Danfoss SZ160-4RAI Scroll Compressors Instructions

June 4, 2024
Danfoss

Instructions
Danfoss scroll compressors
DSH / SM / SY / SZ / SH / WSH 

**** Installation and servicing of the compressor by qualified personnel only. Follow these instructions and sound refrigeration engineering practice relating to installation, commissioning, maintenance and service.

Introduction

These instructions pertain to the Danfoss scroll compressors DSH, SM, SY, SZ, SH & WSH scroll compressors used for air-conditioning systems. They provide necessary information regarding the safety and proper usage of this product.

Nameplate

Danfoss SZ160 4RAI Scroll Compressors - QR

A: Model number
B: Serial number
C: Refrigerant
D: Supply voltage, Starting current & Maximum operating current
E: Housing service pressure
F: Factory-charged lubricant

Operating map

Danfoss SZ160 4RAI Scroll Compressors - fig

! The compressor must only be used for its designed purpose(s) and within its scope of application (refer to «operating limits»). Consult Application guidelines and datasheet available from cc.danfoss.com
Under all circumstances, the EN378 (or other applicable local safety regulations) requirements must be fulfilled.

The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.7 bar) and hence cannot be connected as is; refer to the «assembly» section for the EN378 (or other further details.
The compressor must be  handled with caution in the vertical position (maximum offset from the vertical: 15°)

Instructions

Danfoss SZ160 4RAI Scroll Compressors - fig 1 When SM compressors are used with R417A, the factory-charged mineral oil 160P must be replaced by polyol ester oil 160SZ.

Electrical connections details

*DSH / SH / WSH 090 – 105 – 120 – 140 - 161* – 184*
SM 084 – 090 – 100 – 110 – 112 – 120 – 124 – 147 – 148 – 161 SZ 084 – 090 – 100 – 110 – 120 – 147 – 148 – 161**
These Danfoss scroll compressors are protected against overheating and overloading by an internal safety motor protector. However, an external manual reset overload protector is recommended for protecting the circuit against over-current.

All models except DSH / SH/ WSH140-3 & 161-3 & 184| DSH / SH / WSH140-3 & 161-3 & 184
---|---

Danfoss SZ160 4RAI Scroll Compressors - fig 2Danfoss SZ160 4RAI Scroll Compressors - fig
5 SM / SZ 115 – 125 – 160 – 175 – 185 versions with thermostat
These Danfoss scroll compressors are provided with a bimetallic single pole single throw thermostat which is located in the motor windings. Because the thermostat is an automatic reset device, it must be wired in a lockout safety circuit with a manual reset to restart the unit. For over-current protection, an external manual reset overload protector must be used. Danfoss SZ160 4RAI
Scroll Compressors - bimetallic

SH 180 – 240 – 295 – 300 – 380
DSH 240 – 295 – 381
SY/ SZ 240 – 300 – 380
SM / SZ 185 versions with an electronic module
These Danfoss scroll compressor motors are protected by an external module protecting against phase loss/reversal, overheating and high current draw.Danfoss SZ160 4RAI Scroll Compressors - motorsDanfoss SZ160 4RAI Scroll Compressors -
electronic SH/DSH485, DSH600
These Danfoss scroll compressor motors are protected by an external module protecting against phase loss/reversal, overheating, and high current draw.Danfoss SZ160 4RAI Scroll Compressors - reversal,

DSH485-3
These Danfoss scroll compressor motors are protected by two external modules protecting against phase loss/reversal, overheating and high current draw.

Danfoss SZ160 4RAI Scroll Compressors - Danfoss

Legend:
Fuses ……………………………………………………………………………..F1
Compressor contactor ……………………………………………….. KM
High-pressure safety switch………………………………………… HP
Discharge gas thermistor (embedded in compressors
DSH240-600 and SH485) …………………………………………. DGT
Surface Sump Heater ………………………………………………… SSH
Compressor motor ………………………………………………………..M
Motor Protection Module ………………………………………..MPM
Thermistor chain……………………………………………………………. S
Safety pressure switch ………………………………………………..LPS
Thermal magnetic motor circuit breaker ………………….. CB

Handling and storage

  • Handle the compressor with care. Use the dedicated handles in the packaging. Use the compressor lifting lug and use appropriate and safe lifting equipment.
  • Store and transport the compressor in an upright position.
  • Store the compressor between Ts min and Ts max values for LP side indicated on the compressor nameplate.
  •  Don’t expose the compressor and the packaging to rain or corrosive atmosphere.

 Safety measures before assembly

Never use the compressor in a flammable atmosphere.

  • Check before assembly that the compressor does not show any obvious signs of deterioration that could have occurred during inappropriate transportation, handling or storage.
  • The compressor ambient temperature may not exceed Ts max value for the LP side indicated on the compressor nameplate during off-cycle.
  • Mount the compressor on a horizontal flat surface with less than 3° slope.
  • Verify that the power supply corresponds to the compressor motor characteristics (see nameplate).
  • When installing DSH, SH, WSH or SZ, use equipment specifically reserved for HFC refrigerants that was never used for CFC or HCFC refrigerants.
  • Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
  • Use clean and dehydrated system components.
  • The piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations.

Assembly

  • The compressor must be mounted on rails or chassis according to Danfoss recommendations described in related product guidelines (type of spacer, tightening torques).
  • Slowly release the nitrogen-holding charge through the Schrader port.
  • Remove the gaskets when brazing roto lock connectors.
  • Always use new gaskets for assembly.
  • Connect the compressor to the system as soon as possible to avoid oil contamination from ambient moisture.
  • Avoid material entering the system while cutting tubes. Never drill holes where burrs cannot be removed.
  • Braze with great care using state-of-the-art techniques and vent piping with nitrogen gas flow.
  • Connect the required safety and control devices. When the Schrader port is used for this, remove the internal valve.
  • Do not exceed the maximum tightening torque for roto lock connections:
Rotolock connections Tightening torque
1″ rotolock 80 Nm
1 1/4 ” rotolock 90 Nm
1 3/4″ rotolock 110 Nm
2 1/4″ rotolock 145 Nm.

Leak detection

**** Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.

  • SM 084 to 185, SY 380, SZ 084 to 185, SZ 380, DSH / SH / WSH 090 to 184: Pressurize the system on the HP side first and then on the LP side. Never let the pressure on the LP side exceed the pressure on HP side with more than 5 bar. Such a pressure difference could cause internal compressor damage.
  • Do not use dye for leak detection.
  • Perform a leak detection test on the complete system.
  • The test pressure must not exceed 1.1 x PS value for LP side and PS value for HP side indicated on the compressor nameplate.
  • When a leak is discovered, repair the leak and repeat the leak detection.

Vacuum dehydration

  • Never use the compressor to evacuate the system.
  • Connect a vacuum pump to both the LP & HP sides.
  • Pull down the system under a vacuum of 500 µm Hg (0.67 mbar) absolute.
  • Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.

Electrical connections

  • Switch off and isolate the main power supply. See overleaf for wiring details.
  • All electrical components must be selected as per local standards and compressor requirements.
  • Refer to section 4 for electrical connection details.
  • The Danfoss scroll compressors only work correctly in one rotation direction. Line phases L1, L2, L3 must absolutely be connected to compressor terminals T1, T2, T3 to avoid reverse rotation.
  • According to the compressor model, electrical power is connected to the compressor terminals either by 4.8mm (10-32) screws or by M5 studs and nuts . In both cases use appropriate ring terminals, and fasten with 3Nm torque.
  • The thermostat connection (if present) is a ¼” AMP-AWE spade connector.
  • The compressor must be connected to the earth. For M5 nut, the maximum torque is 4Nm. For M4 nut, the maximum torque is 2Nm.

Filling the system

  • Keep the compressor switched off.
  • Fill the refrigerant in the liquid phase into the condenser or liquid receiver. The charge must be as close as possible to the nominal system charge to avoid low-pressure operation and excessive superheating. Never let the pressure on LP side exceed the pressure on the HP side with more than 5 bar. Such a pressure difference could cause internal compressor damage.
  • Keep the refrigerant charge below the indicated charge limits if possible. Above this limit;  protect the compressor against liquid flood-back with a pump-down cycle or suction line accumulator.
  •  Never leave the filling cylinder connected to the circuit.
Compressor models Refrigerant charge limit (kg)
SM/SZ 084, 090, 100 9.
SM/SZ 110,120 10
SM 112,124, 147 ,5Z147 8.
SM/SZ 115, 125 11
SM/SZ 148, 160, 161 13.
SM/SZ 175, 185 14.
SY/SZ 240 16
SY/SZ 380 20
DSH / SH /WSH 090 6.
DSH / SH /WSH 105, 120, 140, 161, 184 8.
SH 180, 240, 295,300 14.
DSH 240,295 15
SH 380 15.
SH 485, DSH600, DSH 381,485 17

Verification before commissioning

Use safety devices such as safety pressure switches and mechanical relief valves in compliance with both generally and locally applicable regulations and safety standards. Ensure that they are operational and properly set.
Check that the settings of high-pressure switches and relief valves don’t exceed the maximum service pressure of any system component.

  • A low-pressure switch is recommended to avoid vacuum operation. Minimum setting for SM/SY/SZ: 0.5 bar g. Minimum setting for DSH / SH / WSH: 1.7 bar g.
  • Verify that all electrical connections are properly fastened and in compliance with local regulations.
  • When a crankcase heater is required, it must be energized at least 12 hours before initial start-up and start-up after prolonged shutdown for belt-type crankcase heaters (6 hours for surface sump heaters).

Start-up

**** Never operate the compressor without the electrical box cover fitted.

  • Never start the compressor when no refrigerant is charged.
  • All service valves must be in the open position.
  • Balance the HP/LP pressure.
  • Energize the compressor. It must start promptly. If the compressor does not start, check wiring conformity and voltage on terminals.
  • Eventual reverse rotation can be detected by the following phenomena; the compressor doesn’t build up pressure, it has abnormally high sound level and abnormally low power consumption. In such a case, shut down the compressor immediately and connect the phases to their proper terminals. Most Danfoss scroll compressors are protected against reverse rotation either by internal reverse rotation protection or by the external electronic protection module. They will shut off automatically. Only SM 112, 124, 147, SZ147 have no reverse rotation protection. Prolonged reverse rotation will damage these compressors.
  • If the internal overload protector trips out (SM/SZ 084, 090, 100, 110, 112, 120, 124, 147,148, 161 and DSH / SH / WSH 090, 105, 120, 140, 161, 184), it must cool down to 60°C to reset. Depending on ambient temperature, this may take up to several hours.
  • If the internal pressure relief valve is opened (SY/SZ 240, 300, 380 / SH 380, 485 / DSH 381, 485, DSH600), the compressor sump will be warm and the compressor will trip out on the motor protector.

 Check with the running compressor

  • Check current draw and voltage.
  • Check suction superheat to reduce the risk of slugging.
  • Observe the oil level in the sight glass for about 60 minutes to ensure proper oil return to the compressor.
  • Respect the operating limits.
  • Check all tubes for abnormal vibration. Movements in excess of 1.5 mm require corrective measures such as tube brackets.
  • When needed, the additional refrigerant in the liquid phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this process.
  • Do not overcharge the system.
  • Never release refrigerant to the atmosphere.
  • For reversible systems, ensure that the 4-way valve does not reverse when the compressor is stopped due to heating or cooling demand (stop on the thermostat)
  • Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise and leak detection.
  • Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.

 Maintenance

Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools. Tubing temperature may exceed 100°C and can cause severe burns.
Ensure that periodic service inspection to ensure system reliability and as required by local regulations are performed. To prevent system-related compressor problems, the following periodic maintenance is recommended:

  • Verify that safety devices are operational and properly set.
  • Ensure that the system is leak tight.
  • Check the compressor current draw.
  • Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
  • Check that all electrical connections are still adequately fastened.
  • Keep the compressor clean and verify the absence of rust and oxidation on the compressor shell, tubes and electrical connections.

Warranty

Always transmit the model number and serial number with any claim filed regarding this product. The product warranty may be void in the following cases:

  • Absence of nameplate.
  • External modifications; in particular, drilling, welding, broken feet and shock marks.
  • Compressor opened or returned unsealed.
  • Rust, water or leak detection dye inside the compressor.
  • Use of a refrigerant or lubricant not approved by Danfoss.
  • Any deviation from recommended instructions pertaining to installation, application or maintenance.
  • Use in mobile applications.
  • Use in the explosive atmospheric environment.
  • No model number or serial number was transmitted with the warranty claim. The compressor is not designed to withstand natural disasters such as earthquakes, cyclones, floods…. or extreme events such as fires, terrorist attacks, military bombardments, or explosions of any kind. Danfoss Commercial Compressor is not liable or any malfunction of its product resulting from such events

 Disposal

Danfoss recommends that compressors and compressor oil should be recycled by a suitable company at its site.

Danfoss A/S
Climate Solutions « danfoss.com + +45 7488 2222
Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogs descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogs, brochures, videos, and other material.
Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All rights reserved.

© Danfoss
Climate Solutions
2021.11 8510197P05AB – AN245986497033en-000901

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals