PHILIPS SM136V WIA EL CoreLine Surface Mounted LED Panel Instruction Manual
- June 9, 2024
- Philips
Table of Contents
CoreLine
Surface mounted
SM136V WIA EL
SM136V WIA EL CoreLine Surface Mounted LED Panel
| Power| Lumen output (lm)| Efficacy (lm/(w)| CCT (K)| **UGR**
|
---|---|---|---|---|---|---
SM136V 43S/840 WIA W20L120 OC ELB3| 35W| 4300| 123| 4000| 19| 4.3/ 4.8
SM136V 43S/840 WIA W20L150 OC ELB3
SM136V 43S/840 WIA W20L150 OC W3 ELB3
Optional
Suspension kit:
(can not be used with Wieland versions) 911401806584 SM136Z SME-3 WH (WIA)
Plaster ceiling kit:
911401892180 RC132Z SMB-PLC
2022-08-24
442710705327
© 2022 Signify Holding. All rights reserved.
Printed in Poland
Data subject to change without notice
Keep for future reference:
www.philips.com/lighting
Suspension
Optional with 911401806584 SM136Z SME-3 WH(PSU)
Do not lift and handle the luminaire with the cable between driver (cover) and TrustSight invertor.
Lifetime
The batteries have a life time expectancy of 4 years when maintained properly.
Replace after that time!
Automatic emergency time selection
After installation and power up the driver will detect the battery and start
the automatic detection process.
– During automatic detection, the indicator LED willlight up with short green
flashes.
– Between minimum 6 and maximum 30 seconds the TrustSight driver will set the
battery type (number of cells) and will set the emergency output power
accordingly.
After that, the system is defined and fully operational. The battery type
definition has influence on the performance during the self-test and on the
battery charge method. When the automatic battery detection process is
disrupted, e.g. by switching off the permanent mains, the detection process is
stopped and the TrustSight emergency driver will go into emergency mode with
the lowest output power. At a next power up, the automatic detection process
will start again.
Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to
EN50172 clause 7.2.3 and 7.2.4.
Switch on in the emergency mode each month by simulation of a failure of the
supply to the normal lighting for a period sufficient to ensure that each lamp
is illuminated. Twice per year, each luminaire shall be tested for its full
rated duration (at least 3hrs).
For more information please consult the TrustSight Gen 3 Design in guide. The
latest version is available online.
LED indicator status
LED indicator (color/ flashing)| Error condition| Cause|
Sohrtiavt
---|---|---|---
Green/no flashing| | System OK battery M.y charged
Off| | Mains oft EM mode Rest mode, test in progress
Green /slow (1225s on 125s oft)| | System OK battery is charging
Green/fast ((225s on, 0255 off)| | System OK recently tested (c 5 clan
Australia mode only)
Red/no flashing| Battery voltage too high or too low| No battery connected|
Connect battery
| Wrong or bad battery connected| Replace battery
Red/fast (025s on 025s off)| Output voltage too low or too high| Wrong LED
load connected| Connect right load and perform functional test
No load connected or output shorted| Wrong connection| Connect right load and
perform functional test
Red/slow (025s or; 125s off)| Failed test due to battery| Battey end of life
Charger failure| Replace battery and perform duration test Replace driver
Red-green/fast
Fast flashing: (on-time = aas off-time = 025s)
Slow flashing: (on-time = 0254 off-time = 125s)| | DAL, device identification|
Green/short
on-time = 50ms off-time = 0.95s)| | Battery detection|
Inrush current
SM136V WIA
Electrical characteristics
Inrush current Ipeak | 4.8 A |
---|---|
Inrush current Twidth | 290 ( µs) |
MCB | No. of luminaires max. |
16A type B | ≤ 50 pcs |
– The luminaire shall be installed by a qualified electrician and wired in
accordance with the latest IEE electrical regulations or the national
requirements.
– The light source of this luminaire is not replaceable; when the light source
reaches its end of life the whole luminaire shall be replaced.
– During installation or maintaining the luminaire please use gloves to avoid
spots on the cover.
· To remove dirt and spots use the following:
· Dust: use micro fiber cloths only.
– Fingerprints, etc.: use a cleaner for synthetic materials with antistatic
properties.
– Luminaires not suitable for covering with thermally insulating material
– Luminaire must not be used or stored in corrosive environment where
hazardous materials such as Sulphur,Chlorine, Phthalates, etc, are present
– Only to be installed outside arm’s reach.
– If the external flexible cable or cord of this luminaire is damaged, it
shall be exclusively replaced by the manufacturer or his service agent or a
similar qualified person in order to avoid a hazard.
ATTENTION
OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES
According to new ErP requirement
This product contains a light source of energy efficiency class: see table or label.
Disconnect before servicing
Luminaire has basic insulation between Low Voltage supply and control
conductors.
The light source and/or control gear and/or the external flexible cable
contained in this luminaire shall only be replaced by the manufacturer or his
service agent or a similar qualified person.
Storage, installation, use, operation and maintenance of the products needs to
be performed exactly according the instructions in this manual and/or other
instructions as may be provided by us to guarantee safe use of the product
over its entire lifetime. Failure to adhere to these instructions will
invalidate your entitlement to warranty. Bolts with indication of torque
strength on the drawing need to be tightened using a calibrated torque wrench.
Pre-assembled bolts need to be retightened again to the required torque
specification to assure maximum strength over lifetime.
Zhaga-D4i and SR certified compatibility – For Zhaga-D4i/SR-Certified based luminaires only Zhaga-D4i/SR-Certified components/sensors are to be used (see also: https://www.zhagastandard.org/products / https://www.lighting.philips.co.uk/oem-emea/products/driving-connected- lighting). The functional compatibility of two SR-certified and/or Zhaga-D4i controllers/sensors to be used in combination, as well as the override possibility of any line-switch function used in an SR-based/Zhaga-D4i luminaire, is to be released by the master controller/sensor supplier. If using a NEMA 7-pin socket on an SR-based luminaire, a full system verification is required. Not following this advice can/will cause risk of damage and non- compliance for which Signify cannot take any responsibility.
©2022 Signify Holding
All rights reserved. Reproduction in whole or in part is prohibited without
the prior written consent of the copyright owner.
The information presented in this document does not form part of any quotation
or contract, is believed to be accurate and reliable and may be changed
without notice. No liability will be accepted by the publisher for any
consequence of its use.
Publication thereof does not convey nor imply any license under patent- or
other industrial or intellectual property rights.
Signify Holding
The Netherlands
References
- Identity Digital | Create authentic digital identities with the world's largest and most relevant domain extension portfolio.
- Welcome | Philips lighting
- Driving connected lighting | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Sustainable LED lighting solutions | Philips lighting
- Driving connected lighting | Philips lighting
- Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>