VESDA VES-A00-P, VES-A10-P Thermostick Elettrotecnica User Guide
- June 9, 2024
- VESDA
Table of Contents
VESDA VES-A00-P, VES-A10-P Thermostick Elettrotecnica
The VESDA-E VES is similar to the flagship VESDA-E VEP aspirating smoke
detector but also includes a valve mechanism in the inlet manifold and
software to control the airflow from the four Sectors (pipes). This
configuration enables a single zone to be divided into four separate sectors,
for example, distinguishing between separate aisles within a data room. The
VES enables the user to locate the source of smoke by identifying the first
sector to reach the Alert level. The detector then continues to sample from
all sectors to monitor fire growth and will report separate alarm levels for
each sector. The VES provides four individually configurable alarm levels
(Alert, Action, Fire 1 and Fire 2) for each sector allowing optimum protection
in a wide range of applications. Built on the Flair detection technology and
years of application experience, VES detectors achieve consistent performance
over their lifetime via absolute calibration. In addition, the VES delivers a
range of revolutionary features that provide user value.
How it Works
The VES draws air from all sectors in use. If the smoke level reaches the Adaptive Scan Threshold, the VES quickly scans each sector to identify which sector is carrying smoke. The first sector to reach the Alert level is designated as the First Alarm Sector (FAS) and this sector is signalled to the user. If two or more sectors reach the Alert level then, the sector with the highest smoke concentration is designated as the First Alarm Sector (FAS). Once Fast Scan is completed and the FAS identified, the VES continues to closely monitor all four sectors to track fire growth and maintain full protection of the area.
Flair Detection Technology
Flair is the revolutionary detection chamber that forms the core of the VESDA-E VES, providing higher stability and increased longevity. Direct imaging of the sampled particles using a CMOS imager combined with multiple photo-diodes allows better detection and fewer nuisance alarms.
The VES Display
The VES display Home page has a bar graph to indicate the smoke level and adaptive scan threshold. Fault icons are also included to indicate various fault conditions. When the adaptive scan threshold is exceeded the VES display automatically transitions to the Sector status page to indicate the smoke level and alarm level per sector. If alarms are configured as latched then alarm indication per sector will be retained until Reset is applied. The VES display can only return to the Home page under user control.
Installation, Commissioning and Operation
VESDA-E VES is equipped with a powerful aspirator that enables the use of 560
m (1,837 ft)
of total pipe length. Out of box operation is made possible with AutoConfig
which allows airflow normalisation and AutoLearn Smoke and Flow to be
initiated from within the detector. VES is fully supported by Xtralis VSC and
ASPIRE software applications which facilitate ease of pipe network design,
system commissioning and maintenance.
VESDAnet™
VESDA devices communicate on VESDAnet which provides a robust bidirectional communication network allowing continued redundant operation even during single point wiring failures. VESDAnet enables primary reporting, centralized configuration, control, maintenance and monitoring.
Ethernet and WiFi connectivity
VESDA-E detectors offer Ethernet and WiFi connectivity as standard features. The detector can be added to a corporate network, allowing WiFi enabled tablet devices and PC’s installed with Xtralis monitoring and configuration software to connect wirelessly to the detector via the network.
Backward Compatibility
VESDA-E VES is compatible with existing VESDA installations. The detector occupies the same mounting footprint, pipe, conduit and electrical connector positioning as VESDA VLS. VES is also compatible with existing VESDAnet installations allowing monitoring of both VESDA-E and legacy detectors via the latest iVESDA application.
Features
- Sector addressability for up to four sectors
- Adaptive scan threshold
- Flair detection technology delivers reliable very early warning in a wide range of environments with minimal nuisance alarms
- Multi stage filtration and optical protection with clean air barriers ensures lifetime detection performance
- Four configurable alarm levels per sector and a wide sensitivity range deliver optimum protection for the widest range of applications Intuitive LCD display provides instant status information for immediate response
- Flow fault thresholds per port accommodate varying airflow conditions
- Smart on-board filter retains dust count and remaining filter life for predictable maintenance
- Extensive event log (20,000 events) for event analysis and system diagnostics
- AutoLearn™ smoke and flow for reliable and rapid commissioning
- Backward compatible with VLS and VESDAnet
- Ethernet for connectivity with Xtralis software for configuration, secondary monitoring and maintenance
- Secondary monitoring and maintenance via WiFi
- USB for PC configuration, and firmware upgrade using a memory stick
- Two programmable GPIs (1 monitored) for flexible remote control
- Field replaceable sub-assemblies enable faster service and maximum uptime
Listings/Approvals
- UL
- ULC
Regional approvals listings and regulatory compliance vary between product models. Refer to www.xtralis.com for the latest product approvals matrix.
Specifications
Supply voltage | 18-30 VDC (24 V Nominal) |
---|---|
Power consumption @ 24 VDC | VES-A00-P |
Aspirator Setting | 1 |
Power (Quiescent) | 7.0 W |
Power (In Alarm) | 7.8 W |
Dimensions (WHD) | 350 mm x 225 mm x 135 mm (13.8 in x 8.9 in x 5.3 in) |
Weight | 4.3 kg (9.5 lb) |
Operating conditions | Ambient: 0°C to 39°C (32°F to 102°F) * |
Tested to (EN54-20): -10°C to 55°C (14°F to 131°F)
Sampled Air: -20°C to 60°C (-4°F to 140°F) ** Humidity: 5% to 95% RH, non- condensing
Area Coverage| 2,000 m2 (21,520 sq. ft)
Min. airflow per pipe| 20 l/m
Pipe Length (Linear)| 280 m (919 ft)
Pipe Length (Branched)| 560 m (1,837 ft)
Pipe lengths depending on number of pipes in use| 2 Pipe
3 Pipe 4 Pipe
100 m (328 ft) 80 m (262 ft) 70 m (230 ft)
No. of holes (A/B/C)| 40/80/100*
Computer design tool| ASPIRE
Pipe| Inlet: External diameter 25 mm or 1.05 in (3/4 in IPS) Exhaust:
External diameter 25 mm or 1.05 in (3/4 in IPS) via adaptor
Relays| 12 programmable relays (latching or non-latching states)
Contacts rated 2 A @ 30 VDC (Resistive)
IP rating| IP40
Cable access| 4 x 26 mm (1.02 in) cable entries
Cable termination| Screw Terminal blocks 0.2–2.5 sq mm (24–14 AWG)
Dynamic Range| 0.001% to 32% obs/m (0.0003% to 10% obs/ft)
Sensitivity Range| 0.005 to 20% obs/m (0.0016% to 6.25% obs/ft)
Threshold setting range**| Alert: 0.005% to 2.0% obs/m (0.0016% to 0.625%
obs/ft)
Action: 0.005% to 2.0% obs/m (0.0016% to 0.625% obs/ft)
Fire1: 0.010% to 2.0% obs/m (0.0031% to 0.625% obs/ft)
Fire2: 0.020% to 20.0% obs/m (0.0063% to 6.25% obs/ft)
Software features| Event log: Up to 20,000 events
Smoke level and alarm threshold levels, user actions, alarms and faults with time and date stamp
AutoLearn: Detector learns Alarm Thresholds and Flow Fault thresholds by monitoring the environment.
- Product UL listed for use from 0°C to 38°C (32°F to 100°F).
- Sampled Air temperature shall reach Detector Ambient temperature upon entry into Detector. Refer to Xtralis Design Guides & Application Notes for sampled air pre-conditioning.
- Subject to agency confirmation.
Ordering Information
VESDA-E VES with LEDs, Plastic Enclosure | VES-A00-P |
---|---|
VESDA-E VES with 3.5” Display, Plastic Enclosure | VES-A10-P |
VESDA-E VES with LEDs, Plastic Enclosure – NF | VES-A00-P-NF |
VESDA-E VES with 3.5” Display, Plastic Enclosure – NF | VES-A10-P-NF |
VESDA-E VES Demo Kit | VKT-855 |
Spare Parts
VESDA-E VES Scanner Manifold Spare | VSP-955 |
---|---|
VESDA-E Mounting Bracket | VSP-960 |
VESDA-E Exhaust adaptor US | VSP-961 |
VESDA-E Filter | VSP-962 |
VESDA-E Filter – 20 Pieces | VSP-962-20 |
VESDA-E Aspirator | VSP-963 |
VESDA-E Smoke Detection Chamber – MK3 | VSP-964-03 |
VESDA-E Sampling Module | VSP-965 |
VESDA-E VES-A00-P Front Cover Plastic (LEDs) | VSP-968 |
VESDA-E VES-A10-P Front Cover Plastic (3.5” Display) | VSP-969-S |
Approvals Compliance
Please refer to the Product Guide for details regarding compliant design, installation and commissioning.
3.5” Display
www.xtralis.com
UK and Europe +44 1442 242 330 The Americas +1 800 229 4434
Middle East +962 6 588 5622 Asia +86 21 5240 0077 Australia and New Zealand
+61 3 9936 7000
The contents of this document are provided on an “as is” basis. No
representation or warranty (either express or implied) is made as to the
completeness, accuracy or reliability of the contents of this document. The
manufacturer reserves the right to change designs or specifications without
obligation and without further notice. Except as otherwise provided, all
warranties, express or implied, including without limitation any implied
warranties of merchantability and fitness for a particular purpose are
expressly excluded.
Xtralis, the Xtralis logo, The Sooner You Know, VESDA-E, VESDA, ICAM, ECO,
OSID, and Sensepoint are trademarks and/or registered trademarks of Xtralis
and/or its subsidiaries in the United States and/or other countries. Other
brand names mentioned herein are for identification purposes only and may be
trademarks of their respective holder(s). Your use of this document does not
constitute or create a licence or any other right to use the name and/or
trademark and/or label.
This document is subject to copyright owned by Xtralis. You agree not to copy,
communicate to the public, adapt, distribute, transfer, sell, modify or
publish any contents of this document without the express prior written
consent of Xtralis.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>