Danfoss OPTC2/C8 VACON NXP Air Cooled Installation Guide
- June 16, 2024
- Danfoss
Table of Contents
- OPTC2/C8 VACON NXP Air Cooled
- Product Information: Vacon NX AC Drives – Modbus/N2 Option
- Specifications
- General
- RS-485 Option Board Technical Data
- Installation of Vacon NX RS-485 Board
- Commissioning
- Fault Tracking
- Modbus
- Start-up Test
- Q: Where should I install the RS-485 Option Board?
- Q: How can I configure the fieldbus board parameters?
- Q: What should I do if a fault occurs with the frequency
OPTC2/C8 VACON NXP Air Cooled
Product Information: Vacon NX AC Drives – Modbus/N2 Option
Board
Specifications
- Model: Vacon NX
- Product Type: AC Drives
- Option Board: OPTC2/C8 Modbus/N2
- Document Code: DPD00899A
- Date: 19.01.2012
General
The Vacon NX frequency converters can be connected to the RS-485
bus using the Modbus/N2 Option Board. This allows the frequency
converter to be controlled, monitored, and programmed from a host
system. Instead of using I/O, information can be sent and received
through the fieldbus connection.
If you have purchased the RS-485 Option Board separately, please
ensure it is installed in slot E on the control board of the
frequency converter.
WARNING! When the frequency converter is
connected to the power source, internal components and circuit
boards are at high potential. This voltage is extremely dangerous
and may cause death or severe injury if contact is made.
RS-485 Option Board Technical Data
The RS-485 Option Board provides the following technical
data:
Connections| Communications Interface| Data Transfer Method| Transfer Cable|
Electrical Isolation
---|---|---|---|---
OPTC2: Pluggable connector (5.08mm)
OPTC8: 9-pin DSUB connector (female)| RS-485, half-duplex| Modbus RTU
Metasys N2| Twisted pair (1 pair and shield)| 500 VDC
Installation of Vacon NX RS-485 Board
Refer to the user manual for detailed instructions on how to
install the RS-485 Option Board on the Vacon NX frequency
converter. Ensure the board is installed in slot E on the control
board.
Commissioning
During commissioning, you need to configure the fieldbus board
parameters. Refer to Chapter 5.1 of the user manual for detailed
instructions on how to set up the fieldbus parameters.
Fault Tracking
If a fault occurs with the frequency converter, refer to
Appendix 1 of the user manual for fault tracking information.
Modbus
Start-up Test
To perform a start-up test using Modbus:
-
Choose Fieldbus (Bus/Comm) as the active control place (see
Vacon NX User’s Manual, Chapter 7.3.3). -
Set FB Control Word (MBaddr 42001) value to 1hex.
-
Ensure the frequency converter status is RUN.
-
Set FB Speed Reference (MBaddr 42003) value to 5000
(=50.00%). -
The actual value should be 5000 and the frequency converter
output frequency should be 25.00 Hz. -
Set FB Control Word (MBaddr 42001) value to 0hex.
-
Ensure the frequency converter status is STOP.
-
If FB Status Word (Addr 42101) bit 3 = 1, the status of the
frequency converter is FAULT.
FAQ
Q: Where should I install the RS-485 Option Board?
A: The RS-485 Option Board should be installed in slot E on the
control board of the Vacon NX frequency converter.
Q: How can I configure the fieldbus board parameters?
A: Refer to Chapter 5.1 of the user manual for detailed
instructions on how to set up the fieldbus parameters during
commissioning.
Q: What should I do if a fault occurs with the frequency
converter?
A: Refer to Appendix 1 of the user manual for fault tracking
information.
vacon nx
ac drives
optc2/c8
modbus/n2 option board
user manual
INDEX
Document code: DPD00899A Date 19.01.2012
1. GENERAL …………………………………………………………………………………………………………… 3
2. RS-485 OPTION BOARD TECHNICAL DATA ……………………………………………………………… 4 2.1 General ……………………………………………………………………………………………………………………….. 4
3. RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS …………………………………………… 5 3.1 RS-485 OPTC2 option board …………………………………………………………………………………………… 5 3.2 RS-485 OPTC8 option board …………………………………………………………………………………………… 6 3.3 Grounding ……………………………………………………………………………………………………………………. 7 3.3.1 Grounding by clamping the cable to the converter frame………………………………………….7 3.3.2 Grounding only one point on the net……………………………………………………………………….9 3.3.3 Grounding jumper X1 ………………………………………………………………………………………….10 3.4 Bus terminal resistors…………………………………………………………………………………………………. 11 3.5 Bus Biasing ………………………………………………………………………………………………………………… 12 3.6 LED indications …………………………………………………………………………………………………………… 13
4. INSTALLATION OF VACON NX RS-485 BOARD ……………………………………………………….. 14
5. COMMISSIONING……………………………………………………………………………………………….. 16 5.1 Fieldbus board parameters ………………………………………………………………………………………….. 16
6. MODBUS…………………………………………………………………………………………………………… 19 6.1 Modbus RTU protocol, introduction……………………………………………………………………………….. 19 6.1.1 Supported functions……………………………………………………………………………………………21 6.1.2 Exception responses…………………………………………………………………………………………..23 6.2 Modbus interface ………………………………………………………………………………………………………… 25 6.2.1 Modbus registers……………………………………………………………………………………………….25 6.2.2 Process data ……………………………………………………………………………………………………..25 6.2.3 Process data in ………………………………………………………………………………………………….26 6.2.4 Process data out ………………………………………………………………………………………………..27 6.2.5 Parameters ……………………………………………………………………………………………………….30 6.2.6 Actual values……………………………………………………………………………………………………..30 6.2.7 Example messages…………………………………………………………………………………………….31 6.3 Start-up test ………………………………………………………………………………………………………………. 33
7. METASYS N2……………………………………………………………………………………………………… 34 7.1 Metasys N2 Protocol Introduction …………………………………………………………………………………. 34 7.2 Metasys N2 interface …………………………………………………………………………………………………… 34 7.2.1 Analogue Input (AI) …………………………………………………………………………………………….34 7.2.2 Binary Input (BI) …………………………………………………………………………………………………34 7.2.3 Analogue Output (AO)………………………………………………………………………………………….35 7.2.4 Binary Output (BO) ……………………………………………………………………………………………..35 7.2.5 Internal Integer (ADI) ………………………………………………………………………………………….35 7.3 N2 POINT MAP……………………………………………………………………………………………………………. 36 7.3.1 Analogue Inputs (AI)……………………………………………………………………………………………36 7.3.2 Binary Inputs (BI) ……………………………………………………………………………………………….37 7.3.3 Analogue Outputs (AO)………………………………………………………………………………………..37 7.3.4 Binary Outputs (BO) ……………………………………………………………………………………………38 7.3.5 Internal Integers (ADI) ………………………………………………………………………………………..38
8. FAULT TRACKING………………………………………………………………………………………………. 39 APPENDIX 1 ………………………………………………………………………………………………………………………….. 40
general
vacon · 3
1. GENERAL Instead of sending and receiving information to and from frequency
converters through I/O, you can connect them to a fieldbus.
Vacon NX frequency converters can be connected to the RS-485 bus using a
fieldbus board. The converter can then be controlled, monitored and programmed
from the host system.
If you purchase your RS-485 Option Board separately, please note that it shall
be installed in slot E on the control board of the frequency converter.
WARNING!
Internal components and circuit boards are at high potential when the frequency converter is connected to the power source. This voltage is extremely dangerous and may cause death or severe injury if you come into contact with it.
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
1
4 · vacon
technical data
2. RS-485 OPTION BOARD TECHNICAL DATA
2.1 General
Connections Communications
Interface
Data transfer method Transfer cable Electrical isolation Modbus RTU Metasys N2
Environment Safety
Baud rate Addresses Ambient operating temperature Storing temperature Humidity Altitude Vibration
Table 1. RS-485 technical data
OPTC2: Pluggable connector (5.08mm) OPTC8: 9-pin DSUB connector (female)
RS-485, half-duplex
Twisted pair (1 pair and shield) 500 VDC As described in document “Modicon
Modbus Protocol Reference Guide”
Find it for example at: http://public.modicon.com/
As described in Metasys N2 System Protocol Specification 300, 600, 1200, 2400,
4800, 9600, 19200 and 38400 kbaud 1 to 247 10°C…55°C
40°C…60°C
<95%, no condensation allowed Max. 1000 m 0.5 G at 9…200 Hz Fulfils EN50178
standard
2
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
layout and connections
vacon · 5
3. RS-485 FIELDBUS BOARD LAYOUT AND CONNECTIONS
Vacon RS-485 Fieldbus Board is connected to the fieldbus through either a
5-pin pluggable bus connector (board OPTC2) or a 9-pin female sub-D-connector
(board OPTC8). The communication with the control board of the frequency
converter takes place through the standard Vacon Interface Board Connector.
3.1 RS-485 OPTC2 option board
1
2
3 4
X4
5
X1
Bus connector
Jumpers
Grounding plate
Interface board connector
Figure 1. Vacon RS-485 option board OPTC2
Signal
Connector
Description
NC*
1*
No connection
VP
2
Supply voltage plus (5V)
RxD/TxD N
3
Receive/Transmit data A
RxD/TxD P
4
Receive/Transmit data B
DGND
5
Data ground (reference potential for VP)
*You can use this pin (1) to bypass the cable shield to the next slave
Table 2. OPTC2 bus connector signals
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
3
6 · vacon
3.2 RS-485 OPTC8 option board
5
4
3
2
1
9
8
7
6
layout and connections
X4
X1
Bus connector
Jumpers
Grounding plate
Figure 2. Vacon RS-485 option board OPTC8
Interface board connector
Signal
Connector Description
Shield
1
Cable shield
RxD/TxD-N
3
Receive/ A
DGND
5
Data ground (reference potential for VP)
VP
6
Supply voltage plus (5V)
RxD/TxD-P
8
Receive/ Transmit data/ B
Table 3. OPTC8 bus connector signals
3
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
layout and connections
vacon · 7
3.3 Grounding
3.3.1 Grounding by clamping the cable to the converter frame This manner of
grounding is the most effective and especially recommended when the distances
between the devices are relatively short or if the device is the last device
on the net.
Note: Normally, the option board has already been installed in slot D or slot
E of the control board. It is not necessary to detach the whole board for the
grounding of the bus cable shield. Just detach the terminal block.
1 Strip about 5 cm of the cable and cut off the grey cable shield. Remember to
do this for both bus cables (except for the last device). See pictures below.
2 Leave no more than 1 cm of the cable outside the terminal block and strip
the data cables at about 0.5 cm to fit in the terminals. See pictures below.
Note: Do this for both bus cables.
Strip this part Cut here
Figure 3.
1 2 3 4 5
A
B
Figure 4.
3 Insert the data cables of both cables into terminals #3 (Line B) and #4
(Line A).
4 Strip the cable at such a distance from the terminal that you can fix it to the frame with the grounding clamp. See
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
3
8 · vacon Figure 5.
layout and connections
3
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
layout and connections
vacon · 9
3.3.2 Grounding only one point on the net
In this manner of grounding, the shield is connected to ground only at the
last device on the net in the same way as described in chapter 3.3.1. Other
devices of the net just pass the shield. We recommend you to use an Abico
connector to fit the shields into the terminal.
1 Strip about 5 cm of the cable and cut off the grey cable shield. Remember to
do this for both bus cables (except for the last device).
2 Leave no more than 1 cm of the cable outside the terminal block and strip
the data cables at about 0.5 cm to fit in the terminals. See Figure 6. Note:
Do this for both bus cables.
1 2 3 4 5
Shield
A
B
Figure 6. 3 Fix both the cables on the frame with the clamp. See Figure 7.
Figure 7. 24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
3
10 · vacon
layout and connections
3.3.3 Grounding jumper X1
The Grounding jumper X1 on the OPTC8 is used for grounding selection. If
position ON is selected it means that the D-sub connector PIN1 is connected
directly to ground. Selection of position OFF means that PIN1 is connected to
ground via an RC-filter. Jumper X1 has no effect on OPTC2.
5
432
1
9
876
ON
OFF
X4
X1 Figure 8. Grounding jumper X1
3
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
layout and connections
vacon · 11
3.4 Bus terminal resistors
If Vacon is the last device of the fieldbus line the bus termination must be
set. Use jumper X4 (ON position) or external termination resistors (e.g. in
DSUB-9 connector). See Figure 9.
5
432
1
9
876
ON
OFF
X4
X1 Figure 9. Using jumper X4 to set the bus termination.
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
3
12 · vacon
layout and connections
3.5 Bus Biasing
Bus biasing is required to ensure faultless communication between devices at
RS-485 bus. Bus biasing makes sure that the bus state is at proper potential
when no device is transmitting. Without biasing, faulty messages can be
detected when the bus is in idle state. RS-485 bus state should be neather
+0,200..+7V or 0,200..-7V. Illegal bus state is <200mV..-200mV.
Number of nodes Bias resistance
2-5
1.8 kohm
5-10
2.7 kohm
11-20
12 kohm
21-30
18 kohm
31-40
27 kohm
Table 4. Bias resistor size vs number of node
Fail safe biasing in OPTC2 option board
Connect resistor biasing resistors between pins #2 and #4 as well as pins #3
and #5 as shown in picture.
1
2
A DATA-
3
B DATA+
4
5
5
Matters related to this are discussed in the application note Failsafe Biasing of Differential Buses (an847.pdf) published by National Semiconductor (www.national.com).
3
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
layout and connections
vacon · 13
3.6 LED indications
The two LED indications next to the connector show the present statuses of the
RS-485 board (yellow) and the Fieldbus Module (green).
Yellow Green
1
2
3 4
X4
5
X1
Figure 10. LED indications on the RS-485 board
RS-485 board status LED (BS) YELLOW
LED is: OFF
Meaning: Option board not activated
ON
Blinking fast (once/sec) Blinking slow (once/5 secs)
Option board in initialisation state waiting for activation command from the frequency converter Option board is activated and in RUN state · Option board is ready for external communication Option board is activated and in FAULT state · Internal fault of option board
Fieldbus status LED (FS)
GREEN
LED is: OFF
ON
Blinking fast (once/sec) Blinking slow (once/5 secs)
Meaning: Fieldbus module is waiting for parameters from the frequency
converter · No external communication Fieldbus module is activated ·
Parameters received and module activated · Module is waiting for messages from
the bus Module is activated and receiving messages from the bus
Module is in FAULT state · No messages from Master within the watchdog time ·
Bus broken, cable loose or Master off line
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
3
14 · vacon
4. INSTALLATION OF VACON NX RS-485 BOARD
A Vacon NX frequency converter
installation
B Remove the cable cover.
C Open the cover of the control unit.
4
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
installation
vacon · 15
D Install RS-485 option board in slot E on the control board of the frequency
con-
verter. Make sure that the grounding plate (see below) fits tightly in the
clamp.
1
2
3 4
X4
5
X1
E Make a sufficiently wide opening for
your cable by cutting the grid as wide as necessary.
F Close the cover of the control unit and
the cable cover.
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
4
16 · vacon
modbus
5. COMMISSIONING
READ FIRST CHAPTER 8 ‘COMMISSIONING’ IN VACON NX USER’S MANUAL (Document nr.
ud00701, please visit http://www.vacon.com/925.html).
Note! You must select Fieldbus as the active control place, if you wish to
control the frequency converter through fieldbus. See Vacon NX User’s Manual,
Chapter 7.3.3.1.
5.1 Fieldbus board parameters
The Vacon RS-485 board is commissioned with the control keypad by giving
values to appropriate parameters in menu M7 (for locating the expander board
menu see Vacon NX User’s Manual, Chapter 7).
Expander board menu (M7) The Expander board menu makes it possible for the
user 1) to see what expander boards are connected to the control board and 2)
to reach and edit the parameters associated with the expander board.
Enter the following menu level (G#) with the Menu button right. At this level,
you can browse through slots A to E with the Browser buttons to see what
expander boards are connected. On the lowermost line of the display you also
see the number of parameter groups associated with the board.
If you still press the Menu button right once you will reach the parameter
group level where there are two groups: Editable parameters and Monitored
values. A further press on the Menu button right takes you to either of these
groups.
RS-485 parameters
To commission the RS-485 board, enter the level P7.5.1.# from the Parameters
group (G7.5.1). Give desired values to all RS-485 parameters (see Figure 11
and Table 5).
I/Oter m
RE ADY
Expander Board
G1G5
I/Oter m
RE ADY
Slave address
126
I/Oter m
RE ADY
NXOPTC5
G1G2
I/Oter m
RE ADY
Slave address
126
I/Oter m
RE ADY
Parameters
P1P4
CHANGE VALUE enter CONFIRM CHANGE
Figure 11. Changing the RS-485 board commissioning parameter values
5
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
commissioning
vacon · 17
Name 1 COMMUNICATION
PROTOCOL 2 SLAVE ADDRESS 3 BAUD RATE
Default 1 1
6
4 PARITY TYPE 0
5 COMMUNICATION TIMEOUT
20
6 OPERATE MODE
1
Table 5. RS-485 parameters
Range 1 Modbus RTU 2 N2 1…247 1 300 baud 2 600 baud 3 1200 baud 4 2400 baud 5 4800 baud 6 9600 baud 7 19200 baud 8 38400 baud 0 None 1 Even 2 Odd 0–OFF 1–300 s 1 Normal
Description Protocol
Communication speed When N2 protocol is used Baudrate must be set to 9600.
Describes what kind of parity checking is used. When N2-protocol is used
Parity type must be set to 0 = None See chapter Communication timeout below
Reserved for later use
The parameters of every device must be set before connecting to the bus. Especially the parameters Communication Protocol, Slave Address and Baud Rate must be the same as in the master configuration.
Communication timeout
The RS-485 board initiates a communication error if communication is broken
for as long as defined by the Communication Timeout. Communication Timeout is
disabled when given the value 0.
Communication status
To see the present status of the RS-485 fieldbus, enter the Comm.Status page
from Monitor menu (G7.5.2). See Figure 12 and Table 6 below.
I/Oter m
RE ADY
Monitor
V1V1
I/Oter m
RE ADY
Comm. status
0.841
Figure 12. Communication status
Good messages Error messages
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
5
18 · vacon
Good messages 0…999 Number of messages received without
communication errors Error messages
0…64 Number of messages received with CRC or parity errors
Table 6. RS-485 message indications
modbus
5
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 19
6. MODBUS
6.1 Modbus RTU protocol, introduction
The MODBUS protocol is an industrial communications and distributed control
system to integrate PLCs, computers, terminals, and other monitoring, sensing,
and control devices. MODBUS is a Master-Slave communications protocol. The
Master controls all serial activity by selectively polling one or more slave
devices. The protocol provides for one master device and up to 247 slave
devices on a common line. Each device is assigned an address to distinguish it
from all other connected devices.
The MODBUS protocol uses the master-slave technique, in which only one device
(the master) can initiate a transaction. The other devices (the slaves)
respond by supplying the request data to the master, or by taking the action
requested in the query. The master can address individual slaves or initiate a
broadcast message to all slaves. Slaves return a message (`response’) to
queries that are addressed to them individually. Responses are not returned to
broadcast queries from the master.
A transaction comprises a single query and single response frame or a single
broadcast frame. The transaction frames are defined below.
Master’s message
START ADDRESS FUNCTION
DATA
CRC END
Slave response
START ADDRESS FUNCTION
DATA
CRC END
Figure 13. The basic structure of a Modbus frame
Valid slave device addresses are in the range of 0 … 247 decimal. The
individual slave devices are assigned addresses in the range of 1 … 247. A
master addresses a slave by placing the slave address in the address field of
the message. When the slave sends its response, it places its own address in
this address field of the response to let the master know which slave is
responding.
The function code field of a message frame contains two characters (ASCII) or
eight bits (RTU). Valid codes are in the range of 1 … 255 decimal. When a
message is sent from a master to a slave device the function code field tells
the slave what kind of action to perform. Examples are to read the ON / OFF
states of a group of discrete coils or inputs; to read the data contents of a
group of registers; to
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
20 · vacon
modbus
read the diagnostic status of the slave; to write to designated coils or
registers; or to allow loading, recording, or verifying the program within the
slave.
When the slave responds to the master, it uses the function code field to
indicate either a normal (error-free) response or that some kind of error
occurred (called an exception response). For a normal response, the slave
simply echoes the original function code. For an exception response, the slave
returns a code that is equivalent to the original function code with its most
significant bit set to a logic 1.
The data field is constructed using sets of two hexadecimal digits, in the
range of 00 to FF hexadecimal. These can be made from a pair of ASCII
characters, or from one RTU character, according to the network’s serial
transmission mode.
The data field of messages sent from a master to slave devices contains
additional information which the slave must use to take the action defined by
the function code. This can include items like discrete and register
addresses, the quantity of items to be handled, and the count of actual data
bytes in the field. If no error occurs, the data field of a response from a
slave to a master contains the data requested. If an error occurs, the field
contains an exception code that the master application can use to determine
the next action to be taken.
Two kinds of checksum are used for standard Modbus networks. The error
checking field contents depend upon the transmission method that is being
used.
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 21
6.1.1 Supported functions
Function Code Description
Address range
03
Read Holding Registers Applies to all addresses
04
Read Input Registers Applies to all addresses
06
Write Single Register Applies to all addresses
16
Write Multiple Regis- Applies to all addresses
ters
Note: Broadcasting can be used with codes 06 and 16
Table 7. Supported messages
6.1.1.1 Read Holding Registers
The query message specifies the starting register and the quantity of
registers to be read. Registers are addressed starting with zero, i.e.
registers 1 to 16 are addressed as 0 to 15.
Example of a request to read registers 42001-42003 from Slave device 1:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of points HI No. of points LO ERROR CRC HI CHECK CRC
LO
01 hex 03 hex 07 hex D0 hex 00 hex 03 hex 05 hex 46 hex
Slave address 1 hex (= 1) Function 03 hex (= 3) Starting address 07d0 hex (=
2000)
Number of registers 0003 hex (= 3)
CRC field 0546 hex (= 1350)
6.1.1.2 Read Input Registers
The query message specifies the starting register and the quantity of
registers to be read. Registers are addressed starting with zero, i.e.
registers 1 to 16 are addressed as 0 to 15.
Example of a request to read registers 32001 from Slave device 1:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of points HI No. of points LO ERROR CRC HI CHECK CRC
LO
01 hex 04 hex 07 hex D0 hex 00 hex 01 hex 31 hex 47 hex
Slave address 1 hex (= 1) Function 04 hex (= 4) Starting address 07d0 hex (=
2000)
Number of registers 0003 hex (= 3)
CRC field 3147 hex (= 12615)
6.1.1.3 Preset Single Register
The query message specifies the register reference to be preset. Registers are
addressed starting with zero, i.e. register 1 is addressed as 0.
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
22 · vacon
modbus
Example of a request to preset register 42001 to 00001hex in Slave device 1:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO Data HI Data LO ERROR CRC HI CHECK CRC LO
01 hex 06 hex 07 hex D0 hex 00 hex 01 hex 48 hex 87 hex
Slave address 1 hex (= 1) Function 04 hex (= 4) Starting address 07d0 hex (=
2000)
Data = 0001 hex (= 1)
CRC field 4887 hex (= 18567)
6.1.1.4 Preset Multiple Registers
The query message specifies the register references to be preset. Registers
are addressed starting with zero, i.e. register 1 is addressed as 0.
Example of a request to preset two registers starting at 42001 to 0001hex and 0010hex in Slave device 1:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of registers HI No. of registers LO Byte count Data HI
Data LO Data HI Data LO ERROR CRC HI CHECK CRC LO
01 hex 10 hex 07 hex D0 hex 00 hex 02 hex 04 hex 00 hex 01 hex 00 hex 10 hex 88 hex CF hex
Slave address 1 hex (= 1) Function 10 hex (= 16) Starting address 07d0 hex (=
2000)
Number of registers 0002 hex (= 2)
Byte count 04 hex (= 4) Data 1 = 0001 hex (= 1) Data 2 = 0010 hex (= 16)
CRC field 88CF hex (= 35023)
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 23
6.1.2 Exception responses
Error response is given when the Slave receives a message without
communication errors, but cannot handle it. Examples of such messages are an
incorrect register address, data value or unsupported message. No answer is
given if a CRC or parity error occurs or the message is a broadcast message.
Code Function
01
ILLEGAL FUNCTION
02
ILLEGAL DATA AD-
DRESS
03
ILLEGAL DATA VALUE
06
SLAVE DEVICE BUSY
Table 8. Exception response codes
Description
The message function requested is not recognized by the slave.
The received data address is not an allowable address for the slave
The received data value is not an allowable value for the slave.
The message was received without error but the slave was engaged in processing
a long duration program command.
Example of an exception response
In an exception response, the Slave sets the most-significant bit (MSB) of the
function code to 1. The Slave returns an exception code in the data field.
Command Master Slave:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of registers HI No. of registers LO ERROR CRC HI CHECK
CRC LO
01 hex 04 hex 17 hex 70 hex 00 hex 05 hex 34 hex 66 hex
Slave address 1 hex (= 1) Function 4 hex (= 4) Starting address 1770 hex (=
6000)
Invalid number of registers 0005 hex (= 5)
CRC field 3466 hex (= 13414)
Message frame: 01 04 17 70 00 05 34 66
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
24 · vacon
modbus
Exception response.
Answer Slave Master:
ADDRESS FUNCTION ERROR CODE ERROR CRC HI CHECK CRC LO
01 hex 14 hex 02 hex AE hex
C1 hex
Slave address 1 hex (= 1) Most significant bit set to 1 Error code 02 => Illegal Data Address CRC field AEC1 hex (= 44737)
Reply frame: 01 14 02 AE C1
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 25
6.2 Modbus interface
Features of the Modbus-Vacon NX interface: · Direct control of Vacon NX ( e.g.
Run, Stop, Direction, Speed reference, Fault reset) · Full access to all Vacon
NX parameters · Monitor Vacon NX status (e.g. Output frequency, Output
current, Fault code)
6.2.1 Modbus registers
The Vacon variables and fault codes as well as the parameters can be read and
written from Modbus. The parameter addresses are determined in the
application. Every parameter and actual value have been given an ID number in
the application. The ID numbering of the parameter as well as the parameter
ranges and steps can be found in the application manual in question. The
parameter value shall be given without decimals. If several parameters/actual
values are read with one message, the adresses of the parameters/actual values
must be consecutive.
All values can be read with function codes 3 and 4 (all registers are 3X and
4X reference). Modbus registers are mapped to drive ID’s as follows:
ID
Modbus register
1 … 98
40001…40098 (30001…30098)
99
40099 (30099)
101… 1999
40101…41999 (30101…31999)
2001…2099
42001…42099 (32001…32099)
2101…2199
42101…42199 (32101…32199)
Table 9. Index table
Group Actual Values Fault Code Parameters Process Data In Process Data Out
R/W 30/1 30/1 30/1 20/20 20/20
6.2.2 Process data
The process data fields are used to control the drive (e.g. Run, Stop ,
Reference, Fault Reset) and to quickly read actual values (e.g. Output
frequency, Output current, Fault code). The fields are structured as follows:
Process Data Slave -> Master(max 22 bytes)
ID 2101 2102 2103
Modbus register 32101, 42101 32102, 42102 32103, 42103
Name FB Status Word FB General Status Word FB Actual Speed
2104 2105 2106 2107 2108 2109
32104, 42104 32105, 42105 32106, 42106 32107, 42107 32108, 42108 32109, 42109
FB Process Data Out 1 FB Process Data Out 2 FB Process Data Out 3 FB Process Data Out 4 FB Process Data Out 5 FB Process Data Out 6
2110 32110, 42110 2111 32111, 42111
FB Process Data Out 7 FB Process Data Out 8
Table 10.
Range/Type Binary coded Binary coded 0…10000 % See appendix 1 See appendix 1 See appendix 1 See appendix 1 See appendix 1 See appendix 1 See appendix 1 See appendix 1
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
26 · vacon
modbus
Process Data Master -> Slave
(max 22 bytes)
ID
Modbus register Name
2001 2002 2003 2004 2005 2006
32001, 42001 32002, 42002 32003, 42003 32004, 42004 32005, 42005 32006, 42006
FB Control Word FB General Control Word FB Speed Reference FB Process Data In 1 FB Process Data In 2 FB Process Data In 3
2007 2008 2009 2010 2011
32007, 42007 32008, 42008 32009, 42009 32010, 42010 32011, 42011
FB Process Data In 4 FB Process Data In 5 FB Process Data In 6 FB Process Data In 7 FB Process Data In 8
Table 11.
Range/Type Binary coded Binary coded 0…10000 % Integer 16 Integer 16 Integer 16 Integer 16 Integer 16 Integer 16 Integer 16 Integer 16
The use of process data depends on the application. In a typical situation, the device is started and stopped with the ControlWord (CW) written by the Master and the Rotating speed is set with Reference (REF). With PD1…PD8 the device can be given other reference values (e.g. Torque reference). With the StatusWord (SW) read by the Master, the status of the device can be seen. Actual Value (ACT) and PD1…PD8 show the other actual values.
6.2.3 Process data in
This register range is reserved for the control of the frequency converter.
Process data in is located in range ID 2001…2099. The registers are updated
every 10 ms. See Table 12.
ID
Modbus register
Name
2001 32001, 42001
FB Control Word
2002 32002, 42002
FB General Control Word
2003 32003, 42003
FB Speed Reference
2004 32004, 42004
FB Process Data In 1
2005 32005, 42005
FB Process Data In 2
2006 32006, 42006
FB Process Data In 3
2007 32007, 42007
FB Process Data In 4
2008 32008, 42008
FB Process Data In 5
2009 32009, 42009
FB Process Data In 6
2010 32010, 42010
FB Process Data In 7
2011 32011, 42011
FB Process Data In 8
Table 12. Fieldbus basic input table
Range/Type Binary coded Binary coded 0…10000 % Integer 16 Integer 16 Integer 16 Integer 16 Integer 16 Integer 16 Integer 16 Integer 16
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 27
6.2.3.1 Control word
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
–
–
–
–
–
–
–
–
–
–
–
–
– RST DIR RUN
In Vacon applications, the three first bits of the control word are used to control the frequency converter. However, you can customise the content of the control word for your own applications because the control word is sent to the frequency converter as such.
Bit
Description
Value = 0
Value = 1
0
Stop
Run
1
Clockwise
Counterclockwise
2
Rising edge of this bit will reset active fault
3….15
Not in use
Not in use
Table 13. Control word bit descriptions
6.2.3.2 Speed reference
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is the Reference 1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 10000…10000. In the application, the value is scaled in percentage of the frequency area between the set minimum and maximum frequencies.
6.2.3.3 Process data in 1 to 8
Process Data In values 1 to 8 can be used in applications for various
purposes. Update rate is 10 ms for all values. See Vacon NX Application Manual
for usage of these data values.
6.2.4 Process data out
This register range is normally used to fast monitoring of the frequency
converter. Process data out is located in range ID 2101…2199. See Table 14.
ID 2101 2102
Modbus register 32101, 42101 32102, 42102
Name FB Status Word FB General Status Word
2103 2104 2105 2106 2107 2108 2109 2110 2111
32103, 42103 32104, 42104 32105, 42105 32106, 42106 32107, 42107 32108, 42108 32109, 42109 32110, 42110 32111, 42111
FB Actual Speed FB Process Data Out1 FB Process Data Out2 FB Process Data Out3 FB Process Data Out4 FB Process Data Out5 FB Process Data Out6 FB Process Data Out7 FB Process Data Out8
Table 14. Fieldbus basic output table
Range/Type Binary coded Binary coded
0…10000 % See appendix 1 See appendix 1 See appendix 1 See appendix 1 See
appendix 1 See appendix 1 See appendix 1 See appendix 1
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
28 · vacon
modbus
6.2.4.1 Status word
15
14
13
12
11 10
9
8
7
6
5
4
3
2
1
0
–
–
–
–
–
UVFS
DDI R
TCSPDL
FR
Z
ARE F
W FLT DIR RUN RDY
Information about the status of the device and messages is indicated in the Status word. The Status word is composed of 16 bits that have the following meanings:
Bit
Description
Value = 0
Value = 1
0
Not Ready
Ready
1
STOP
RUN
2
Clockwise
Counterclockwise
3
–
Faulted
4
–
Warning
5
Ref. frequency not reached
Ref. Frequency reached
6
–
Motor is running at zero speed
7
Flux Not Ready
Flux Ready
8
TC Speed Limit Active
TC Speed Limit Not Active
9
Detected Encoder Direction Clockwise Encoder Direction Counterclockwise
10
UV Fast Stop Active
UV Fast Stop Not Active
11…15 Not In use
Not In use
Table 15. Status word bit descriptions
6.2.4.2 General status word
15
14
13
12
11 10
9
8
7
6
5
4
3
2
1
0
I/O PANEL FB
–
–
–
–
–
–
–
–
–
–
–
–
Bit
Description
0…12
Not in use
13
Fieldbus control, (1 = FB control active)
14
Panel control, (1 = Panel control active)
15
I/O Control, (1 = I/O control active)
Table 16. General status word bit descriptions
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 29
6.2.4.3 Actual speed
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
MSB
LSB
This is the reference 1 to the frequency converter. Used normally as Speed reference. The allowed scaling is 10000…10000. In the application, the value is scaled in percentage of the frequency area between set minimum and maximum frequency.
6.2.4.4 Process data out 1 to 8
Process Data Out values 1 to 8 can be used in application for various
purposes. Update rate is 10ms for all values. See APPENDIX 1 for usage of
these values.
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
30 · vacon
modbus
6.2.5 Parameters
The parameter addresses are determined in the application. Every parameter has
been given an ID number in the application. The ID numbering of the parameter
as well as the parameter ranges and steps can be found in the application
manual in question. The parameter value shall be given without decimals. The
following functions can be activated with parameters:
Function code Function
03
Read Holding Registers
04
Read Input Registers
06
Preset Single Register
16
Preset Multiple
Registers
Table 17. Parameters
Modbus Address 30101…31999 40101…41999 40101…41999 40101…41999
Parameter ID’s 101-1999 101-1999 101-1999 101-1999
6.2.6 Actual values
The actual values as well as parameter addresses are determined in the
application. Every actual value has been given an ID number in the
application. The ID numbering of the actual values as well as the value ranges
and steps can be found in the application manual in question. The following
functions can be activated with parameters:
Function code Function
03
Read Holding Registers
04
Read Input Registers
Table 18. Actual values
Actual values 30001-30098 40001-40098
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 31
6.2.7 Example messages Example 1
Write the process data 42001…42003 with command 16 (Preset Multiple Registers).
Command Master Slave:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of registers HI No. of registers LO Byte count Data HI
Data LO Data HI Data LO Data HI Data LO ERROR CRC HI CHECK CRC LO
01 hex 10 hex 07 hex D0 hex 00 hex 03 hex 06 hex 00 hex 01 hex 00 hex 00 hex 13 hex 88 hex C8 hex CB hex
Slave address 1 hex (= 1) Function 10 hex (= 16) Starting address 07d0 hex (=
2000)
Number of registers 0003 hex (= 3)
Byte count 06 hex (= 6) Data 1 = 0001 hex (= 1). Setting control word run bit
to 1. Data 2 = 0000 hex (= 0). General control word 0. Data 3 = 1388 hex (=
5000), Speed Reference to 50.00% CRC field C8CB hex (= 51403)
Message frame: 01 10 07 D0 00 03 06 00 01 00 00 13 88 C8 CB
The reply to Preset Multiple Registers message is the echo of 6 first bytes.
Answer Slave Master:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of registers HI No. of registers LO ERROR CRC HI CHECK
CRC LO
01 hex 10 hex 07 hex D0 hex 00 hex 03 hex F1 hex 01 hex
Slave address 1 hex (= 1) Function 10 hex (= 16) Starting address 07d0 hex (=
2000)
Number of registers 0003 hex (= 3)
CRC F101 hex (= 61697)
Reply frame: 01 10 07 D0 00 03 F1 01
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
32 · vacon
modbus
Example 2 Read the Process Data 42103…42104 with command 4 (Read Input Registers).
Command Master Slave:
ADDRESS FUNCTION DATA Starting ddress HI
Starting address LO No. of registers HI No. of registers LO ERROR CRC HI CHECK
CRC LO
01 hex 04 hex 08 hex 36 hex 00 hex 02 hex 93 hex A5 hex
Slave address 1 hex (= 1) Function 4 hex (= 4) Starting address 0836 hex (=
2102)
Number of registers 0002 hex (= 2)
CRC field B321 hex (= 45857)
Message frame: 01 04 08 36 00 02 93 A5
The reply to the Read Input Registers message contains the values of the read registers.
Answer Slave Master:
ADDRESS FUNCTION DATA Byte count
Data HI Data LO Data HI Data LO ERROR CRC HI CHECK CRC LO
01 hex 04 hex 02 hex 13 hex 88 hex 09 hex C4 hex F0 hex
E9 hex
Slave address 1 hex (= 1) Function 4 hex (= 4) Byte count 4 hex (= 4) Speed
reference = 1388 hex (=5000 => 50.00%)
Output Frequency = 09C4 hex (=2500 =>25.00Hz)
CRC field B321 hex (= 45857)
Reply frame: 01 04 02 13 88 09 C4 F0 E9
6
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
modbus
vacon · 33
6.3 Start-up test
Frequency converter application Choose Fieldbus (Bus/Comm) as the active
control place (see Vacon NX User’s Manual, Chapter 7.3.3).
Master software
1. Set FB Control Word (MBaddr 42001) value to 1hex. 2. Frequency converter
status is RUN. 3. Set FB Speed Reference (MBaddr 42003) value to 5000
(=50,00%). 4. The Actual value is 5000 and the frequency converter output
frequency is 25,00 Hz. 5. Set FB Control Word (MBaddr 42001) value to 0hex. 6.
Frequency converter status is STOP.
If FB Status Word (Addr 42101) bit 3 = 1 Status of frequency converter is FAULT.
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
6
34 · vacon
metasys n2
7. METASYS N2
7.1 Metasys N2 Protocol Introduction
The N2 communications protocol is used by Johnson Controls and others to
connect terminal unit controllers to supervisory controllers. It is open to
any manufacturer and based upon a simple ASCII protocol widely used in the
process control industry.
The physical characteristics of the N2 bus are three wire RS-485 with a
maximum of 100 devices over a 4,000 foot distance running at 9,600 bps.
Logically, the N2 is a master-slave protocol, the supervisory controller
normally being the master. Data is partitioned into common HVAC control
objects, such as analogue input, analogue output, binary input and binary
output. N2 messaging supports the reading, writing and overriding of these
points. Additionally, there are messages defined to perform uploads and
downloads of devices as well as direct memory reads and writes.
7.2 Metasys N2 interface
Features of the N2 Interface: · Direct control of Drive ( e.g. Run, Stop,
Direction, Speed reference, Fault reset) · Full access to necessary parameters
· Monitor Drive status (e.g. Output frequency, Output current, Fault code ) ·
In standalone operation, or should the polling stop, the overridden values are
released after a specified period (about 10 minutes).
7.2.1 Analogue Input (AI)
All Analogue Input (AI) points have the following features: · Support Change
of State (COS) reporting based on high and low warning limits. · Support
Change of State (COS) reporting based on high and low alarm limits. · Support
Change of State (COS) reporting based on override status. · Always considered
reliable and never out of range. · Writing of alarm and warning limit values
beyond the range that can be held by the drive’s internal variable will result
in having that limit replaced by the “Invalid Float” value even though the
message is acknowledged. The net result will be the inactivation of the alarm
or warning (the same as if the original out of range value was used). ·
Overriding is supported from the standpoint that the “Override Active” bit
will be set and the value reported to the N2 network will be the overridden
value. However, the value in the drive remains unchanged. Therefore, the N2
system should be set up to disallow overriding AI points or have an alarm
condition activated when an AI point is overridden. · Overriding an AI point
with a value beyond the limit allowed by the drive’s internal variable will
result in an “Invalid Data” error response and the override status and value
will remain unchanged.
7.2.2 Binary Input (BI)
All Binary Input (BI) points have the following features: · Support Change of
State (COS) reporting based on current state. · Support Change of State (COS)
reporting based on alarm condition. · Support Change of State (COS) reporting
based on override status. · Always considered reliable.
Overriding is supported from the standpoint that the “Override Active” bit
will be set and the value reported to the N2 network will be the overridden
value. However, the value in the drive remains un-
7
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
metasys n2
vacon · 35
changed. Therefore, the N2 system should be set up to disallow overriding BI
points or have an alarm condition activated when a BI point is overridden.
7.2.3 Analogue Output (AO)
All Analogue Output (AO) points have the following features: · Support Change
of State (COS) reporting based on override status. · Always considered
reliable. · Overriding of the AO points is the method used to change a value.
Overriding an AO point with a value beyond the limit allowed by the drive’s
internal variable will result in an “Invalid Data” error response and the
override status and value will remain unchanged. If the overridden value is
beyond the drive’s parameter limit but within the range that will fit in the
variable, an acknowledge response is given and the value will be internally
clamped to its limit. · An AO point override copies the override value to the
corresponding drive parameter. This is the same as changing the value on the
keypad. The value is non-volatile and will remain in effect when the drive is
turned off and back on. It also remains at this value when the N2 network
“releases” the point. The N2 system always reads the current parameter value.
Note: On some N2 systems, the system will not poll the AO point when it is
being overridden. In this case, the N2 system will not notice a change in
value if the change is made with the keypad. To avoid this, set the point up
as a “local control” type and release it once it has been overridden. In this
way, the N2 system will monitor the value when not being overridden.
7.2.4 Binary Output (BO)
All Binary Output (BO) points have the follwoing features: · Support Change of
State (COS) reporting based on override status. · Always considered reliable.
· Overriding BO points control the drive. These points are input commands to
the drive. When released, the drive’s internal value remains at its last
overridden value.
7.2.5 Internal Integer (ADI)
All Internal Integer (ADI) points have the follwoing features: · Do not
support Change of State (COS) reporting. · Can be overridden and the “Override
Active” bit will be set. However, the Internal value is unchanged (Read Only).
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
7
36 · vacon
metasys n2
7.3 N2 POINT MAP
7.3.1 Analogue Inputs (AI)
NPT NPA
AI
1
AI
2
AI
3
AI
4
AI
5
AI
6
AI
7
AI
8
AI
9
AI
10
AI
11
AI
12
AI
13
AI
14
AI
15
AI
16
Description Speed Setpoint Output Speed Motor Speed Load (power) Megawatt
Hours Motor Current Bus Voltage Motor Volts Heatsink Temperature Motor Torque
Operating Days (trip) Operating Hours (trip) Kilowatt Hours (trip) Torque
Reference 1) Motor Temperature Rise1)
FBProcessDataOut1 2)
AI
17
FBProcessDataOut2 2)
AI
18
FBProcessDataOut3 2)
AI
19
FBProcessDataOut4 2)
AI
20
FBProcessDataOut5 2)
AI
21
FBProcessDataOut6 2)
AI
22
FBProcessDataOut7 2)
AI
23
Table 19.
FBProcessDataOut8 2)
Units Hz Hz Rpm % MWh A V V ° C % Day Hour kWh %
%
-32768 to +32767 -32768 to +32767 -32768 to +32767 -32768 to +32767 -32768 to +32767 -32768 to +32767 -32768 to +32767 -32768 to +32767
Note 2 decimals 2 decimals 0 decimal 1 decimal Total Counter 2 decimal 0
decimal 1 decimal 0 decimal 1 decimal 0 decimal 0 decimal Trip Counter 1
decimal 1 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
0 decimal
- Torque Reference (AI-14) and Motor Temperature Rise (AI-15) NOT supported in NXL 2) These analogue inputs are application specific.
7
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
metasys n2
vacon · 37
7.3.2 7.3.3
Binary Inputs (BI)
NPT NPA
BI
1
BI
2
BI
3
BI
4
BI
5
BI
6
BI
7
BI
8
BI
9
BI
10
BI
11
BI
12
BI
13
BI
14
BI
15
Table 20.
Description Ready Run Direction Faulted Warning Ref. Frequency reached Motor running zero speed General 0 3) General 1 3) General 2 3) General 3 3) General 4 3) General 5 3) General 6 3) General 7 3)
0 = Not Ready Stop Clockwise Not Faulted Not Warning False False 0 0 0 0 0 0 0 0
1 = Ready Run Counterclockwise Faulted Warning True True 1 1 1 1 1 1 1 1
- These binary inputs are application specific. They are read from the drives General Status Word.
Analogue Outputs (AO)
NPT NPA
AO
1
AO
2
AO
3
AO
4
AO
5
AO
6
AO
7
AO
8
AO
9
AO
10
Table 21.
Description Comms Speed
Current Limit
Minimum Speed Maximum Speed Accel Time Decel Time FBProcessDataIN 1 4)
FBProcessDataIN 2 4) FBProcessDataIN 3 4) FBProcessDataIN 4 4)
Units % A
Hz Hz s s -32768 to +32767 -32768 to +32767 -32768 to +32767 -32768 to +32767
- These Analogue Outputs are application specific.
Note 2 decimals 2 decimals
2 decimals 2 decimals 1 decimal 1 decimal 2 decimals 2 decimals 2 decimals 2
decimals
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
7
38 · vacon
7.3.4 7.3.5
Binary Outputs (BO)
NPT NPA BO 1 BO 2 BO 3 BO 4 BO 5 BO 6 BO 7 BO 8 BO 9 BO 10 BO 11
BO 12
BO 13
BO 14
BO 15
BO 16
Table 22.
Description Comms Start/Stop Comms Forward/Reverse Reset Fault
FBFixedControlWord Bit_3 5) FBFixedControlWord Bit_4 5) FBFixedControlWord
Bit_5 5) FBFixedControlWord Bit_6 5) FBFixedControlWord Bit_7 5)
FBFixedControlWord Bit_8 5) FBFixedControlWord Bit_9 5) FBFixedControlWord
Bit_10
5)
FBFixedControlWord Bit_11
5)
FBFixedControlWord Bit_12
5)
FBFixedControlWord Bit_13
5)
FBFixedControlWord Bit_14
5)
FBFixedControlWord Bit_15
5)
0 = Stop Forward N/A –
–
–
–
–
–
–
- These Binary Outputs are application specific.
Internal Integers (ADI)
NPT NPA
ADI 1 Table 23.
Description Active Fault Code
Units –
metasys n2
1 = Start Reverse Reset –
–
–
–
–
–
7
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
metasys n2
vacon · 39
8. FAULT TRACKING
The table below presents the faults related to the RS-485 option board. For
more information, see also Vacon NX User’s Manual, Chapter 9. The RS-485
option board status LEDs have been described in more detail in Chapter 3.6.
Fault code
37 38 39 40
53
54
Fault
Device change Device added Device removed Device unknown Fieldbus fault
Slot fault
Possible cause
Option board changed. Option board added. Option board removed. Unknown option
board.
The data connection between the Modbus/ N2 Master and the RS-485 option board
is broken Defective option board or slot
Table 24. RS-485 option board faults
Correcting measures
Reset Reset Reset
Check the installation. If installation is correct contact the nearest Vacon
distributor. Check the board and slot. Contact the nearest Vacon distributor.
You can define with parameters how the frequency converter shall react to certain faults:
Code
Parameter
Min
P2.7.22
Response to fieldbus fault
0
Max
Unit
3
P2.7.23
Response to slot fault
0
3
Table 25. Frequency converter responses to faults
Step 1
1
Default 0
0
ID
Note
0=No response
733
1=Warning 2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
0=No response
734
1=Warning 2=Fault,stop acc. to 2.4.7
3=Fault,stop by coasting
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
7
40 · vacon
APPENDIX 1
metasys n2
Process Data OUT (Slave to Master)
The Fieldbus Master can read the frequency converter’s actual values using
process data variables. Basic, Standard, Local/Remote Control, Multi-Step
Speed Control, PID control and Pump and fan control applications use process
data as follows:
ID
Data
Value
2104
Process data OUT 1 Output Frequency
2105
Process data OUT 2 Motor Speed
2106
Process data OUT 3 Motor Current
2107
Process data OUT 4 Motor Torque
2108
Process data OUT 5 Motor Power
2109
Process data OUT 6 Motor Voltage
2110
Process data OUT 7 DC link voltage
2111
Process data OUT 8 Active Fault Code
Table 26. Process data OUT variables
Unit Scale
Hz 0,01 Hz
rpm 1 rpm
A
0,1 A
%
0,1 %
%
0,1 %
V
0,1 V
V
1 V
–
–
The Multipurpose Control application has a selector parameter for every Process Data. The monitoring values and drive parameters can be selected using the ID number (see NX All in One Application Manual, Tables for monitoring values and parameters). Default selections are as in the table above.
Process Data IN (Master to Slave) ControlWord, Reference and Process Data are used with All-inOne applications as follows:
Basic, Standard, Local/Remote Control and Multi-Step Speed Control applications
ID 2003 2001
20042011 Table 27.
Data Reference ControlWord
PD1 PD8
Value
Unit
Speed Reference
%
Start/Stop Command –
Fault reset Command
Not used
–
Scale 0.01% –
–
7
Tel.+358 (0)201 2121 · Fax +358 (0)201 212 205
metasys n2
Multipurpose Control application
ID 2003 2001
2004 2005 20062011 Table 28.
Data
Value
Unit
Reference
Speed Reference
%
ControlWord
Start/Stop Command –
Fault reset Command
Process Data IN1 Torque Reference
%
Process Data IN2 Free Analogia INPUT %
PD3 PD8
Not Used
–
PID control and Pump and fan control applications
Scale 0.01% –
0.1% 0.01% –
ID 2003 2001
2004
2005
2006
20072011 Table 29
Data
Value
Unit
Reference
Speed Reference
%
ControlWord
Start/Stop Command –
Fault reset Command
Process Data IN1 Reference for PID
%
controller
Process Data IN2 Actual Value 1 to PID %
controller
Process Data IN3 Actual Value 2 to PID %
controller
PD4PD8
Not Used
–
Scale 0.01% –
0.01%
0.01%
0.01%
–
vacon · 41
24-hour support +358 (0)40 8371 150 · Email: vacon@vacon.com
7
Find your nearest Vacon office on the Internet at:
www.vacon.com
Manual authoring: documentation@vacon.com
Vacon Plc. Runsorintie 7 65380 Vaasa Finland
Subject to change without prior notice © 2012 Vacon Plc.
Document ID: Rev. A
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>