MITSUBISHI SRK50ZTL Micro Inverter Packaged Air Conditioners User Manual
- June 9, 2024
- Mitsubishi
Table of Contents
SRK50ZTL Micro Inverter Packaged Air Conditioners
Manual No.’19 · PAC-SM-309
updated January 27, 2020
SERVICE MANUAL
M I CRO I N V ERT ER PACK AGED AI R-CON DI T I ON ERS
(Split system, air to air heat pump type)
CEILING CASSETTE-4 WAY TYPE
Single type
Twin type
Triple type
FDT100VNAWVH FDT100VNAWPVH FDT140VNAWTVH
100VSAWVH
100VSAWPVH
140VSAWTVH
125VNAWVH
125VNAWPVH
125VSAWVH
125VSAWPVH
140VNAWVH
140VNAWPVH
140VSAWVH
140VSAWPVH
CEILING CASSETTE-4 WAY COMPACT TYPE
Twin type
Triple type
FDTC100VNAWPVH FDTC140VNAWTVH
100VSAWPVH
140VSAWTVH
125VNAWPVH
125VSAWPVH
DUCT CONNECTED-HIGH STATIC PRESSURE TYPE
Single type FDU100VNAWVH 100VSAWVH 125VNAWVH 125VSAWVH 140VNAWVH 140VSAWVH
DUCT CONNECTED-LOW/MIDDLE STATIC PRESSURE TYPE
Single type
Twin type
Triple type
FDUM100VNAWVH FDUM100VNAWPVH FDUM140VNAWTVH
100VSAWVH
100VSAWPVH
140VSAWTVH
125VNAWVH
125VNAWPVH
125VSAWVH
125VSAWPVH
140VNAWVH
140VNAWPVH
140VSAWVH
140VSAWPVH
CEILING SUSPENDED TYPE
Single type
Twin type
Triple type
FDE100VNAWVH FDE100VNAWPVH FDE140VNAWTVH
100VSAWVH
100VSAWPVH
140VSAWTVH
125VNAWVH
125VNAWPVH
125VSAWVH
125VSAWPVH
140VNAVWH
140VNAWPVH
140VSAVWH
140VSAWPVH
WALL MOUNTED TYPE
Single type
Twin type
Triple type
SRK100VNAWZR SRK100VNAWPZSX SRK140VNAWTZSX
100VSAWZR
100VSAWPZSX
140VSAWTZSX
125VNAWPZSX
125VSAWPZSX
140VNAWPZR
140VSAWPZR
V Multi System
(OUTDOOR UNIT) (INDOOR UNIT)
FDC100VNA-W FDT50VH FDE50VH
100VSA-W
60VH 60VH
125VNA-W
71VH 71VH
125VSA-W
140VNA-W
140VSA-W
’19 · PAC-SM-309
(i) Models FDC100VNA-W, 125VNA-W, 140VNA-W 1) Disassembly
PCA012D083 A
a) After the breaker is shut down, remove the service panel, top panel and rear panel. (Refer to Fig.1).
b) Don’t touch the main PCB until three minutes have passed after the breaker is shut doun.
(After having shut down the breaker, some capacitor is held by high voltage. It is very dangerous to touch
the main PCB in this condition.)
In the situation that hamesses are connected to main PCB, be sure to measure voltage (DC) on main PCB,
and check that the voltage is discharged sufficientlv (DC voltage 30 V or less). (Refer to Fig.2)
c) Disconnect the connectors, faston terminals and round terminals from the main PCB as shown in Fig.2.
And then remove the fixing screws (3 places) as shown in Fig.3.
After removing the main PCB, wipe off the heat conduction sheet neatly from the copper plate.
– 68 –
’19 · PAC-SM-309
LED2(Red) LED1(Green)
– 69 –
’19 · PAC-SM-309 2) Exchange
a) Match the setting of new main PCB switches (JSW1, SW3-7) with former main
PCB. (Refer to Fig.4) b) Tum over the separator of new heat conduction sheet
and paste the heat conduction sheet on the aluminum
block. (Refer to Fig.5) c) Install the attached hamess clip on the new main
PCB as shown in Fig.6. 3) Installation a) Install the new main PCB on the
control and tighten the screw as shown in Fig.7. b) Reconnect the connectors,
faston terminals and round terminals to the main PCB as before. (Refer to
Fig.2)
(Confirm that the connectors are not half inserted.)
– 70 –
’19 · PAC-SM-309
– 71 –
DIP switch setting list (Outdoor unit)
Moedls FDC100, 125, 140VNA-W, 100, 125, 140VSA-W
Switch
Description
Default setting
Remark
SW1 JSW1-1 JSW1-2 JSW1-3 JSW1-4 SW3-1 SW3-2 SW3-3 SW3-4 SW4-1 SW4-2 SW4-3 SW4-4 SW5-1 SW5-2 SW5-3 SW5-4 SW6-1 SW6-2 SW6-3 SW6-4 SW7-1 SW7-2 SW7-3
(See table 1)
OFF
Model selection
As per model
Reserved
OFF
Defrost condition
Normal*/Cold region
OFF
Snow protection control
Normal*/Snow protection
OFF
Test run SW
Normal*/Test run
OFF
Test run mode
Cooling*/Heating
OFF
Reserved
OFF
Cancel measuring of refrigerant leak
Normal*/Cancel
OFF
Reserved
OFF
Reserved
OFF
Utilization of existing piping control
Normal*/Existing piping control OFF
Hight difference of IU and OU control Normal*/High head control
OFF
Reserved
OFF
Reserved
OFF
Reserved
OFF
Reserved
OFF
Reserved
OFF
Inverter checker mode
Normal*/Check INV
OFF
SW1 function selection
OFF
Frost protection by frequent external ON/OFF Normal*/connected external device OFF
Silent mode selection
Normal*/Silent mode
OFF
Normal Normal Normal Cooling Normal
Normal Normal
Normal Normal Normal
See table 2
Keep OFF Refer to page 45 Refer to page 44 Refer to page 48 Refer to page 48
Keep OFF Detection function of error in E57 refrigeration system protection
(OFF: Detection / ON: Cancel to detect) Keep OFF Keep OFF See Note 1 When the
outdoor unit is positioned higher than 30m (OFF : Normal / ON : high head)
Keep OFF Keep OFF Keep OFF Keep OFF Keep OFF Refer to page 79 See table1 In
case external device switches ON/OFF frequently, switch to ON to start defrost
operation even though short operation time. Refer to page 48
- Default setting
Table 1: SW1 fuction selection
0: OFF 1:ON
SW7-1
SW1 function
Remark
0 Pump down operation
Refer to page 49
1 Reset cumulative time of compressor operation Reset of operation time after replacing a compressor
– 76 –
Table 2: Outdoor unit model selection with JSW1-1-JSW1-3 0: OFF 1:ON
100VNA 100VSA 125VNA 125VSA 140VNA 140VSA
JSW1-1
0
0
1
1
0
0
JSW1-2
0
0
0
0
1
1
JSW1-3
0
0
0
0
0
0
’19 · PAC-SM-309
Note 1: Utilization of existing pipe
1 In case of reusing annealed pipe ø19.05 × t1.0, be sure to turn the DIP
switch on the outdoor PCB ON as shown in the table because of its insufficient
strength. If its material is 1/2H or its thickness is 1.2mm or more it is no
necessary.
2 If bendng radius of existing pipe is less than R70mm, be sure to turn the
DIP switch on the outdoor PCB shown in the table due to its insufficient
strength.
’19 · PAC-SM-309
(5) Check of anomalous operation data with the remote control (a) In case of
RC-EX3A remote control [Operating procedure] On the TOP screen, touch the
buttons in the order of “Menu” “Service setting” “Service & Maintenance”
“Service password” “Set” “Error display” “Error history”. When only one indoor
unit is connected to the remote control, followings will be displayed. 1. When
there is any anomaly: “Loading. Wait a while” is displayed, followed by the
operation data at the occurrence of anomaly Contents of display Error code
Number and data item 2. When there is no anomaly: “No anomaly” is displayed,
and this mode is terminated. When two or more indoor units are connected to
the remote control, followings will be displayed. 1. When there is any
anomaly: If the unit having anomaly is selected on the “Select IU” screen,
“Loading. Wait a while” is displayed, followed by the operation data at the
occurrence of anomaly. Contents of display Indoor unit No. Error code Number
and data item 2. When there is no anomaly: “No anomaly” is displayed, ant this
mode is terminated.
Note (1) When the number of connected units cannot be shown in a page, select
“Next”.
If you press [RUN/STOP] button, the display returns to the TOP screen. If you
touch “Back” button on the way of setting, the display returns to the last
precious screen.
Note (1) When two remote controls are used to control indoor units, the check
of anomaly operation data can be made on the master remote control only. (It
cannot be operated from the slave remote control.)
Anomaly operation data (Corresponding data may not be provided depending on
models. Such items will not be displayed.)
Number 01 02 03 04 05 06 07 08 09 10 11 12 13 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
Data Item (Operation Mode) (Set Temperature) (Return Air Temperature) (Remote
Control Temperature Sensor) (Indoor Heat Exchanger Temperature Sensor / U
Bend) (Indoor Heat Exchanger Temperature Sensor /Capillary) (Indoor Heat
Exchanger Temperature Sensor /Gas Header) (Indoor Unit Fan Speed) (Frequency
Requirements) (Response Frequency) (Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit) (Supply Air Temperature) (Outdoor Air
Temperature) (Outdoor Heat Exchanger Temperature Sensor) (Outdoor Heat
Exchanger Temperature Sensor) (Compressor Frequency) (High Pressure) (Low
Pressure) (Discharge Pipe Temperature) (Comp Bottom Temperature) (Current)
(Target Super Heat) (Super Heat) (Discharge Pipe Super Heat) (Protection State
No. of The Compressor) (Outdoor Unit Fan Speed) (63H1 On/Off) (Defrost Control
On/Off)
(Total Running Hours of The Compressor) (Pulse of The Outdoor Unit Expansion
Valve EEVC) (Pulse of The Outdoor Unit Expansion Valve EEVH)
Details of compressor protection status No. 33
No.
Contents of display
Reference page
“0” Normal “1” Discharge pipe temperature protection control “2” Discharge pipe temperature anomaly “3” Current safe control of inverter primary current “4” High pressure protection control “5” High pressure anomaly “6” Low pressure protection control “7” Low pressure anomaly “8” Anti-frost prevention control “9” Current cut “11” Power transistor anomaly (Overheat)
P.45.(a).(i) P.45.(a).(ii) P.47.(f) P.45.(b).(i)P.45.(c).(i) P.45.(b).(ii) P.46.(e).(i) P.46.(e).(ii) P.47.(j) P.47.(f) P.47.(h)
“13” Spare
“14” Dewing prevention control
P.47.(k)
“15” Current safe control of inverter secondary current P.46.(f)
“16” Stop by compressor rotor lock “17” Stop by compressor startup failure
P.48.(o)
“18” Active filter anomaly
Note(1) Operation data display on the remote control.
Data is dispalyed until canceling the protection control.
In case of multiple protections controlled, only the younger No. is displayed.
Note(2) Common item. In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. “4” is displayed.
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. “8” is displayed.
– 77 –
’19 · PAC-SM-309
(b) In case of RC-E5 remote control Operation data can be checked with remote control unit operation.
Press the
button.
The display change ”
”
Press the
(SET) button while ”
” is
displayed.
When only one indoor unit is connected to remote control,
”
” is displayed (blinking indication during
data loading).
Next, operation data of the indoor unit will be displayed.
Skip to step .
When plural indoor units is connected, the smallest address
number of indoor unit among all connected indoor unit is
displayed.
[Example]:
”
” (blinking 1 seconds) ”
” blinking.
Select the indoor unit number you would like to have data
displayed with the
button.
Determine the indoor unit number with the
(SET)
button.
(The indoor unit number changes from blinking indication
to continuous indication)
”
” (The address of selected indoor unit is blinking
for 2 seconds.)
Number 01 02 03 04 05 06 07 08 09 10 11 12 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39
Data Item (Operation Mode) (Set Temperature) (Return Air Temperature) (Remote
Control Temperature Sensor) (Indoor Heat Exchanger Temperature Sensor / U
Bend) (Indoor Heat Exchanger Temperature Sensor /Capillary) (Indoor Heat
Exchanger Temperature Sensor /Gas Header) (Indoor Unit Fan Speed) (Frequency
Requirements) (Response Frequency) (Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit) (Outdoor Air Temperature) (Outdoor
Heat Exchanger Temperature Sensor) (Outdoor Heat Exchanger Temperature Sensor)
(Compressor Frequency) (High Pressure) (Low Pressure) (Discharge Pipe
Temperature) (Compressor Bottom Temperature) (Current) (Target Super Heat)
(Super Heat) (Discharge Pipe Super Heat) (Protection State No. of The
Compressor) (Outdoor Unit Fan Speed) (63H1 On/Off) (Defrost Control On/Off)
(Total Running Hours of The Compressor) (Pulse of The Outdoor Unit Expansion
Valve EEVC) (Pulse of The Outdoor Unit Expansion Valve EEVH)
”
” (A blinking indication appears while data loaded.)
Next, the operation data of the indoor unit is indicated.
Upon operation of the
button, the current operation data is displayed in order from data number 01.
The items displayed are in the above table.
*Depending on models, the items that do not have corresponding data are not displayed.
To display the data of a different indoor unit, press the indoor unit selection screen.
button, which allows you to go back to the
Pressing the
button will stop displaying data.
Pressing the
(RESET) button during remote control unit operation will undo your last operation and allow you
to go back to the previous screen. If two (2) remote controls are connected to one (1) inside unit, only the master control is available for trial
operation and confirmation of operation data. (The slave remote control is not
available.)
Details of compressor protection status No. 33
Refer to page 77.
– 78 –
’19 · PAC-SM-309
(6) Inverter checker for diagnosis of inverter output Checking method
(a) Setup procedure of checker. 1) Power OFF (Turn off the breaker). 2) Remove
the terminal cover of compressor and disconnect the wires (U, V, W) from
compressor. 3) Connect the wires U (Red) , V (White) and W (Black) of checker
to the terminal of disconnected wires (U, V, W) from compressor respectively.
(b) Operation for judgment. 1) Power ON after SW6-4 on outdoor inverter PCB
was turned ON. 2) After 15 seconds since power has turned ON, LED start ON/OFF
for 5 seconds cyclically and it repeats 10 times. 3) Check ON/OFF status of 6
LED’s on the checker. 4) Judge the PCB by ON/OFF status of 6 LED’s on the
checker.
ON/OFF
If all of LED are ON/OFF
status of LED according to following pattern
Inverter PCB
Normal
If all of LED stay OFF or some of LED are ON/OFF
Anomalous
Power ON or start check operation 123
During this period, ON/OFF status of LED is repeated cyclically according to
following pattern
10
15 sec. 5sec. 5sec. 5sec.
5) Be sure to turn off SW6-4 on outdoor inverter PCB, after finishing the
check operation.
Inverter Checker
LED
LED ON/OFF pattern
LED1 LED2
LED3 LED4
LED5 LED6
LED1 LED2
LED3 LED4
LED5 LED6
LED1 LED2
LED3 LED4
LED5 LED6
LED1 LED2
LED3 LED4
LED5 LED6
LED1 LED2
LED3 LED4
LED5 LED6
LED1 LED2
LED3 LED4
LED5 LED6
Faston terminal
Red U
White V
Black
W
Connect to the terminal of the wires which are disconnected from compressor.
Cyclically
ON OFF
– 79 –
– 80 –
Models FDC100, 125, 140VNA-W Outdoor unit check points
Check items with the *mark when the power is ON.
- Power source check:
Measure the power source L,N (It is normal if it is AC220-240V)
Noise filter check: There should be continuity. There should be no shorts between phases.
DC reactor continuity check: Max 25m
Must be conductive. When fuse is blown, replace it or check wiring.
LED2 LED1 (Red) (Green)
LED2(Red) check: 1~5 time flash (Refer to page 5253)
When the outdoor unit fan motor is abnormal. (Refer to page 122165)
(7) Outdoor unit control failure diagnosis circuit diagram
’19 · PAC-SM-309
’19 · PAC-SM-309
– 81 –
FDC100,125,140VSA-W Outdoor unit check points
Check items with the *mark when the power is ON.
- Power source check: Measure the power source L1,L2,L3 (It is normal if it is AC380-415V)
Noise filter check: There should be continuity. There should be no shorts between phases.
DC reactor contiuity check:55m or less
LED1 LED2 (Green) (Red)
When the outdoor unit fan motor is anomalous. (Refer to page 122165)
LED2(Red) check: 1~5 time flash (Refer to page 5253)
– 197 –
PCA001Z854
MCCB ELCB
GN GN
Power source 1Phase 220 -240V 50Hz 220V 60Hz
TB
L RD
F (30A)
TB3
F (8A)
RD CN1
N WH YGN
TB4
(WH) WH
NOISE FILTER PCB2
TB5
TB7
TB8 TB6
TB
1 2 3
PWB7 L1 L2
CN1
TO INDOOR UNIT
POWER CABLE 1 2 SIGNAL WIRE 3
EEVC
EEVH
FM1
M
M
M
RD
BL
BR
OR
WH
WH Y
OR Y
BL
RD
WH
Y
OR
BL
RD
RD RD WH BR WH BR
WH BL
WH RD
CNW2 (OR)
CNP T12 T22 ( WH)
6 4321 6 4321 76541
CNEEV1 ( WH)
CNEEV2 ( RD)
CNFAN1 ( WH)
CT1
TB1 TB2 YGN T1
52X11
PCB1
52X15 52X3
52X14 52X1
LED1 LED2
1234
SW3
1234
SW5
123
SW7
SW1
F (2A) F (2A) F (3.15A )
CNF
CNR
CNS
CNH
( BK)
(WH)
( RD)
( BR)
CNTH
CNB
( WH)
( RD)
IPM
CM
TB7 RD U MS
TB8 WH V 3 YGN
TB9 BL W
E
CNPSL WH
WH RD
BK
BK
BK
Y
RD
RD
BK
BK
BK
BK
BK
BK
BR BR
t°
t°
t°
t°
t°
CH
20S
PSL
63H1 Tho-R1 Tho-D Tho-S Tho-A Tho-R2
Power cable, indoor-outdoor connecting wires
Model
MAX over current A
Power cable size mm2
100
125
24
5.5
140
At the connection with the duct type indoor unit.
Model
MAX over current A
Power cable size mm2
100
26
125
5.5
140
27
Power cable length m
22
Power cable length m
20
indoor-outdoor wire size x number
1.6mm x 3
indoor-outdoor wire size x number
1.6mm x 3
Earth wire size mm
1.6
Earth wire size mm
1.6
The specifications shown in the above table are for units without heaters. For
units with heaters, refer to the installation instructions or the construction
instructions of the indoor unit.
Switchgear of circuit breaker capacity which is calculated from MAX. over
current should be chosen along the regulations in each country. The cable
specifications are based on the assumption that a metal or plastic conduit is
used with no more than three cables contained in a conduit and a voltage drop
is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations.
Adapt it to the regulation in effect in each country.
Local setting switch SW3,5,7Set up at shipment OFF
SW3-1 Defrost control change
The defrost operation interval becomes shorter by turning ON this switch. This switch should be turned ON in the area where outside temperature becomes below the freezing point.
SW3-2 Snow guard fan control
When this switch is turned ON, the outdoor unit fan will run for 30 seconds in every 10 minutes, when outdoor temperature falls to 3°C or lower and the compressor is not running when the unit is used in a very snowy country, set this switch to ON.
SW3-3,4 Trial operation
Method of trial operation
1 Trial operation can be performed by using SW3-3,4.
2 Compressor will be in the operation when SW3-3 is ON.
3 Cooling trial operation will be performed when SW3-4 is OFF, and heating
trial operation when SW3-4 is ON
4 Be sure to turn OFF SW3-3 after the trial operation is finished.
SW5-2
High height difference operation control
Set this switch to ON when outdoor unit is installed at a position higher than indoor unit by 30m or more.
SW7-2 Defrost control change
Set this switch to ON when managing unit operation by remote control connected external equipment.
SW7-3 Lower noise silent mode
Upper limit of compressor speed and fan speed becomes lower in silent mode.
Meaning of marks
Item
CH CM CN CT1 EEVC EEVH F FM1 IPM LED1 LED2 L1,2 PSL SW1 SW3,5,7 TB THo-A THo-D
THo-R1,R2 THo-S 20S 52X1 52X3 52X11 52X14 52X15 63H1
Description
Crankcase heater Compressor motor Connector Current sensor Expansion valve for
cooling Expansion valve for heating Fuse Fan motor Intelligent power module
Indication lampGREEN Indication lampRED Reactor Low pressure sensor Switch
Local setting switch Terminal block Temperature sensor Outdoor air Temperature
sesor Discharge pipe Temperature sensor Heat exchanger Temperature sensor
Suction pipe Solenoid valve for 4-way valve Auxilliary relay Auxilliary relay
Auxilliary relayfor 20S Auxilliary relayfor CH Auxilliary relay High pressure
switch
Color marks
Mark Color BK Black BL Blue BR Brown GN Green OR Orange RD Red WH White Y
Yellow YGN YellowGreen
(2) Outdoor units Models FDC100VNA-W, 125VNA-W, 140VNA-W
’19 · PAC-SM-309
– 198 –
PCA001Z855
Power source 3Phase 380415V 50Hz
TB
L1 RD
L2 WH L3 BL
N BK
TB1
F10A
TB6 RD
TB2
TB7 WH
TB3 TB4
NOISE FILTER PCB2
T12 TB5
TB8 TB9
BL BK
GN
YGN BK BK
MCCB ELCB
TO INDOOR UNIT
POWER CABLE 1 2 SIGNAL WIRE 3
TB
1
RD
2 3 BL
YGN
BK RD BK RD WH
EEVC
EEVH
FM1
M
M
M
RD
WH Y
CNW1 Y
CNW3 WH
BL
BR
OR
WH
OR Y
BL
RD
WH
Y
OR
L
BL
RD
WH
Y
6 4321 6 4321 76541
TB3 TB2 TB1 T11 T12
CNEEV1 WH
CNEEV2 RD
CNFAN1 WH
PCB1
52X11 52X15
52X14 52X1 CNW2 OR
CNF BK
52X2
52X6 LED1 LED2
CNR WH
CNS RD
CNH BR
1234
SW3
1234
SW5
123
SW7
SW1
CNTH WH
F2A F2A F2A
IPM
CM TB7 RD U MS TB8 WH V 3
TB9 BL W
CNB CNPSL RD WH
WH RD
BK
BK
BK
Y
RD
RD
BK
BK
BK
BK
BK
BK
BR
BR
BR BR
t°
t°
t°
t°
t°
CH
20S
PSL
63H1 Tho-R1 Tho-D Tho-S Tho-A Tho-R2
Power cable, indoor-outdoor connecting wires
Model
MAX over current A
Power cable size mm2
100
125
15
3.5
140
At the connection with the duct type indoor unit.
Power cable length m
46
indoor-outdoor wire size x number
1.6mm x 3
Earth wire size mm
1.6
Model
MAX over current A
Power cable size mm2
Power cable length m
indoor-outdoor wire size x number
Earth wire size mm
100 17
125
140
18
3.5
40
1.6mm x 3
38
The specifications shown in the above table are for units without heaters. For
units with heaters, refer to the installation instructions or the construction
instructions of the indoor unit.
Switchgear of circuit breaker capacity which is calculated from MAX. over
current should be chosen along the regulations in each country. The cable
specifications are based on the assumption that a metal or plastic conduit is
used with no more than three cables contained in a conduit and a voltage drop
is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations.
Adapt it to the regulation in effect in each country.
1.6
Local setting switch SW3,5,7Set up at shipment OFF
SW3-1 Defrost control change
The defrost operation interval becomes shorter by turning ON this switch. This switch should be turned ON in the area where outside temperature becomes below the freezing point.
SW3-2 Snow guard fan control
When this switch is turned ON, the outdoor unit fan will run for 30 seconds in every 10 minutes, when outdoor temperature falls to 3°C or lower and the compressor is not running when the unit is used in a very snowy country, set this switch to ON.
SW3-3,4 Trial operation
Method of trial operation
1 Trial operation can be performed by using SW3-3,4.
2 Compressor will be in the operation when SW3-3 is ON.
3 Cooling trial operation will be performed when SW3-4 is OFF, and heating
trial operation when SW3-4 is ON
4 Be sure to turn OFF SW3-3 after the trial operation is finished.
SW5-2
High height difference operation control
Set this switch to ON when outdoor unit is installed at a position higher than indoor unit by 30m or more.
SW7-2 Defrost control change
Set this switch to ON when managing unit operation by remote control connected external equipment.
SW7-3 Lower noise silent mode
Upper limit of compressor speed and fan speed becomes lower in silent mode.
Meaning of marks
Item
Description
CH CM CN EEVC EEVH F FM1 IPM L LED1 LED2 PSL SW1 SW3,5,7 TB THo-A THo-D THo-R1,R2 THo-S 20S 52X1 52X2 52X6 52X11 52X14 52X15 63H1
Crankcase heater Compressor motor Connector Expansion valve for cooling Expansion valve for heating Fuse Fan motor Intelligent power module Reactor Indication lampGREEN Indication lampRED Low pressure sensor Switch Local setting switch Terminal block Temperature sensor Outdoor air Temperature sensor Discharge pipe Temperature sensor Heat exchanger Temperature sensor Suction pipe Solenoid valve for 4-way valve Auxilliary relay Auxilliary relay Auxiliary relayfor FM1 Auxilliary relayfor 20S Auxilliary relayfor CH Auxilliary relay High pressure switch
Color marks
Mark
Color
BK Black
BL Blue
BR Brown
GN Green
OR Orange
RD Red
WH White
Y Yellow
YGN YellowGreen
Models FDC100VSA-W, 125VSA-W, 140VSA-W
’19 · PAC-SM-309
’19 · PAC-SM-309
1.5 PIPING SYSTEM (1) Single type Models 100, 125, 140 Indoor unit
Gas line (ø15.88)
Outdoor unit
Check joint Muffler
Cooling cycle
Heating cycle
4-way valve
Temperature sensor (Tho-A)
Flare connecting Temperature sensor (Heat exchanger)
(Thi-R3 or Th22) Temperature sensor
(Return air) (Thi-A or Th1) Heat exchanger Temperature sensor (Heat exchanger)
(Thi-R1) Temperature sensor (Heat exchanger) (Thi-R2 or Th21)
Flare connecting
Liquid line (ø9.52)
Service valve (Flare connecting)
High pressure switch
63H1 Muffler
Check valve Temperature sensor (Tho-S)
Temperature sensor (Tho-D)
Heat exchanger
Lower pressure sensor (PSL)
Temperature sensor (Tho-R1)
Check joint
(Discharge) Compressor
(Suction)
Service valve (Flare connecting) Strainer
Strainer
Electronic expansion valve (cooling)(EEVC)
Receiver
Accumulator
Temperature sensor (Tho-R2)
Sub-cooling coil
Check joint
Strainer Strainer
Control cooling
Electronic expansion valve (heating)(EEVH)
(2) Twin type Models 100, 125, 140
Indoor unit
Indoor unit
Diameter joint of different (50,60 only)
Gas branch pipe
( ) 50,60:ø12.7 71:ø15.88
Gas line (ø15.88)
Outdoor unit
Check joint Muffler
Cooling cycle
Heating cycle
4-way valve
Temperature sensor (Tho-A)
Flare connecting
Temperature sensor (Heat exchanger)
(Thi-R3 or Th22) Temperature sensor (Return air)
(Thi-A or Th1) Heat exchanger
Temperature sensor (Heat exchanger)
(Thi-R1) Temperature sensor (Heat exchanger) (Thi-R2 or Th21)
Flare connecting (ø6.35)
Service valve (Flare connecting)
High pressure switch
63H1 Muffler
Check valve Temperature sensor (Tho-S)
Temperature sensor (Tho-D)
Liquid line (ø9.52)
Check joint
(Discharge) Compressor
(Suction)
Heat exchanger Lower pressure sensor
(PSL)
Temperature sensor (Tho-R1)
Accumulator Temperature sensor
(Tho-R2) Sub-cooling coil
Liquid branch pipe
(ø9.52)
Service valve (Flare connecting) Strainer
Strainer
Electronic expansion valve (cooling)(EEVC)
Receiver
Check joint
Strainer Strainer
Control cooling
Electronic expansion valve (heating)(EEVH)
– 199 –
(3) Triple type Model 140
Indoor unit
Indoor unit
’19 · PAC-SM-309
Indoor unit
Flare connecting (ø6.35)
Gas branch pipe
(ø12.7)
Gas line (ø15.88)
Flare connecting Temperature sensor (Heat exchanger) (Thi-R3 or Th22)
Temperature sensor (Return air) (Thi-A or Th1) Heat exchanger
Temperature sensor (Heat exchanger) (Thi-R1) Temperature sensor (Heat
exchanger) (Thi-R2 or Th21)
Liquid branch pipe (ø9.52)
Liquid line (ø9.52) Diameter joint of different
Check joint Muffler
Cooling cycle
Heating cycle
4-way valve
Temperature sensor (Tho-A)
Service valve (Flare connecting)
High pressure switch
63H1 Muffler
Check valve Temperature sensor (Tho-S)
Temperature sensor (Tho-D)
Heat exchanger
Lower pressure sensor (PSL)
Temperature sensor (Tho-R1)
Check joint
(Discharge) Compressor
(Suction)
Service valve (Flare connecting) Strainer
Strainer
Electronic expansion valve (cooling)(EEVC)
Receiver
Accumulator
Temperature sensor (Tho-R2)
Sub-cooling coil
Check joint
Strainer Strainer
Control cooling
Electronic expansion valve (heating)(EEVH)
Preset point of the protective devices
Parts name
Mark
Equipped unit
Temperature sensor (for protection overloading in heating)
Temperature sensor (for frost prevention)
Thi-R (Tho-A)
Thi-R (Th2)
Indoor unit
Temperature sensor (for protection high pressure in cooling.)
Tho-R Outdoor unit
Temperature sensor (for detecting discharge pipe temp.)
Tho-D Outdoor unit
High pressure switch (for protection)
63H1 Outdoor unit
Low pressure sensor (for protection)
PSL Outdoor unit
Note (1) Values in ( ) are for the SRK models.
100, 125, 140 model
OFF 63°C OFF 16°C
ON 56°C ON 17°C
OFF 1.0°C OFF 2.5°C
ON 10°C ON 8°C
OFF 51°C ON 65°C
OFF 115°C ON 85°C
OFF 4.15MPa ON 3.15MPa OFF 0.227MPa ON 0.079MPa
– 200 –
MICRO INVERTER PACKAGED AIR-CONDITIONERS
MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.
16-5 Konan 2-chome, Minato-ku, Tokyo, 108-8215, Japan http://www.mhi-
mth.co.jp/en/ Because of our policy of continuous improvement, we reserve the
right to make changes in all specifications without notice.
C Copyright MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS, LTD.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>