KEW 4506 Intelligent Socket Tester Instruction Manual
- June 9, 2024
- KEW
Table of Contents
- KEW 4506 Intelligent Socket Tester
- Product Information: Intelligent Socket Tester KEW 4506
- Features:
- Specifications:
- Product Usage Instructions:
- DANGER Read through and understand the instructions contained in this
- DANGER : is reserved for conditions and actions that are likely to cause
- WARNING : is reserved for conditions and actions that can cause serious or
- CAUTION : is reserved for conditions and actions that can cause injury or
- DANGER Use the tester under operating conditions as specified;
- WARNING Always verify the proper operation on a well-known power
- CAUTION Do not apply voltage to the tester while the tester is off. Do not
- DANGER
- CAUTION Anti-trip-technology is applicable to RCDs rated to 30 mA or higher.
- CAUTION
- DANGER If earth wire of conversion adapter is connected to the earth
- CAUTION Do not apply excessive force to the tip of outlet plug.
- DANGER Do not try to open the battery compartment cover if the surface
- WARNING In order to avoid getting electrical shock, ensure that the tester
- CAUTIOIN Do not mix new and old batteries or mix different types of
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
KEW 4506 Intelligent Socket Tester
Product Information: Intelligent Socket Tester KEW 4506
The Intelligent Socket Tester KEW 4506 is an electronic measuring apparatus that has been designed and manufactured according to IEC 61010 safety requirements (CAT II 300V). It is used to test power sockets and detect any wiring faults or mismatches, such as missing earth, live-neutral reverse, and live-earth reverse. The tester is equipped with LED indicators that display the status of each tested socket, making it easy to identify the fault.
Features:
- Multiple socket types: The tester is compatible with various socket types, including BS 1363, Schuko, French, Italian, Swiss, Australian, and American.
- LED indicators: The tester has three LED indicators that display the status of each tested socket, indicating whether it is correctly wired, has a fault, or is unsafe to use.
- Safety: The tester complies with IEC 61010 safety standards and has built-in safety features to protect the user from electric shock.
Specifications:
- Measurement categories: CAT II 300V
- Operating voltage range: 100-250V AC
- Frequency range: 45-65Hz
Product Usage Instructions:
Step 1: Insert the tester into the power socket that you want to test. Ensure that the tester is fully inserted and that it fits securely in the socket.
Step 2: Observe the three LED indicators on the tester. If all three LEDs light up green, the socket is correctly wired and safe to use. If any other combination of LEDs light up, there is a fault in the socket that needs to be fixed before use.
Step 3: Refer to the instruction manual for the meaning of the LED combinations and how to interpret them. Take the necessary steps to fix the wiring fault or seek advice from a qualified electrician.
Step 4: Remove the tester from the socket and repeat the process for any other sockets that need to be tested.
Note: Always follow the safety precautions and instructions contained in the manual before using the tester. Failure to do so may cause injury, instrument damage, and damage to the equipment under test.
Instruction Manual
INTELLIGENT SOCKET TESTER
KEW 4506
Contents
,&8
4BGFUZQSFDBVUJPOT ‘FBUVSFT *OTUSVNFOUMBZPVU “DDFTTPSJFT (FUUJOHTUBSUFE
4PDLFUUFTU 0VUMFUXJUIFBSUIQPMF<1> /&XJSJOHDIFDLCBTFEPOSFTJTUBODFTPGFBSUIXJSF &
BOEOFVUSBMXJSF /
/&XJSJOHDIFDLCBTFEPOQPMBSJUJFTPGWPMUBHFTJHOBM GSPNTJHOBMTPVSDF ,&8
4PDLFUUFTUQSPDFEVSFT $POOFDUJPOPG,&8 )PXUPVTF,&8 1PVUMFU 4FUUJOHT
%JTBCMJOHSFTJTUBODFNFBTVSFNFOUPGFBSUIXJSF &
BOE OFVUSBMXJSF /
1PVUMFU #V[[FSBOECBDLMJHIUTFUUJOHT -$%CBDLMJHIU #BUUFSZSFQMBDFNFOU
4QFDJGJDBUJPOT
1. Safety precautions
This tester has been designed, manufactured, and tested according to IEC 61010
(CAT II 300V): Safety requirements for Electronic measuring apparatus, and
delivered in the best condition after passing quality control tests.
This instruction manual contains warnings and safety rules which must be
observed by the user to ensure safe operation of the tester and retain it in
safe condition. Therefore, read through these operating instructions before
starting to use the tester.
DANGER Read through and understand the instructions contained in this
manual before starting to use the tester. Keep the manual at hand to enable
quick reference whenever
necessary. The tester is to be used only in its intended applications.
Understand and follow all the safety instructions contained in
the manual. When using the optional KEW 8343 (Signal source) together
with KEW 4506,read the instruction manual for KEW 8343 as well. It is
essential that the above instructions are adhered to. Failure to follow the
instructions may cause injury, instrument damage and/or damage to the
equipment under test. Kyoritsu is by no means liable for any damage resulting
from the tester in contradiction to these cautionary notes.
The symbol # indicated on the tester means that the user must refer to the
related parts in the manual for safe operation of the tester. It is essential
to read the instructions wherever the symbol appears in the manual.
DANGER : is reserved for conditions and actions that are likely to cause
serious or fatal injury.
WARNING : is reserved for conditions and actions that can cause serious or
fatal injury.
CAUTION : is reserved for conditions and actions that can cause injury or
instrument damage.
– Measurement (over-voltage) category To ensure safe operation of measuring
instruments, IEC 61010 establishes safety standards for various electrical
environments, categorized as CAT O to CAT IV and called measurement
categories. Higher-numbered categories correspond to electrical environments
with greater momentary energy, so a measuring instrument designed for CAT III
environments can endure greater momentary energy than one designed for CAT II.
O (None, Other) : Circuits which are not directly connected to the
mains power supply.
CAT II
: Primary electrical circuits of the equipment
connected to an AC electrical outlet by a power
cord.
CAT III
: Primary electrical circuits of the equipment
connected directly to the distribution panel, and
feeders from the distribution panel to outlets.
CAT IV
: The circuit from the service drop to the service
entrance, and to the power meter and primary
overcurrent protection device (distribution panel).
O: Device which is not directly connected to the mains power supply
DANGER Use the tester under operating conditions as specified;
otherwise, the protection supplied by the tester can be compromised and damage
itself or lead to a serious accident. Verify proper operation on a well-known
source before using the tester, or taking actions against the indication of
the tester. This tester is rated to CAT II 300 V AC. (max. voltage to ground)
Do not test the circuits which exceed this rating: circuits in which 300 V or
higher voltage to ground exists. Do not attempt to operate this tester in an
explosive atmosphere. (e.g.: in the presence of flammable or explosive gasses
or vapor) Never attempt to use the tester if the tester or your hands are wet.
– Measurement Be careful not to short-circuit a power line with the metal tips
of
KEW 4506 during a measurement. It may cause personal injury. Do not exceed the
maximum allowable input of any measuring
range. Never open the battery compartment cover during a measurement.
WARNING Always verify the proper operation on a well-known power
source before starting to use the tester. If any breaks or cracks are noted on
the tester or tip plugs, or
exposed metal parts are noted, do not use the tester. Press the test button
after connected to the outlet to be tested. Never install substitute parts or
make any modifications to the
tester. Send the tester to your local KYORITSU distributor for repair or
recalibration. Do not try to replace batteries if the surface of the tester is
wet. Firmly insert and attach the conversion adapter to the tip plugs as
necessary. When opening the battery compartment cover for battery replacement,
power off the tester and disconnect from the object to be tested.
CAUTION Do not apply voltage to the tester while the tester is off. Do not
attempt to operate the tester in dusty or wet place. Use the tester at a
distance as far as possible from a strong
magnetic field or energized objects. Never give shocks, such as vibration or
drop, which may
damage the tester.
– Battery Brand and type of the batteries should be harmonized.
– After use Always power off the tester after use. Remove batteries if the
tester is to be stored and will not be in use for a long period. Do not give
vibration, shock, or drop the tester during
transportation. Do not expose the tester to the direct sunlight, extremely
high
temperature and humidity, or dew fall. Use a damp cloth with neutral detergent
or water for cleaning
the tester. Do not use abrasives or solvents. If the tester is wet, make sure
to let it dry before putting it into
storage.
The following symbols are marked and used on the tester or in this instruction
manual. Before starting to use the tester, please read and understand the
meaning of each symbol.
CAT II
Symbols
Electrical circuits of equipment connected to an AC electrical outlet by a
power cord. (Primary side)
Double or reinforced insulation
User must refer to the explanations in the instruction manual.
(Functional) Earth
This instrument satisfies the marking requirement defined in the WEEE
Directive. This symbol indicates separate collection for electrical and
electronic equipment.
2. Features
This is a socket tester which can test wiring connection and find miswiring
in:
- Single-phase 2-Wire, Single-phase 3-Wire systems, 3P outlet with earth pole in Three-phase 3-Wire 200 V
(delta connection, L2(S) grounded) and Three-phase 4-Wire commercial power line, and 2P outlet.
For 3P outlet, it is possible to test whether the outlet is correctly wired by using KEW 4506 together with KEW 8343 (signal source). It is applicable to integrated earthing systems with low resistances such as TN, building structure, and common earth systems.
For a wiring system like TT system which has high integrated earth resistance – resistance between N-E exceeds 2 -, you just need KEW 4506 to perform a test. The tester measures resistance between earth pole (E) and neutral wire (N) and judges N-E connection is correct or reverse. When NE reverse connection is detected, LCD visually shows incorrect wiring. (e.g.: L-N Reverse or E Non-connect, etc.)
Compatible with 3P and 2P outlets To connect the tester to 2P outlet, commercially available 3P/ 2P conversion adapter is required.
At 3P outlet testing, the tester measures resistance between N-E and displays the value on the LCD. Test current is 10 mA max, therefore, RCDs rated to 30 mA (sensitive current) don’t trip unintentionally.
If N-E resistance measurement function is turned off, test is performed with a test voltage applied from an optional signal source only: current flows between N-E is less than 1 µA. If the function is disabled, KEW 4506 doesn’t show resistance between N-E.
LCD with backlight. It turns on/ off depending on the ambient brightness.
Compact and easy-to-use design Tester automatically powers off after 10 minutes of no use. This
function doesn’t work if 80 V or higher voltage is applied to the tester. It is possible to disable backlight and buzzer.
3. Instrument layout
(1) KEW 4506 main unit
Fig. 3-1
Name
Description
Socket for test lead
Terminal to connect test lead with IEC connector.
Indicates test result.
LED indicator
Judgement: Correct…Green LED lights up.
Reverse…..Red LED lights up.
Test button
Test button with touch pad. Hold down 0.5 sec or longer with a bare finger. *
Tester measures potential differences between the operator and N terminal by
touching the pad at test and
check miswiring.
3P/2P button
Selects 3P or 2P. (“3P” is always on when powering on KEW 4506.)
Power button
Powers on/ off KEW 4506 by holding down at least 1 second.
LCD
With auto-backlight: turns on/ off automatically depending on the ambient brightness.
Illuminance sensor
Detects ambient brightness and automatically turns on/ off the LCD backlight.
(2) LCD
Fig. 3-2
Displayed segments and symbols
Testable and selectable socket system:
- ” ” blinks only when testing for the first time
with default setting.
Ready to detect test voltage
Ready to measure N-E resistance
Low battery warning
Buzzer is disabled.
Appears during judgement is in progress.
Indicates voltage between L-N.
Indicates the following values based on the measured N-E voltage. – less than
8.0 V: resistances between
0.0 and 1999 – 8.0 V or higher: voltages between
8.0 V and 20.0 V.
Indicates the measured values are out of display range. L-N voltage
290V : Measured value is over 290 V. < 80V : Measured value is less than 80 V.
N-E resistance > 1999: Measured value is over 1999 .
N-E voltage > 20.0V: Measured value is over 20.0 V.
Indicates N-E resistance measurement is disabled. * Displayed only when the test voltage is used for
wiring check. Indicates the result is judged by test voltage detection method. Indicates correct wiring. Indicates miswiring. Indicates N-E connection is unjudgeable. Indicates wiring errors are detected. Indicates abnormal voltage across terminals.
Indicates incomplete connection.
Indicates miswiring or reverse connection terminal.
4. Accessories
Carrying case MODEL 9161 Others:
(1) KAMP10 (1500 mm) test lead with IEC connector/ MODEL 7284 (720 mm) test
lead with IEC connector
(2) Strap belt (3) Two size AA Alkaline batteries (4) Instruction manual
Optional accessory Signal source KEW 8343 (Diameter 24 mm)
5. Getting started
Before starting to use KEW 4506, check the following points.
See “9. Battery replacement” in this manual and insert batteries.
(1) Hold down power button 1 sec. to power on KEW 4506.
A long press (1 sec. or longer) is required to power on the tester
for safety purpose. A long press of power button is also required
to power off the tester.
(2) Confirm that battery level indicator
isn’t displayed at the
upper left on the LCD.
Note
Use of size AA Alkaline battery is recommended. The battery
level indicator
may not be properly displayed if the
other types of batteries are used.
Battery level is extremely low when the battery indicator
is
displayed on the LCD. To perform further measurements, please
refer to “9. Battery replacement” and replace batteries with new
ones.
6. Socket test
This tester is designed to perform wiring check for electrical outlet sockets: 2P and 3P.
DANGER
This tester is rated to CAT II 300 V AC (max. voltage to ground). Do not test the circuits which exceed this rating: circuits in which 300 V or higher voltage to ground exists.
Note
When conducting a test, stand on the floor and do not touch
anything other than the tester to measure electrical potentials
precisely when touching the touch pad on the tester.
The tester may suddenly power off if you continue testing with
battery level warning indicator
is displayed on the LCD.
6-1 Outlet with earth pole [3P] Note The tester may show “E Non-connect”,
although the outlet is
correctly wired, if the earth resistance of the circuit under test is high or
voltage between L-E is extremely low due to large leakage currents.
The tester measures the following values and judges whether wall outlets are
properly wired or not.
(1) Voltages across terminals (2) Potential differences between N terminal and
touch pad
(operator) (3) Resistances of earth wire (E) and neutral wire (N) (4) Polarity
of test voltage signal from signal source (KEW 8343)
As for (3) and (4) mentioned above, detailed explanations are described in the
following pages.
6-1-1 N-E wiring check based on resistances of earth wire (E) and neutral wire
(N)
RE (RE1 + RE2) in Fig. 6-1 includes earth resistance; therefore, the
resistance value is higher than the RN (resistance of a neutral wire). Compare
the measured RE and RN and KEW 4506 judges as follows. RE > RN……[PASS], RE <
RN……[NE Reverse]
Power supply RN
N
L
E
3P outlet
RE2 RE=RE2+RE1
RE1 Fig. 6-1
Note This tester cannot be used as an earth resistance tester since the
frequency of test current is low: common earth resistance testers may have
different resistance measurement values.
If any of the conditions described in the following # CAUTION or Note is
applicable, it is recommended to use test voltage signal only with N-E
resistance measurement function turning off. See “Outlet with earth pole (3P),
resistance of earth wire (E), and turning off resistance measurement of
neutral wire (N)” in “7. Settings”.
CAUTION Anti-trip-technology is applicable to RCDs rated to 30 mA or higher.
It’s not applicable to RCDs rated to 15 mA. RCDs rated to 30 mA or higher may
trip if the circuit under test
has insulation resistance of 0.1 M or less. It is recommended to measure
leakage current before conducting a test and add it to test current of 10 mA
max and confirm the total current value doesn’t exceed the rated current. If
insulation monitoring devices are installed, conducting a test may activate
the warning alarm. In such case, please contact management company or owner of
the test site.
Note
When testing 3P outlet, do not connect multiple KEW 4506
at the same time. If testing outlets wired from the same
transformer simultaneously, correct judgement result may not
be obtained.
On the following wiring systems, resistance value isn’t used for
judgment.
– voltage between N-E is 8 V or more
– small differences in RN and RE (|RNRE| 1 )
– low resistance between N-E
(RN+RE 2 )
– N-E resistance: over-range
(RN+RE > 1999 )
6-1-2 N-E wiring check based on polarities of voltage signal from signal
source (KEW 8343)
As shown in Fig. 6-2, apply test voltage to a neutral wire (N) via signal
source. Connect KEW 4506 to a 3P outlet and measure the test voltage between
N-E and then compare the phase of test voltage and reference value to judge
whether: the phase is the same with the reference value [Correct] or
180-degree reverse (opposite to the reference value) [NE Reverse].
Power supply
Test voltage
3P outlet
N
L
N-E voltage
[correct] Phase coordinate
E
[NE Reverse]
N
L Reversed phase
E
Fig. 6-2
When testing wiring systems such as TT system, which has high total earth
resistance (resistance between N-E is 2 or higher), you just need KEW 4506 and
measure resistances of earth pole (E) and neutral wire (N) to check N and E
are wired properly.
To test wiring systems with low resistances such as TN, building structure,
and common earth systems, connect KEW 8343 to the location close to the branch
circuit breaker to which 3P outlet under test is wired and apply test voltage.
See “5. Wiring system” described in the instruction manual for KEW 8343.
6-1-3 Socket test procedures KEW 4506 conducts test in the following procedures.
VL-N VL-E VN-E VMAX
- RE RN RNE
: Voltage between L-N : Voltage between L-E : Voltage between N-E : The maximum voltage among L-N, L-E, and N-E : Measured voltage is 70% or higher than VMAX. : Measured voltage is less than 70% of VMAX. : Resistance of earth pole (E) : Resistance of neutral wire (N) : Resistance between neutral wire (N) and earth pole (E)
Line voltage test
L-N voltage: //
/
L-E voltage: //
/
N-E voltage: //
/
Potential differences
detected.
Touch pad
Touch pad
test
test
No potential differences.
No potential differences.
Abnormal Volt.
L-E Reverse L-N Reverse
VN-E8V
N-E Volt. test 1
VN-E8V
N-E Volt. VN-E20V test 2
VN-E20V
RNRE
RNRE
Resistance
test
|RN-RE|1
or RNE2
or RNE2000
Positive Test Volt. Negative signal test
Undetectable
N-E unjudgeable
(>20 V)
Correct
N-E unjudgeable
N-E Reverse
Fig. 6-3
6-1-4 Connection of KEW 8343 To obtain accurate result: Clamp a neutral wire
(N) with test voltage injection clamp observing the orientation shown below:
arrow mark on the clamp shall be towards the outlet. Ensure that the
transformer jaws are firmly engaged and closed.
Power source side
Arrow mark
Outlet side
Fig. 6-4 Note To apply test voltage correctly, check the size of conductor to
be tested – the maximum measurable conductor size is approx. 24 mm – so that
the jaws close completely.
Note
As shown in Fig. 6-5, the phase of test voltage applied to a neutral wire (N)
changes 180-degree depending on the orientation of the test voltage injection
clamp. KEW 4506 performs socket test based on the polarity (phase difference)
of the test voltage signal; therefore, if the orientation of test voltage
injection clamp is incorrect, KEW 4506 judges as [NE Reverse] even if the
tested socket is correctly wired.
[NE Reverse] [correctly wired]
Fig. 6-5
It is impossible to test ungrounding system (floating power supply) which is
mainly utilized in hospital, sound room, and UPS (Uninterruptible Power
Supply) because test voltage cannot be applied to.
Power supply
KEW8343
Fig. 6-6
Note Socket test cannot be performed if a neutral wire (N) connected
to ground is closer to the outlet to be tested than the clamp position of test
voltage injection clamp.
Power supply
KEW8343
Fig. 6-7
KEW 8343 and KEW 4506 (Socket tester) cannot perform socket test if they are
connected to: * a live phase and in which one voltage phase is different from
other phases in Three-phase 4-wire system (wye or delta connection).
That is, if you make connections as illustrated on the next page (Fig. 6-9 and
Fig. 6-10) for the wiring systems described below, correct measurement result
cannot be obtained.
Fig. 6-8
Power supply
KEW8343
Power supply
Fig. 6-9
KEW8343
Fig. 6-10
Single-phase 2-Wire
Clamp the neutral wire (N) with test voltage injection clamp and black voltage
detection cable to neutral wire (N) and red voltage detection cable to
hot/live wire (L).
Red Black
Power supply
KEW8343
Fig. 6-11
Single-phase 3-Wire Clamp the neutral wire (N) with test voltage injection
clamp and black voltage detection cable to neutral wire (N) and red voltage
detection cable to hot/live wire: either L1 or L2 correctly. Then you can test
any 3P sockets which are connected to L1 or L2.
Power supply
Black Red
KEW8343
Fig. 6-12
Three-phase 3-Wire 200 V (delta connection, L2(S) grounded) Clamp the grounded
L2(S) with the test voltage injection clamp and connect the black voltage
detection cable to L2(S) and red voltage detection cable to a hot/live wire:
either L1(R) or L3(T) correctly. Then you can test any 3P outlets which are
connected to L1(R) or L3(T).
Power supply
Black Red
KEW8343
Fig. 6-13
Three-phase 4-Wire Clamp the neutral wire (N) with test voltage injection
clamp and black voltage detection cable to neutral wire (N) and red voltage
detection cable to hot/live wire: either L1(R), L2(S), or L3(T) correctly.
Then you can test any 3P outlets which are connected to L1(R), L2(S), or
L3(T).
Power supply
Black Red
KEW8343
Fig. 6-14
Note Check the wiring diagram before making connections and
identify the branch circuit breaker to which 3P outlet is wired, and then
connect the injection clamp close to the outlet to be tested.
Depending on the orientation of the test voltage injection clamp, as explained
with Fig. 6-5 at the previous clause, KEW 4506 may judge as [NE Reverse] even
if the outlet is correctly wired as shown in Fig. 6-15 (outlet wired to branch
circuit breaker [B]). Connect the test voltage injection clamp to the
appropriate neutral wire (N) of the branch circuit breaker with the correct
orientation and location.
Power supply
Other branch circuit breakers [NE Reverse]
Branch circuit breaker [B] [NE Reverse]
Branch circuit breaker [A] [correct]
Fig. 6-15
Note
When the test voltage injection clamp is connected close to the
distribution board, KEW 4506 can test the outlet which is wired
to branch circuit breaker [B] shown in Fig. 6-15 and judge as
“PASS” (correct); however, it is NOT recommended to connect
test voltage injection clamp to the position shown in Fig. 6-16.
This is because KEW 4506 may show ”
” if multiple
loads are connected to an outlet wired from any of the other
branch circuit breakers, which is not the one to be tested, and
where those loads are active.
Power supply
Other branch circuit breakers [correct]
Branch circuit breaker [B] [correct]
Branch circuit breaker [A] [correct]
Fig. 6-16
6-1-5 How to use KEW 4506 (1) Press button to select “3P”.
When you test a 3P socket with earth pole (E) correctly connected,
while “2P” has been selected with
button, KEW 4506
automatically switches the settings for “3P” and
indicator
blinks at testing for the first time.
(2) Connection
CAUTION
Use the power cord and test leads supplied with the tester only. Kyoritsu is
by no means liable for any damage resulting from the use of commercially
available power cord and test leads.
KEW 4506 may not judge the wiring condition if test lead with IEC connector
KAMP10 or MODEL 7284 is degraded and the internal resistances are extremely
changed.
Fig. 6-17
Firmly connect test lead with IEC connector KAMP10 or MODEL 7284 to KEW 4506
before connecting the plug of the test lead to the outlet to be tested.
DANGER If earth wire of conversion adapter is connected to the earth
terminal of the outlet, wear a pair of insulated gloves or other protective gears, and do not touch the earth terminal of the outlet to avoid electrical shock accident due to wiring error.
CAUTION Do not apply excessive force to the tip of outlet plug.
Note When conducting a test, stand on the floor and do not touch
anything other than the tester to measure electrical potentials precisely.
(3) Measurement
Press the test button
0.5 sec. Press the button with
bare hand since it works as touch pad. KEW 4506 starts
measurement in 0.5 sec. with audible warning. The LCD shows
”
” during measurement. A measurement is done in about
1 sec. and the LCD displays the measured result.
The LCD shows “PASS” as shown in Fig. 6-18 when the cables are correctly wired. In addition, green LED indicator lights up as shown in Fig. 6-19 and beep sounds once.
N-E resistance < 2 N-E voltage > 8 V
Meas. OFF
Resistance check
Test voltage polarity check
Fig. 6-18
Green LED lights up.
Fig. 6-19
Measured value displayed on the bottom area of LCD Resistance value: N-E
resistance determined by measuring resistance between neutral wire (N) and
earth wire (E) is displayed. Voltage value : N-E voltage is displayed if
voltage between N-E is 8 V or higher. When N-E voltage is higher than 8 V, KEW
4506 cannot measure resistance.
When KEW 4506 detects miswiring, any of the following indications is displayed
on the LCD. See Fig. 6-20. In addition, red LED
indicator lights up, as Fig. 6-21 shows, with continuous beep sounds.
Fig. 6-20
L-N Reverse L-E Reverse
N-E Reverse
Abnormal voltage N Non-connect E Non-connect N-E unjudgeable
Red LED lights up.
Fig. 6-21
Measured value displayed on the bottom area of LCD in case of “N-E Reverse”
Resistance value : N-E resistance determined by measuring resistance between
neutral wire (N) and earth wire (E) is displayed. Voltage value : N-E voltage
is displayed if voltage between N-E is 8 V or higher. When N-E voltage is
higher than 8 V, KEW 4506 cannot measure resistance.
Measured value displayed on the bottom area of LCD in case of N-E unjudgeable Resistance value : N-E resistance or “>1999 ” is displayed when N-E resistance is 2 or less or exceeds 1999 and the tester cannot detect test voltage applied via signal source.
Voltage value
: N-E voltage or “>20 V” is displayed if N-E voltage is 8 V or higher and the tester cannot detect test voltage applied via signal source. When N-E voltage is 8 V or higher, KEW 4506 cannot measure resistance.
Possible causes when test voltage from signal source cannot be detected:
Check the signal source (KEW 8343) connected within a branch circuit breaker is NOT in the following status.
Green Power LED is blinking. Battey voltage is low. Please refer to the manual for signal source and replace batteries with new ones.
Signal source is clamped in incorrect location. Please refer to each “Note” described in 6-1-4 Connection of KEW 8343 and make connections in correct position observing correct orientation.
Large load current is flowing through the clamped neutral wire (N). Signal source cannot apply test voltage correctly if large current exceeding 100 A is flowing through a neutral wire (N). In this case, turn off the load of the object to be tested or disconnect the load once and try to apply test voltage again.
Clamp jaws aren’t closed completely. Buzzer keeps beeping if the jaws aren’t closed completely. If buzzer keeps beeping even though signal source is clamping a neutral wire (N) and jaws are firmly closed, load current exceeding 30 A may be flowing on the neutral wire. In this case, test voltage is being applied correctly though buzzer keeps beeping.
Measured result remains displayed until test button
or
button is pressed.
Voltage warning
If voltage terminals,
of 253 V or higher is applied to KEW 4506 gives audible warning
awniythobf litnhkeintghr#ee
symbol and “V[L-N]” as shown in Fig. 6-22. Even while the tester
is giving voltage warning, the tester can perform tests if voltages
are 290 V or less.
The tester doesn’t start a test even if the test button
is
pressed when 290 V or higher voltage is applied to any of the
three terminals.
Blink
Blink
Fig. 6-22
6-2 2P outlet
(1) Test method
The tester conducts the following two measurements and judges whether wall
outlets are properly wired or not. 1) Voltage between L-N terminals 2)
Potential differences between N terminal and touch pad (operator)
Judgement result
L-N voltage
Potential differences
(between N terminal and touch pad)
PASS
X
FAIL: LN Reverse
FAIL: <80V [L-N]
X
(2) Press button to select “2P”. Note
Settings always restore to the ones for 3P socket whenever powering on the
tester.
If the earth terminal of the outlet to be tested is earthed at 2P test, the
settings automatically change to the ones for “3P”.
(3) Connection # CAUTION
When earth pole (E) is connected, settings automatically change to the ones
for “3P”.
Kyoritsu is by no means liable for any damage or injury resulting from the use
of 3P/ 2P conversion adapter.
A 3P/ 2P conversion adapter, which is required to connect with 2P outlet,
isn’t supplied with the tester. Prepare commercially available 3P/ 2P
conversion adapter to connect the tester to 2P outlet, and attach it to the
plug part of test lead with IEC connector KAMP10 or MODEL 7284 before
conducting a test. Observe the correct orientation and connect to the outlet
to be tested.
Note When conducting a test, stand on the floor and do not touch
anything other than the tester to measure electrical potentials precisely. If
3P/ 2P conversion adapter you prepared has exposed metal terminals, do not
touch the metal terminals during a test. KEW 4506 judges as “N-E Reverse” even
if the outlet under test is correctly wired.
(4) Measurement
Press the test button
0.5 sec. Press the button with bare hand
since it works as touch pad. KEW 4506 starts measurement in 0.5
sec. with audible warning.
The LCD screen will be like Fig. 6-23 when the wiring is correct. In addition, green LED indicator lights up as shown in Fig. 6-24 and beep sounds once.
Green LED lights up.
Fig. 6-23
Fig. 6-24
When the tester detects miswiring, the LCD shows either of the following
indication as shown in Fig. 6-25 and red LED indicator lights up to indicate
miswiring with continuous beep sounds (Fig.
6-26).
Red LED lights up.
L-N Reverse
Abnormal voltage
Fig. 6-25
Fig. 6-26
Measured result remains displayed until test button
or
button is pressed.
Voltage warning
If voltage of 253 V or higher is applied
between two terminals, KEW audible warning with blinking
4#506sygmivbeosl
and “V[L-N]” as shown in Fig. 6-27. Even
while the tester is giving voltage warning,
the tester can perform tests if voltages
are less than 290 V.
Fig. 6-27
Blink
Blink
The tester doesn’t start a test even if the test button
is
pressed when 290 V or higher voltage is applied between two
terminals.
7. Settings
7-1 Disabling resistance measurement of earth wire (E) and neutral wire (N): 3P outlet
Disabling N-E resistance measurement and using test voltage signal only is
recommended if the test site is applied to the conditions mentioned in
cautions on page 11 and 12 in this manual. Current flows by applying test
voltage signal between N-E is less than 1 µA.
Note Use of signal source (KEW 8343) is required to conduct a test
when N-E resistance measurement is disabled. Settings won’t be cleared by
powering off KEW 4506.
Holding down
3 sec. switches resistance
measurement ON/ OFF.
While resistance measurement is OFF (disabled),
”
” symbol doesn’t appear and resistance
value isn’t displayed as shown in Fig. 7-1.
Fig. 7-1
7-2 Buzzer and backlight settings
Buzzer and backlight function can be turned ON/ OFF respectively. See Fig.
7-2.
(1) Power off KEW 4506 if it is on.
(2) Press button 1 sec. with holding down tester enters setting mode.
button. Now the
(3) Press
button and set the displayed function either ON or
OFF, and then press
to confirm the selection and move to
the next setting item.
- Blinking buzzer symbol ” ”
+ =>
=>=>
- Blinking backlight symbol” ”
Volt. Meas. screen
=>=>
=>=>
Fig. 7-2
- Buzzer OFF When “OFF” is selected and set, ” buzzer doesn’t sound.
” symbol is displayed and
- Backlight OFF When “OFF” is selected and set, LCD backlight doesn’t turn
on. The number of beeps when powering on the tester indicates the currently
selected settings.
(No beep sounds when buzzer function is off.)
Pi…
Buzzer sounds
when powering on
the tester.
Fig. 7-3
Number of beeps
Setting
Once
Automatically turns on/ off.
Twice
Backlight is disabled. (Always off.)
8. LCD backlight
Note Keep the surface of the illuminance sensor clean to ensure
proper detection of brightness. The sensitivity of the sensor is not
adjustable. Cover the sensor
with your finger to turn on the light manually.
The illuminance sensor on the tester detects ambient brightness and
automatically turns on/ off the LCD backlight. Once the light turn on, it
stays on for about 15 seconds in a good light place. The light turns off
automatically after 2 minutes of no use even in a dark place. A light press of
power button turns on the LCD backlight again. Ambient brightness is detected
by the illuminance sensor shown in Fig. 8-1.
Fig. 8-1
Illuminance sensor
9. Battery replacement
DANGER Do not try to open the battery compartment cover if the surface
of the tester is wet. Do not replace batteries during a measurement. The
battery compartment cover must be closed and screwed
before starting a measurement. Otherwise, electrical shock hazard may be
caused.
WARNING In order to avoid getting electrical shock, ensure that the tester
is powered off and is disconnected from the object to be tested before opening the battery compartment cover for battery replacement.
CAUTIOIN Do not mix new and old batteries or mix different types of
batteries. Insert batteries in correct polarity as marked inside. Remove
batteries if the tester is to be stored and will not be in
use for a long period.
(1) Power off the tester.
(2) Loosen one battery compartment cover-fixing screw and remove
the cover.
(3) Replace two batteries with new ones at the same time. Confirm
new batteries are inserted in the correct polarity.
Use of two size AA alkaline batteries (LR6) is recommended.
(4) Install the battery compartment cover, and tighten the screw and
secure the cover.
Battery compartment cover
Screw
10. Specifications
Location for use : In-door use, Altitude up to 2000m 3P or 2P outlet with earth pole up to 253 V in Single-phase 2-Wire, Single-phase 3-Wire, Three- phase 3-Wire 200 V (delta connection, L2(S) grounded), Three-phase 4-Wire commercial power line
Temp. & humidity range : 23ºC±5ºC, relative humidity 85% or less
(accuracy guaranteed)
(no condensation)
Operating Temp.& : -10ºC to 50ºC, relative humidity 85% or less
humidity range
(no condensation)
Storage Temp. & : -20ºC to 60ºC, relative humidity 85% or less
humidity range
(no condensation)
Withstand voltage : 2210 V AC (50/60 Hz)/ for 5 sec. between electrical circuit and enclosure
Insulation resistance : 50 M or more / 1000 V DC between electrical circuit and enclosure
Applicable standards : IEC 61010-1/ -2-030, CAT II 300V, Pollution degree 2, IEC 63000 (RoHS)
Dustproof/ waterproof : IEC 60529 IP40
LCD
: Segment display with backlight
Dimension
: 212(L) × 56(W) × 39(D) mm
Weight
: Approx. 250g (including batteries)
Power source
: Size AA battery x 2 pcs. (Alkaline LR6 is recommended.)
Possible number of measurements When testing 3P outlet once every 30 sec. with AA alkaline batteries:
N-E resistance Possible number of measurements within effective battery voltage range
10
Approx. 3000 times
L-N RMS voltage (in stand-by mode)
Measuring range / Display range
Accuracy
80 Vrms 290 Vrms (50 Hz/ 60 Hz) ±2%rdg±4dgt*1
*1 Add ±3dgt to the specified accuracy for the sine waves other than CF<2.5 (411Vpeak).
Socket test (1) Measurable range of power supply voltage The tester gives
voltage warning if 253 V or higher voltage is detected but it can perform
socket test.
Power supply voltage
80 Vrms 290 Vrms (50 Hz/ 60 Hz)
- 290 V or higher voltage: KEW 4506 doesn’t start test even though the test button is pressed.
- Voltages less than 80 V: Judged as abnormal voltage.
(2) Judgement
The LCD shows any of the followings depending on the measured result.
3P
2P
-
PASS
-
L-N Reverse 3) L-E Reverse 4) N-E Reverse 5) E Not connected 6) N Not connected
-
- Abnormal voltage
-
PASS
-
L-N Reverse 3) Abnormal voltage
(3) Resistance measurement between N-E (only when N-E voltage is less than 8 V) Resistance between N-E is displayed with the judgement result.
Range
Measuring
(Auto-ranging) range
Test current Accuracy
200 range 0.0-199.9 2000 range 200-1999
5 mA(5.3 Hz) ±3%rdg±5dgt 1 mA(5.3 Hz)
(4) N-E RMS voltage (displayed only when N-E voltage is 8 V or higher.)
Measuring range
8.0 Vrms 20.0 Vrms (50 Hz/ 60 Hz)
Memo
Memo
DISTRIBUTOR
Kyoritsu reserves the rights to change specifications or designs described in this manual without notice and without obligations.