The VESDA VLC detector has been specifically designed to provide all the benefits of aspirating smoke detection, including very early warning, in single environment small areas and where space is a premium. The VLC combines the well-proven VESDA VLP detection technology with a modified aspirator design, and incorporates them into a compact enclosure with a simplified display.

Two variants and a remote display option
The VLC is available in two versions, one that interfaces via relays only (RO) and one that interfaces via relays and VESDAnet (VN).
The VN version is compatible with the remote Display Module, which allows the current status of the detector to be reported in the most convenient location. The remote Display Module has 7 remote relays to support any combination of signalling that may be demanded by the application. The VN version allows several detectors to be linked together on VESDAnet thereby allowing one to act as a reference detector for other VESDA detectors.

Description

The VLC is made up of two parts: the main enclosure and the front cover. The main enclosure houses all the key components of the detector. All non- serviceable items like the main processor board and detector chamber are mounted away from the general access area, protecting them during the installation and service process.

The front cover includes:

  • 5 LEDs : Fire, Pre-Alarm/Alert, Fault, OK, Reset/Isolate
  • Reset/Isolate Push Button (press to reset, press and hold to isolate)

Features

  • Absolute smoke detection
  • Wide sensitivity range
  • Single pipe inlet
  • Five (5) status LEDs
  • Referencing
  • VESDAnet communication (VN)
  • Clean air barrier optics protection
  • Three (3) Alarm Levels
  • Three (3) Programmable Relays
  • Air flow monitoring
  • Optional remote display and relay capability
  • Simple mounting design
  • AutoLearn™

Approvals/Listings

  • UL
  • ULC
  • FM
  • CCC
  • ActivFire
  • CE
  • LPCB
  • VdS
  • NF
  • VNIIPO
  • EN 54-20
    • Class A (30 holes / 0.05% obs/m)
    • Class B (36 holes / 0.09% obs/m)
    • Class C (40 holes / 0.165% obs/m)

Classification of any configuration is determined using ASPIRE2. Regional approvals listings and regulatory compliance vary between VESDA product models. Refer to www.xtralis.com for the latest product approvals matrix.

VLC Termination Card (VN)

Terminal A

  1. Bias (-) (GND)
  2. Reset (-)
  3. Reset (-)
  4. Bias (+)
  5. LED ) (GND)
  6. LED (+)
  7. FIRE (NO)
  8. FIRE (C)
  9. PRE-ALARM (NO)
  10. PRE-ALARM (C)
  11. FAULT (NO)
  12. FAULT (C)
  13. FAULT (NC)

TerminalB

  1. Shield
  2. VESDAnet-A (-)
  3. VESDAnet-A (+)
  4. Shield
  5. VESDAnet-B (-)
  6. VESDAnet-B (+)
  7. Power (-)
  8. Power (+)
  9. Power (-)
  10. Power (+)
VLC Termination Card (RO)

Terminal A

  1. FIRE (NO)
  2. FIRE (C)
  3. PRE-ALARM (NO)
  4. PRE-ALARM (C)
  5. FAULT (NO)
  6. FAULT (C)
  7. FAULT (NC)

Terminal B

  1. Bias (-) (GND)
  2. Reset (-)
  3. Reset (+)
  4. Bias (+)
  5. LED (-) (GND)
  6. LED (+)
  7. Power (-)
  8. Power (+)
  9. Power (-)
  10. Power (+)

Specifications

Supply voltage:
18 to 30 VDC

Power consumption:
5.4 W quiescent, 5.9 W with alarm

Current consumption:
225 mA quiescent, 245 mA with alarm

Fuse rating:
1.6 A

Dimensions (WHD):
225 mm x 225 mm x 85 mm (8 7/8” x 8 7/8”x 3 3/8”)

Weight:
1.9 kg (4.2 lbs.)

Operating conditions:

  • Ambient : 0°C to 39°C (32°F to 103°F) *
  • Tested : -10°C to 55°C (14°F to 131°F)
  • Sampled Air : -20°C to 60°C (-4°F to 140°F)
  • Humidity : 10% to 95% RH, non-condensing

Storage conditions (non-operational):

  • Humidity : Dry (<95%)
  • Temperature : 0° to 85° C (32°F to 185°F)
  • Must not be exposed to sunlight or other radiation sources

Sampling network:
Maximum area of coverage

  • Code compliant : 800 m² (8000 sq.ft)
  • Maximum (120sec transport time): 2,370 m² (25,500 sq.ft).

Local code requirements shall take precedence

Maximum pipe lengths:
1 x 80 m (260ft), 2 x 50 m (164ft)

Computer design tool:
ASPIRE2™

Pipe:

  • Internal Diameter 15 mm–21 mm (9/16”–7/8”)
  • External Diameter 25 mm (1”)

Relays:

  • 3 Relays rated 2 A @ 30 VDC
  • Fire (NO)
  • Pre-Alarm (NO)
  • Alert/Fault (Maintenance & Isolate) (NC/NO)
  • Configurable as latching or non-latching

IP rating:
IP30

Cable access:
4 x 25 mm (1”) cable entries

Cable termination:
Screw Terminal blocks 0.2–2.5 sq mm (30–12 AWG)

Alarm sensitivity range:
0.005% to 20% obs/m (0.0015% to 6.25% obs/ft)

Threshold setting range:

  • Alert : 0.005%–1.990% obs/m (0.0015%–0.6218% obs/ft)
  • Pre-Alarm : 0.010%–1.995% obs/m (0.0031%–0.6234% obs/ft)
  • Fire : 0.015%–20.00% obs/m (0.0046%–6.25% obs/ft)*

Software features:
Event log: Up to 12,000 events stored in FIFO format Smoke level, user actions, alarms and faults with time and date stamp AutoLearn: Minimum 15 minutes, maximum 15 days. Recommended minimum 14 days. During AutoLearn thresholds are NOT changed from pre-set values.

Configurable general input (24 VDC):
Standby, Mains OK or Reset/Isolate

Product UL listed for use from 0°C to 38°C (32°F to 104°F)

Ordering Information

Product/Part number

  • VESDA VLC – VESDAnet VLC-505
  • VESDA VLC – Relays Only VLC-500
  • Remote Display (relays) VRT-J00
  • Remote Display (no relays) VRT-K00
  • Remote Relays (no display) VRT-500

www.xtralis.com

UK and Europe +44 1442 242 330 D-A-CH +49 431 23284 1 The Americas +1 781 740 2223 Middle East +962 6 588 5622 Asia +86 21 5240 0077 Australia and New Zealand +61 3 9936 7000

The contents of this document are provided on an “as is” basis. No representation or warranty (either express or implied) is made as to the completeness, accuracy or reliability of the contents of this document. The manufacturer reserves the right to change designs or specifications without obligation and without further notice. Except as otherwise provided, all warranties, express or implied, including without limitation any implied warranties of merchantability and fitness for a particular purpose are expressly excluded. Xtralis, the Xtralis logo,

The Sooner You Know, VESDA-E, VESDA, ICAM, ECO, OSID, HeiTel, ADPRO, IntrusionTrace, LoiterTrace, ClientTrace, SmokeTrace, XOa, XOh, iTrace, iCommand, iRespond, iCommission, and iPIR are trademarks and/or registered trademarks of Xtralis and/or its subsidiaries in the United States and/or other countries. Other brand names mentioned herein are for identification purposes only and may be trademarks of their respective holder(s). Your use of this document does not constitute or create a licence or any other right to use the name and/or trademark and/or label. This document is subject to copyright owned by Xtralis. You agree not to copy, communicate to the public, adapt, distribute, transfer, sell, modify or publish any contents of this document without the express prior written consent of Xtralis. firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals