175° F [-40° C to +79° C] | Slow-opening |
VR8300M | -40° F to 175° F [-40° C to +79° C] | Standard-opening |
VR8300P | -40° F to 175° F [-40° C to +79° C] | Step-opening |
VR8301 | 0° F to 175° F [-18° C to 79° C] | Standard-opening |
TABLE 4—FLANGE PART NUMBERS.
| | Part Number
---|---|---
Inlet/Outlet
Pipe Size| Flange
Type| Without
Hex
Wrench| With
Hex
Wrench
1/2 inch NPT
| Straight| 394599-6| 393690-16
Elbow| 394599-3| 393690-13
3/4 inch NPT
| Straight| 394599-4| 393690-14
Elbow| 394599-5| 393690-15
NOTE: Flange kits include one flange with attached 0-ring and fan
mounting screw.
APPROVALS:
American Gas Association Design Certificate: UP-70-69A.
Canadian Gas Association Design Certificate: UP-70-69A.
Australian Gas Association Certificate: Applied for.
Delta C: Applied for.
Installation
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.
- Check the ratings given in the instructions and on the product to assure the product is suitable for your application.
- Assure the installer is a trained, experienced service technician. 4. After installation is complete, use these instructions to check out product operation.
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Follow these warnings exactly.
- Disconnect the power supply before wiring to prevent electrical shock or equipment damage.
- To avoid the dangerous accumulation of fuel gas, turn off the gas supply at the appliance service valve before starting Installation, and perform a Gas Leak Test after completion of Installation.
- Do not bend the pilot tubing at the gas control or pilot burner after the compression fitting has been tightened, or gas leakage at the connection may result.
- Always install sediment traps in the gas supply line to prevent contamination of gas control.
- Do not force the gas control knob. Use only your hand to push down the reset button or turn the gas control knob. Never use any tools. If the gas control knob or reset button will not operate by hand, to replace the gas control, contact a qualified service technician. Force or attempted repair may result in fire or explosion.
CAUTION
Never apply a jumper across or short the valve coil terminals. This may burn
out the heat anticipator in the thermostat.
IMPORTANT: These gas controls are shipped with protective seals over
inlet and outlet tappings. Do not remove seals until ready to connect piping.
Follow the appliance manufacturer’s instructions if available; otherwise, use
the instructions provided below.
CONVERTING BETWEEN NATURAL AND LP GAS
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Do not use a gas control set for natural gas on LP gas or a gas control set
for LP gas on natural gas.
To convert a gas control from natural gas to LP gas or from LP gas to natural
gas, contact your Honeywell representative.
Standard- or slow-opening gas controls are converted from one gas to another
with a conversion kit (ordered separately).
Order part number 393691 to convert from natural to LP gas.
Order part number 394588 to convert from LP to natural gas.
Step-opening gas controls cannot be converted.
INSTALL ADAPTERS TO CONTROL
Install adapters on the gas control as follows:
Flanges
- Choose the appropriate flange for your application.
- Remove seal over gas control inlet or outlet.
- Assure the O-ring fits in the flange groove. If the O-ring is not attached or is missing, do not use a flange.
- With the O-ring facing gas control, align the screw holes on the gas control with the holes in the flange. Insert and tighten the screws provided with the flange. See Fig. 1.
Tighten the screws to 25-inch pounds of torque to provide a gas-tight seal.
Bushings:
- Remove the seal over the gas control inlet or outlet.
- Apply a moderate amount of good quality pipe com- pound to bushing, leaving two end threads bare. On LP installation, use a compound resistant to LP gas. Do NOT use Teflon tape.
- Insert bushing in gas control and thread pipe carefully into the bushing until tight.
Complete the instructions below for piping, installing control, connecting
pilot tubing, thermocouple, and wiring. Make certain the leak test you perform
on the control after completing the installation includes leak testing the
adapters and screws. If you use a wrench on the valve after flanges are
installed, use the wrench only on the flange, not on the control.
USING ADAPTERS TO SOLVE SWING RADIUS PROBLEMS
In some field service applications, it is difficult or impossible to thread
the gas control onto the gas supply pipe because of space limitations. This
problem can be resolved in many instances by using an adapter. The adapter is
installed on the end of the supply pipe in place of the gas control, following
the same precautions and instructions that are used for installing the gas
control. After the adapter is installed, the gas control is attached to the
adapter as outlined above. Note that using an adapter increases the overall
length of the gas control.
Fig. 1—Install flange to gas control.
CHOOSE GAS CONTROL LOCATION
Do not locate the gas control where it may be affected by steam cleaning,
high humidity, dripping water, corrosive chemicals, dust or grease
accumulation, or excessive heat.
To assure proper operation, follow these guidelines:
- Locate gas control in a well-ventilated area.
- Mount the gas control high enough above the cabinet bottom to avoid exposure to flooding or splashing water.
- Assure the ambient temperature does not exceed the ambient temperature ratings for each component.
- Cover the gas control if the appliance is cleaned with water, steam, or chemicals to avoid dust and grease accumulation.
- Avoid locating gas control where exposure to corrosive chemical fumes or dripping water is likely.
Locate the gas control in the appliance vestibule on the gas manifold. In
replacement applications, locate the gas control in the same location as the
old gas control.
Install Piping to Gas Control
All piping must comply with local codes and ordinances or with the National
Fuel Gas Code (ANSI Z223.1 NFPA No. 54), whichever applies. Tubing
installation must comply with approved standards and practices.
- Use new, properly reamed pipe free from chips. If tubing is used, assure the ends are square, deburred, and clean. All tubing bends must be smooth and without deformation.
- Run pipe or tubing to the gas control. If tubing is used, obtain a tube-to-pipe coupling to connect the tubing to the gas control.
- Install sediment trap in the supply line to the gas control. See Fig. 2.
Install Gas Control
- Mount the gas control 0-90 degrees, in any direction from the upright position of the gas control knob.
- Mount the gas control so gas flow 1s in the direction of the arrow on the bottom of the gas control.
- Thread pipe the amount shown in Table 5 for insertion into gas control.
IMPORTANT: Do not thread pipe too far. Valve distortion or malfunction may result if the pipe is inserted too deeply into the gas control. Refer to Fig. 3.
TABLE 5—NPT PIPE THREAD LENGTH IN IN.
** Pipe
Size| Thread Pipe This Amount| Maximum Depth
Pipe Can Be
Inserted Into
Control**
---|---|---
3/8| 9/16| 3/8
1/2| 3/4| 1/2
3/4| 13/16| 3/4 - Apply a moderate amount of good quality pipe compound (do not use Teflon tape) to pipe only, leaving two end threads bare. On LP installations, use compounds resistant to LP gas.
- Remove seals over the gas control inlet and outlet if necessary.
- Connect the pipe to the gas control inlet and outlet. Use a wrench on the square ends of the gas control. If an adapter is used, place the wrench on the adapter rather than onthe gas control. See Figs. 4 and 5.
Fig. 2—Sediment trap installation.
- ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.
- CAUTION: SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING THE END CAP TO PREVENT GAS FROM FILLING THE WORK AREA. TEST FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.
M3077
Fig. 3—Use a moderate amount of pipe compound. ****
Connect Pilot Gas Tubing
-
Cut the tubing to the desired length and bend as necessary for routing to the pilot burner.
CAUTION
Do not make sharp bends or deform the tubing. Do not bend tubing at gas control or pilot burner after compression fitting is tightened, because this may result in a gas leakage at the connection. -
Square off and remove burrs from the end of the tubing.
-
Unscrew the compression fitting from the pilot outlet (Fig. 4). Slip the compression fitting over the tubing and slide it out of the way.
NOTE: When replacing a gas control, cut offthe old compression fitting and replaceit with the new compression fitting provided on the gas control. Never use the old compression fitting because it may not provide a gas-tight seal. -
Push tubing into the pilot gas tapping on the outlet end of the control until it bottoms. While holding tubing all the way in, slide compression fitting into place and engage threads—turn until finger tight. Then tighten one more turn with a wrench. Do not over-tighten. See Fig. 6.
-
Connect the other end of the tubing to the pilot burner according to the pilot burner manufacturer’s instructions.
Connect Thermocouple
Connect thermocouple lead as shown in Fig. 7. See Tables 6 and 7. This is
an electrical connection and must be clean and dry. Never use pipe compound.
Tighten only 1/4 turn beyond finger tight to give good electrical continuity.
Do not over-tighten.
Fig. 7—Installing thermocouple to the power unit.
WIRING
CAUTION
Disconnect the power supply before making wiring connections to prevent
electrical shock or equipment damage.
Follow the wiring instructions furnished by the appliance manufacturer, if
available, or use the general instructions.
All wiring must comply with applicable electrical codes and ordinances.
- Check the power supply rating on the gas control and make sure it matches the available supply. Install transformer, thermostat, and other controls as required.
- Connect control circuit to gas control terminals. See Figs. 4, 8, and 9.
- Adjust thermostat heat anticipator to 0.70 ratings stamped on valve operator.
Fig. 8—VR8300 wiring connections for 24-volt control.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- DO NOT JUMP THESE TERMINALS. THIS SHORTS VALVE COIL MAY BURN OUT THE ANTICIPATOR IN THE THERMOSTAT.
- CONVENIENCE TERMINALS SERVE AS A TIE POINT ONLY. THEY ARE NOT INTERNALLY WIRED TO THE CONTROL CIRCUIT OR TO THE GROUND.
- OPTIONAL HIGH LIMIT. M8581
Fig. 9—VR8301 wiring connections for 24-volt control.
- POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
- DO NOT JUMP THESE TERMINALS. THIS SHORTS VALVE COIL MAY BURN OUT THE ANTICIPATOR IN THE THERMOSTAT.
- OPTIONAL HIGH LIMIT. M8580
TABLE 6—MAXIMUM LENGTH OF SUPPLEMENTARY LIMIT LEAD WIRES WHEN USING Q340A THERMOCOUPLE.
| Maximum Leadwire Length x 2 (Wires)
---|---
Thermocouple Length| AWG No. 14| AWG No. 16| AWG No. 18
Inches| Meters| Inches| Meters| Inches| Meters|
Inches| Meters
18| 0.5| 0.| 0.9| 22| 0.6| 13| 0.3
24| 0.6| 0.| 0.7| 18| 0.5| 11| 0.3
30| 0.8| 0.| 0.6| 15| 0.4| 9| 0.2
36| 0.9| 0.| 0.4| 11| 0.3| 6| 0.2
48| 1.2| DO NOT USE.
60| 1.5
TABLE 7—MAXIMUM LENGTH OF SUPPLEMENTARY LIMIT LEAD WIRES WHEN USING Q309A THERMOCOUPLE.
| Maximum Leadwire Length x 2 (Wires)
---|---
Thermocouple Length| AWG No. 14| AWG No. 16| AWG No. 18
Inches| Meters| Inches| Meters| Inches| Meters|
Inches| Meters
12| 0.3| 47| 1.| 30| 0.8| 18| 0.5
18| 0.5| 41| 1.0| 26| 0.7| 16| 0.4
24| 0.6| 35| 0.9| 22| 0.6| 14| 0.4
30| 0.8| 29| 0.8| 18| 0.5| 11| 0.3
36| 0.9| 23| 0.6| 15| OA| 9| 0.2
40| 1.0| 19| 0.5| 12| 0.3| 7| 0.2
48| 1.2| 11| 0.3| 7| 0.2|
60| 1.5| DO NOT USE.
Start-up and Checkout
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
- Do not force the gas control knob. Use only your hand to push down the reset button or turn the gas control knob. Never use any tools.
- If the gas control knob or reset button will not operate by hand, or if the reset button stays depressed after it is released, to replace the gas control call a qualified service technician.
GAS CONTROL KNOB SETTINGS
The gas control knob has three settings:
OFF: Prevents pilot and main burner gas flow.
PILOT: Permits pilot gas flow only. The gas control knob must be held
depressed or the thermocouple must be heated sufficiently to hold the safety
control valve open.
ON: Permits main burner and pilot gas flow. Gas control and thermostat
control main burner gas flow.
NOTE: Gas controls are shipped with the gas control knob in the ON
position.
PERFORM GAS LEAK TEST
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Check for gas leaks with rich soap and water solution any time work is done on
gas control.
GAS LEAK TEST
-
Paint all pipe connections upstream of the gas control with a rich soap and water solution. Bubbles indicate a gas leak.
-
If a gas leak is detected, tighten the pipe connection.
CAUTION
Stand clear while lighting the main burner to prevent injury caused by hidden gas leaks that could cause flashbacks in the appliance vestibule. -
Light the main burner.
-
With the main burner in operation, paint all pipe joints (including adapters) and gas control inlet and outlet with rich soap and water solution.
-
If another gas leak is detected, tighten adapter screws, joints, and pipe connections.
-
If the gas leak can not be stopped, turn the gas control knob clockwise to off
-
Replace the leaking part.
-
Perform the gas leak test.
LIGHT THE PILOT BURNER FLAME
- Turn the gas control knob clockwise to OFF. Wait five minutes to dissipate any unburned gas. Sniff around the appliance near the floor. Do not relight the pilot flame if you smell gas.
- Turn the gas control knob counterclockwise to PILOT. Push down and hold the gas control knob while lighting the pilot flame.
- Hold the gas control knob down for about one minute, then release it.
• If the pilot flame goes out, turn the gas control knob clockwise to OFF and repeat steps one through three.
• If the pilot flame remains lit, turn the gas control knob counterclockwise to ON.
ADJUST THE PILOT BURNER FLAME
The pilot flame should envelop 3/8 to 1 /2 in. [10 to 13 mm] of the
thermocouple tip. Refer to Fig. 10. To adjust the pilot flame:
- Remove the pilot adjustment cover screw. Refer to Fig. 5.
- Turn the inner adjustment screw clockwise , to decrease or counterclockwise n to increase the pilot flame.
- Be sure to replace the cover screw after adjustment and tighten it firmly.
LIGHT MAIN BURNER
Follow the appliance manufacturer’s instructions or set the thermostat setting
above room temperature to call for heat.
Fig. 10 Proper flame adjustment.
CHECK AND ADJUST GAS INPUT TO THE MAIN BURNER
CAUTION
-
Do not exceed the input rating stamped on the appliance nameplate, or the manufacturer’s recommended burner orifice pressure for the sizing orifice(s) used. Make sure the main burner’s primary air supply is properly adjusted for complete combustion (refer to the appliance manufacturer’s instructions).
-
WHEN CHECKING GAS INPUT BY CLOCKING THE GAS METER:
• Make sure that the only gas flow through the meter is that of the appliance being checked.
• Make sure that other appliances are turned off and that the pilot burners are extinguished (or deduct the gas consumption from the meter reading).
• Convert the flow rate to Btuh as described in the Gas Controls Handbook, (form 70-2602), and compare it to the Btuh input rating on the appliance nameplate. -
WHEN CHECKING GAS INPUT WITH A MANOMETER (PRESSURE GAUGE):
• Make sure the gas control knob is in the PILOT position before removing the outlet pressure tap plug to connect the manometer.
• Turn the gas control knob back to PILOT when removing the manometer and replacing the outlet pressure tap plug.
• Shut off the gas supply at the appliance service valve or, for LP gas, at the gas tank before removing the outlet pressure tap plug and before disconnecting the manometer and replacing the outlet pressure tap plug.
Standard-Opening and Slow-Opening Pressure Regulator
-
The gas control outlet pressure should match the mani-fold pressure listed on the appliance nameplate.
-
With the main burner operating, check the gas control flow rate using the meter clocking method or check the gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig. 4.
-
If necessary, adjust the pressure regulator to match the appliance rating. Refer to Table 8 or 9 for the factory set nominal outlet pressures and adjustment ranges.
a. Remove the pressure regulator adjustment cap screw.
b. Using a screwdriver, turn the inner adjustment screw clockwise to increase or counterclockwise. to decrease the main burner gas pressure.
c. Always replace the cap screw and tighten it firmly to be sure of proper operation. -
If the desired outlet gas pressure or gas flow rate cannot be achieved by adjusting the gas control, check the gas control inlet pressure using a manometer at the inlet pressure tap. If the inlet pressure is in the normal range (refer to Table 8 or 9), replace the gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.
Step-Opening Pressure Regulator
-
The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate.
-
With the main burner operating, check the gas control flow rate using the meter clocking method or check the gas pressure using a manometer connected to the gas control outlet pressure tap. Refer to Fig. 4.
-
If necessary, adjust the pressure regulator to match the appliance rating. Refer to Table 8 or 9 for factory set nominal outlet pressures and adjustment ranges.
a. Remove the pressure regulator adjustment cap screw.
b. Using a screwdriver, turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the main burner gas pressure.
c. Always replace the cap screw and tighten it firmly to safeguard proper operation. -
If desired outlet pressure or flow rate cannot be achieved by adjusting the gas control, check the inlet pressure using a manometer at the inlet pressure tap or upstream of the gas control. If the inlet pressure is in the normal range (refer to Table 8 or 9), replace the existing gas control. Otherwise, take the necessary steps to provide proper gas pressure to the gas control.
-
Carefully check the main burner light off at the step pres-sure. Be sure the main burner lights smoothly and without a flashback to the orifice and that all ports remain lit. Cycle the main burner several times, allowing at least 30 seconds between cycles for the regulator to resume the step function. Repeat after allowing the main burner to cool. Readjust the full rate outlet pressure, if necessary, to improve light-off characteristics.
TABLE 8—PRESSURE REGULATOR SPECIFICATION PRESSURES IN IN. WC.
Model| Nominal Inlet Pressure
Type of Gas| Nominal Inlet
Pressure Range| Outlet Pressure
---|---|---|---
Nominal Factory Setting| Setting Range
Step| Full Rate| Step| Full Rate
Standard,
Slow opening| Natural| 5.0 – 7.0| —| 3.5| —| 3.0 – 5.0
LP| 12.0 – 14.0| —| 11.0| —| 8.0 – 12.0
Step-opening| Natural| 5.0 – 7.0| 0.9| 3.5| —| 3.0 – 5.0
LP| 12.0- 14.0| 2.2| 11.0| —| 8.0 – 12.0
TABLE 9—PRESSURE REGULATOR SPECIFICATION PRESSURES IN kPa.
Model| Type of Gas| Nominal Inlet
Pressure Range| Outlet Pressure
---|---|---|---
Nominal Factory Setting| Setting Range
Step| Full Rate| Step| Full Rate
Standard,
Slow opening| Natural| 1.2 – 1.7| —| 0.9| —| 0.7 – 1.2
LP| 2.9| —| 2.7| —| 2.0 – 3.0
Step-opening| Natural| 1.2 – 1.7| 0.2| 0.9| —| 0.7 – 1.2
LP| 2.9 – 3.9| 0.9| 2.7| —| 2.0 – 3.0
CHECK SAFETY SHUTDOWN PERFORMANCE
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Perform the safety shutdown test any time work is done on a gas system.
- Place the gas control knob in the PILOT position. The main burner should go off and the pilot should remain lit.
- Extinguish pilot flame. Pilot gas flow should stop within 2-1/2 minutes. Safety shutoff of pilot gas proves complete shutdown because safety shutoff valve prevents main burner and pilot gas flow.
- Relight the pilot burner and operate the system through one complete cycle to make sure all controls operate properly.
Maintenance
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR DEATH
Improper cleaning or reassembly can cause gas leakage. When cleaning, be sure
that the control is reassembled properly and perform a gas leak test.
Regular preventive maintenance is important in applications such as in the
commercial cooking and agricultural and industrial industries that place a
heavy load on system controls, because:
- In many such applications, particularly commercial cooking, the equipment operates 100,000 to 200,000 cycles per year. Such heavy cycling can wear out the gas control in one to two years.
- Exposure to water, dirt, chemicals, and heat can damage the gas control and shut down the control system.
The maintenance program should include regular checkout of the gas control as outlined in the Start-up and Checkout section, and check out the control system as described in the appliance manufacturers’ literature. Maintenance frequency must be determined individually for each application. Some considerations are:
- Cycling frequency. Appliances that may cycle 100,000 times annually should be checked monthly.
- Intermittent use. Appliances that are used seasonally should be checked before shutdown and again before the next use.
- The consequence of unexpected shutdown. Where the cost of an unexpected shutdown would be high, the system should be checked more often.
- Dusty, wet, or corrosive environment. Since these environments can cause the gas control to deteriorate more rapidly, the system should be checked more often.
The gas control should be replaced if:
- It does not perform properly on checkout or troubleshooting.
- The gas control knob is hard to turn or push down, or it fails to pop back up when released.
- The gas control is likely to have operated for more than 200,000 cycles.
Service
WARNING
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY OR DEATH
Do not disassemble the gas control; it contains no replaceable components.
Attempted disassembly or repair may damage the gas control.
CAUTION
Do not apply a jumper across or short the valve coil terminals. Doing so
can burn out the heat anticipator in the thermostat.
IMPORTANT: Allow 60 seconds after shutdown before reenergizing the step-
opening model to assure light off at step pressure.
IF THE PILOT BURNER FLAME WILL NOT LIGHT
- Assure the main gas supply valve is open and the pilot gas supply line is purged of air.
- Attempt to light pilot burner flame following procedures in the Lighting the Pilot Burner Flame section. If the pilot burner flame still will not light:
a. Check the pilot gas adjustment screw. If closed, readjust the pilot flame. Refer to Adjust the Pilot Burner Flame section.
b. Perform the Gas Leak Test at the compression fitting. If a gas leak is detected, replace the old compression fitting or tighten the newly installed one. Refer to Fig. 4.
c. Assure that the pilot burner tubing or pilot burner orifice is not clogged.
IF THE PILOT BURNER FLAME GOES OUT WHEN THE GAS CONTROL KNOB IS RELEASED
- Assure the gas control knob is held for at least one minute to allow the thermocouple time to heat.
- Check the pilot burner flame adjustment. Refer to Adjust the Pilot Burner Flame section.
- Check the wiring between the thermocouple and the gas control valve operator.
- Assure thermocouple connection to the power unit is tightened one-fourth turn beyond finger tight.
- If the pilot burner flame still goes out, measure the open and closed thermocouple output voltage. Compare it to the acceptable range charts in the thermocouple specifications or in the Gas Controls Handbook. Replace the thermocouple if voltages are outside the acceptable range.
- Check the power unit resistance. If above 11 ohms, replace the gas control.
IF THE MAIN BURNER WILL NOT COME ON WITH A CALL FOR HEAT
-
Be sure the gas control knob is in the ON position.
-
Adjust the thermostat several degrees above room temperature.
-
Use an ac voltmeter to measure the voltage across terminals TH and TR or MV/PV and MV. If:
a. No voltage is present, check the control circuit for proper operation.
b. 24 Vac is present, but the first operator did not click open, check for excessive inlet gas pressure. If the inlet gas pressure is correct, replace the gas control. -
Measure the open and closed thermocouple output voltages and compare them to the acceptable range charts in the thermocouple specifications or in the Gas Controls Handbook. Replace the thermocouple if voltages are outside the acceptable range.
-
Measure the open and closed thermocouple output voltages and compare them to the acceptable range charts in the thermocouple specifications or in the Gas Controls Handbook. Replace the thermocouple if voltages are outside the acceptable range.
IF THE MAIN BURNER IS OVERFIRING
Adjust the gas control pressure regulator to the correct pressure. If the
regulator cannot be adjusted and supply the pressure is in the normal range,
replace the gas control.
INSTRUCTIONS TO THE HOMEOWNER
CAUTION
FIRE OR EXPLOSION HAZARDS CAN CAUSE PROPERTY DAMAGE, SEVERE INJURY, OR
DEATH
Follow these warnings exactly:
-
The pilot burner flame must be lit manually. Follow these instructions exactly.
-
Before lighting the pilot burner flame, smell around the appliance for gas. Be sure to smell next to the floor because LP gas is heavier than air.
-
IF YOU SMELL GAS:
• Turn off the gas supply at the appliance service valve. On LP gas systems, turn off the gas supply at the gas tank.
• Do not light any appliances in the house.
• Do not touch electrical switches or use the phone.
• Leave the building and use a neighbor’s phone to call your gas supplier.
• If you cannot reach your gas supplier, call the fire department. -
Do not force the gas control knob. Use only your hand to push down or turn the gas control knob. Never use any tools. If the gas control knob will not operate by hand, the gas control should be replaced by a qualified service technician. Force or attempted repair can result in a fire or explosion.
-
Replace the gas control in case of any physical damage, tampering, bent terminals, missing or broken parts, stripped threads, evidence of exposure to heat, or if flooded by water.
IMPORTANT: Follow the operating instructions provided by the manufacturer
of your heating appliance. The information below will be of assistance in a
typical gas control application, but the specific controls used and the
procedures outlined by the manufacturer or your appliance may differ and
require special instructions.
LIGHTING THE PILOT BURNER FLAME
Stop: Read the warnings above.
The pilot burner flame must be lit manually. If the pilot burner flame has
gone out, follow these instructions exactly:
-
Set the thermostat to its lowest setting.
-
Disconnect all electric power to the appliance.
-
Remove the gas control access panel.
-
Push in the gas control knob slightly and turn clockwise to OFF.
NOTE: The gas control knob can not be turned from PILOT to OFF unless it is pushed in slightly. Do not force the gas control knob. -
Wait five minutes to clear out any unburned gas. If you then smell gas, STOP! Follow step 3 in the Warnings at the beginning of the Instructions to the Homeowner section. If you do not smell gas, continue with the next step.
-
Remove the pilot burner access panel located below and behind the gas control.
-
Find the pilot burner by following the metal tube from the gas control. The pilot burner is located between the two burner tubes behind the pilot burner access panel.
-
Turn the gas control knob counterclockwise to PILOT.
-
Push and hold the gas control knob all the way in. Immediately light the pilot burner flame with a match and continue holding the gas control knob in for one minute after the pilot burner flame is lit.
-
Release the gas control knob and it will pop back up. The pilot burner flame should remain lit. If the pilot burner flame goes out, repeat steps one through ten.
• If the gas control knob does not pop up when released, stop immediately and call your service technician or gas supplier.
• If the pilot flame will not stay lit after several tries, turn the gas control knob to OFF and call your service technician or gas supplier. -
Turn the gas control knob counterclockwise to ON.
-
Replace the pilot burner access panel.
-
Replace the gas control access panel.
-
Reconnect all electric power to the appliance.
-
Set the thermostat to the desired setting.
TURNING OFF THE APPLIANCE
VACATION SHUTDOWN: Set the thermostat to the desired room temperature while
you are away.
COMPLETE SHUTDOWN: Push the gas control knob in slightly and turn clockwise to
OFF. Do not force. The appliance will completely shut off. Follow the Lighting
The Pilot Burner Flame procedures to resume normal operation.
Helping You Control Your World
Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Printed in the U.S.A
Home and Building Control
Honeywell Limited—Honeywell Limit &
740 Ellesmere Road
Scarborough, Ontario
M1P 2V9
QUALITY IS KEY
www.honeywell.com
J.H.
Rev. 9-94
©Honeywell Inc. 1994
Form Number 69-0624-2
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>