VESDA VLC-EX-US Smoke Detector Owner’s Manual

June 9, 2024
VESDA

**VESDA VLC-EX-US Smoke Detector Owner’s Manual

**

Introduction

The VESDA VLC-EX-US detector has been specifically designed to provide all the benefits of aspirating smoke detection, including very early warning, for the protection of hazardous applications with a Class 1 Division 2 classification.

The VLC-EX-US combines the well-proven VESDA VLP detection technology with a modified aspirator design, and incorporates them into an IP54 rated stainless steel enclosure.

Four variants and a remote display option

The VLC-EX-US is available in a version that is suited for small area applications up to 2000sq.ft (200m²) and another that is suited for medium area applications up to 8000sq.ft (800m²). Each of which is available in two versions, one that interfaces via relays only (RO) and one that interfaces via relays and VESD Anet (VN).

The VN version is compatible with the remote Display Module, which allows the current status of the detector to be reported in the most convenient location. The remote Display Module has 7 remote relays to support any combination of sig nalling that may be demanded by the application. The VN version allows several detectors to be linked together on VESD Anet thereby allowing one to act as a reference detector for other VESDA detectors.

Description

The VLC-EX-US is enclosed in a stainless steel housing which is comprised of the main enclosure and the front cover.

The main enclosure houses all the key components of the detector. All non- serviceable items such as the main processor board and detector chamber are mounted away from the general access area, protecting them during the installation and servicing process.

The front cover includes:

  • 5 LEDs: Fire, Pre-Alarm/Alert, Fault, OK, Reset/Isolate
  • Reset/Isolate Push Button (press to reset, press and hold to isolate)

Features

  • Suitable for Class 1 Division 2 applications
    • Groups A,B,C & D
  • Absolute smoke detection
  • Wide sensitivity range
  • Single pipe inlet
  • Five (5) status LEDs
  • Referencing
  • VESDAnet communication (VN)
  • Clean air barrier optics protection
  • Three (3) Alarm Levels
  • Three (3) Programmable Relays
  • Air flow monitoring
  • Optional remote display and relay capability
  • Simple mounting design
  • AutoLearn™
  • IP54 rated stainless steel enclosure

Approvals/Listings

  • UL
  • ULC
  • FM

Regional approvals listings and regulatory compliance vary between VESDA product models. Refer to www.xtralis.com for the latest product approvals matrix.

How it works

Air is continually drawn through the pipe network to a central detector by a high efficiency aspirator. Air entering the unit passes a flow sensor before a sample  is passed through a dual-stage dust filter. The first stage removes dust and dirt from the air sample before it enters the chamber for smoke detection. The second, ultrafine stage provides a clean air supply to be used inside the detection chamber to form clean air barriers, which protect the optical surfaces from contamination.

The detection chamber uses a stable, highly efficient laser light source and unique sensor configuration to achieve the optimum response to a wide range of smoke types. When smoke passes through the detection chamber it creates light scatter which is detected by the very sensitive sensor circuitry.

The status of the detector, all alarms, service and fault events, are monitored and
logged with time and date stamps. Status reporting can be transmitted via simple relay connections or across the advanced VESDAnet communications network (VN version only).

Installation Consideration

For a Class 1 Division 2 installation, the detector, sampling network and exhaust must be located within the same protected area. Detector accessories, VPS‑100US‑120 power supply, etc, are installed outside the classified area with interconnect wiring meeting NEC (NFPA 70) requirements for Class 1, Division 2 systems.

VLC Termination Card (VN)
VLC Termination Card

Terminal A

  1. Bias (-) (GND)
  2. Reset (-
  3. Reset (+)
  4. Bias (+)
  5. LED (-) (GND
  6. LED (+)
  7. FIRE (NO)
  8. FIRE (C)
  9. PRE-ALARM (NO)
  10. PRE-ALARM (C)
  11. FAULT (NO
  12. FAULT (C)
  13. FAULT (NC)

Terminal B

  1. Shield
  2. VESD Anet-A (-)
  3. VESD Anet-A (+)
  4. Shield
  5. VESD Anet-B (-)
  6. VESD Anet-B (+)
  7. Power (-)
  8. Power (+
  9. Power (-)
  10. Power (+)

VLC Termination Card (RO)
VLC Termination Card

Terminal A

  1. FIRE (NO
  2. FIRE (C)
  3. PRE-ALARM (NO)
  4. PRE-ALARM (C)
  5. FAULT (NO
  6. FAULT (C)
  7. FAULT (NC)

Terminal B

  1. Bias (-) (GND)
  2. Reset (-)
  3. Reset (+)
  4. Bias (+)
  5. LED (-) (GND)
  6. LED (+)
  7. Power (-)
  8. Power (+)
  9. Power (-)
  10. Power (+)

Ordering Information

Product

VLC-205 (VN) Class 1 Div 2 2000ft2 (200m2 )
VLC-200 (RO) Class 1 Div 2 2000ft2 (200m2 )
VLC-505 (VN) Class 1 Div 2 8000ft2 (800m2 )
VLC-500 (RO) Class 1 Div 2 8000ft2 (800m2 )
Remote Display (relays)
Remote Display (no relays)

Remote Relays (no display)*

Part number

VLC-205-EX-US
VLC-200-EX-US
VLC-505-EX-US
VLC-500-EX-US
VRT-J00
VRT-K00
VRT-500

Approvals Compliance

Please refer to the Product Guide for details regarding compliant design, installation and commissioning.

Specifications

  • Supply voltage: 18 to 30 VDC
  • Power consumption: 5.4 W quiescent, 5.9 W with alarm
  • Current consumption: 225 mA quiescent, 245 mA with alarm
  • Fuse rating: 1.6 A
  • Dimensions (WHD): 10 5 /8” x 10 5 /8” x 3 7 /8” (270 mm x 270 mm x 97 mm)
  • Weight: 10.8 lbs. (4.9 kg)
  • Operating conditions:
  • Ambient: 32°F to 103°F (0°C to 39°C) *
  • Tested: 14°F to 131°F (-10°C to 55°C)
  • Sampled Air: -4°F to 140°F (-20°C to 60°C)
  • Humidity: 10% to 95% RH, non-condensing
  • Sampling network: VLC-EX-US 200 Series
  • Maximum area of Coverage: 2000 sq.ft (200 sq.m)
  • Maximum pipe length: 1 x 65 ft (20 m), 2 x 50 ft (15 m)
  • Design: Pre-engineered VLC-EX-US 500 Series
  • Maximum area of Coverage: 8000 sq.ft (800 sq.m)
  • Maximum pipe length: 1 x 260 ft (80 m), 2 x 164 ft (50 m)
  • Design: ASPIRE2™
  • Pipe: Internal Diameter 9 /16”–7 /8” (15 mm–21 mm)  External Diameter 1 inch. (25 mm)
  • Relays : 3 Relays rated 2 A @ 30 VDC Fire (NO) Pre-Alarm (NO) Alert/Fault (Maintenance & Isolate) (NC/NO) Configurable as latching or non-latching
  • Enclosure:
  • Material: Grade 304 stainless steel
  • Rating: IP54 **
  • Cable access: 2 x 7 /8” (23.2 mm) cable entries Cable glands and blanking plugs NOT supplied
  • Cable termination: Screw Terminal blocks 0.2–2.5 sq mm (30–12 AWG)
  • Alarm sensitivity range: 0.0015% to 6.25% obs/ft (0.005% to 20% obs/m)
  • Threshold setting range:
    • Alert: 0.0015%–0.6218% obs/ft (0.005%–1.990% obs/m)
    • Pre-Alarm: 0.0031%–0.6234% obs/ft (0.010%–1.995% obs/m)
    • Fire: 0.0046%–6.25% obs/ft*** (0.015%–20.00% obs/m)

*Limited to 4% obs/ft for UL

Software features:
Event log: Up to 12,000 events stored in FIFO format Smoke level, user actions, alarms and faults with time and date stamp
Auto Learn: Minimum 15 minutes, maximum 15 days. Recommended minimum 14 days. During Auto Learn thresholds are NOT changed from pre-set values.

Configurable general input (24 VDC): Standby, Mains OK or Reset/Isolate

Product UL listed for use from 32°F to 104°F (0°C to 38°C) Product Enclosure Rating has not been evaluated by UL.

www.xtralis.com
UK and Europe +44 1442 242 330 D-A-CH +49 4347 903 0 The Americas +1 781 740 2223 Middle East +962 6 588 5622 Asia +86 21 5240 0077 Australia and New Zealand +61 3 9936 7000

The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied warranties of merchantability and fitness for a particular purpose are expressly excluded.
This document includes registered and unregistered trademarks. All trademarks displayed are the trademarks of their respective owners. Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label.
This document is subject to copyright owned by Xtralis AG (“Xtralis”). You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written consent of X tralis.

Doc. no. 21566_01

firealarmresources.com

VESDA Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals