SYSTEM SENSOR DH100ACDC Air Duct Smoke Detector User Manual
- June 9, 2024
- SYSTEM SENSOR
Table of Contents
- DH100ACDC Air Duct Smoke Detector
- Before Installing
- General Description
- Limitations Of Duct Smoke Detectors
- Figure 1: Exploded View Of Duct Smoke Detector Components
- Contents Of The Duct Smoke Detector Kit
- Installation Sequence
- Duct Smoke Detector Maintenance And Test Procedures
- Detector Cleaning Procedures
- Board Replacement
- Model DH100ACDC Air Duct Smoke Detector Specifications
- Three-Year Limited Warranty
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
DH100ACDC Air Duct Smoke Detector
INSTALLATION AND MAINTENANCE INSTRUCTIONS
DH100ACDC Air Duct Smoke Detecto r
Before Installing
Please thoroughly read the System Sensor Guide for Proper Use of Smoke
Detectors in Duct Applications (I56-473), which provides detailed information
on detector spacing, placement, zoning, wiring, and special applications.
Copies of this manual are available from System Sensor. NFPA Standards 72 and
90A should also be referenced for detailed information.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This detector must be tested and maintained regularly
following NFPA 72 requirements. The detector should be cleaned at least once a
year.
General Description
An HVAC system supplies conditioned air to virtually every area of a building.
Smoke introduced into this air duct system will be distributed to the entire
building. Smoke detectors designed for use in air duct systems are used to
sense the presence of smoke in the duct.
Model DH100ACDC Air Duct Smoke Detectors are supplied as an ionization model
or photoelectronic model. These two smoke detection methods are combined with
an efficient housing design that samples air passing through a duct and allows
detection of a developing hazardous condition. When sufficient smoke is
sensed, an alarm signal is initiated at the fire control panel monitoring the
detector, and appropriate action can be taken to shut off fans, blowers,
change over air handling systems, etc. These actions
can facilitate the management of toxic smoke and fire gases throughout the
areas served by the duct system.
DH100ACDC detectors are designed to operate on 24 VDC/ VAC, 120 VAC, or 240
VAC. Alarm and supervisory relay contacts are available for control panel
interface (alarm initiation), HVAC control, and other auxiliary functions.
Auxiliary relays are also provided for fan shut down or signaling of up to 9
other detectors in the loop for multiple fan shut down. These detectors are
not designed for 2-wire applications.
For testing, the alarm can be enabled by a magnet activated test switch or by
the optional remote test station.
The duct smoke detector latches into alarm state when an alarm occurs.
A green LED flashes to indicate power, a red LED signals local alarm
indication, and optional accessories offer a variety of annunciation
capabilities.
The DH100ACDC can be reset by a momentary power interruption, the reset button
on the front cover, the control panel, or remote reset accessory.
Limitations Of Duct Smoke Detectors
WARNING
The National Fire Protection Association has established that DUCT DETECTORS
MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR
PROTECTION as a means of providing life safety. Nor are they a substitute
for early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user
read NFPA Standards 90A, 72, and 101. The DH100ACDC Air Duct Smoke Detectors
are listed per UL 268A.
WARNING
This device will not operate without electrical power. Fire situations may
cause an interruption of power. The system safeguards should be discussed with
your local fire
protection specialist.
WARNING
This device will not sense smoke unless the ventilation system is operating
and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed according to the
instructions in this manual. Furthermore, the detector MUST be protected from
the elements and operated within ALL electrical and environmental
specifications listed in this manual. Failure to comply with these
requirements may prevent the detector from activating
when smoke is present in the air duct.
Figure 1: Exploded View Of Duct Smoke Detector Components
Contents Of The Duct Smoke Detector Kit
- Complete housing base and cover assembly
- Two #10 machine screws for mounting
- Two sampling tube filters
- One test magnet
- Drilling template
- Two foam gaskets
- Four #6-self tapping mounting screws for the metal sampling tube and optional exhaust tube extension
- Two jack nuts
- One inlet tube end plug
- One telescoping sampling tube
- One #8 self-tapping screw for the telescoping sampling tube
NOTE: For ducts over 11/2 feet, longer inlet sampling tubes must be ordered to complete the installation. They must be the correct length for the width of the duct where they will be installed. See Table 1 on page 3 to determine the inlet tube required for different duct widths.
Installation Sequence
[5.1] Verify Duct Air Flow Direction And Velocity
Model DH100ACDC detectors are designed to be used in air handling systems
having air velocities of 500 to 4000 feet per minute. Be sure to check
engineering pecifications to ensure that the air velocity in the duct falls
within these parameters. If necessary, use a velocity meter to check the air
velocity in the duct.
[5.2] Drill The Mounting Holes
Remove the paper backing from the mounting template supplied. Affix the
template to the duct at the desired mounting location. Make sure the template
lies flat and smooth on the duct. Center punch holes A and B. Drill the holes
as indicated on the template. Insert the two jack nut receptacles. Drive a #10
machine screw into jacket to flare the retainer, then back out the screw to
use for detector mounting.
Tube Installation Chart:
Supplemental Tube Holes | Duct Width |
---|---|
5 | 512″-14″ |
6 | 614″-16″ |
7 | 716″-18″ |
[5.2.1] Sampling Tube Installation for Ducts Less Than 11/2 Feet Wide (see Figure 2)
- Remove the front cover.
- Use the tube installation chart above to determine the set screw setting.
- Slide the sampling tube into the housing bushing.
- Align the holes in the bushing with the holes in the sampling tube. Make sure the number of exposed holes on the supplemental tube matches the number as determined in step 2.
Secure with the #8 self-tapping screw into the bottom of the permanent tube.
NOTE: For ducts greater than 1 1/2 feet in width, refer to sections
[5.4.1] and [5.4.2].
Figure 2. Sampling tube connected to duct smoke detector: [5.3] Secure The Detector Housing To The Duct
Slide the foam gaskets over the tube bushings as shown in Figure 3. Use the
two machine screws to screw the detector housing to the duct.
CAUTION: Do not overtighten the screws.
Figure 3. Installation of foam gaskets over sampling tube
bushings: [5.4] Sampling Tube
Installation for Ducts Greater
Than 11/2 Feet Wide
The sampling tube is identified by a series of air inlet holes on the tube. A
telescoping tube is included for ducts up to 18″ in width. All other lengths
must be purchased separately. Order the correct length, as specified in Table
1, for width of the duct where it will be installed. The exhaust tube is
molded onto the base of the duct housing, and the A2440-00 Exhaust Tube
Extension is available as an accessory in those cases where the molded
exhaust port does not extend at least 2 inches into the duct.
The inlet tube is always installed with the air inlet holes facing into the
air flow. To assist proper installation, the tube’s mounting flange is marked
with arrows. Make sure the inlet tube is mounted so that the arrows point into
the air flow (see Figure 4). Figure 5 shows the various combinations of tube
mounting configurations with respect to air flow. Mounting the detector
housing in a vertical orientation is acceptable, provided that the air flows
directly into the sampling tube holes as indicated in Figure 4
Table 1. Inlet tubes required for different duct widths:
Outside Duct Width | Inlet Tube Required |
---|---|
1 to 2 ft. | ST-1.5 |
2 to 4 ft. | ST-3 |
4 to 8 ft. | ST-5 |
8 to 12 ft. | ST-10 |
[5.4.1] Installation For Ducts Greater Than 11/2 Feet But Less Than 8 Feet Wide
- If the tube is longer than the width of the air duct, drill a 3 /4″ hole in the duct opposite the hole already cut for the inlet tube. Make sure the hole is 1″ to 2″ below the inlet hole on the opposite side of the duct to allow moisture drainage away from the detector. If the tube is shorter than the width of the air duct, install the end plug into the inlet tube as shown in Figure 4. Sampling tubes over 3 ft. long must be supported at the end opposite the duct detector.
- Slide the tube into the housing bushing that meets the air flow first. Position the tube so that the arrows point into the air flow.
- Secure the tube flange to the housing bushing with two #6 self-tapping screws.
- For tubes longer than the width of the air duct, the tube should extend out of the opposite side of the duct. If there are more than 2 holes in the section of the tube extending out of the duct, select a different length using
Table 1. Otherwise, trim the end of the tube protruding through the duct
so that 1″ to 2″ of the tube extend outside the duct. Plug this end with the
end plug and tape closed
any holes in the protruding section of the tube. Be sure to seal the duct
where the tube protrudes.
Figure 4. Air duct detector inlet sampling tube: Figure 5. Tube mounting configurations with varying air
flow direction: WARNING
In no case should more than 2 air inlet holes be cut off the tube. There must
be a minimum of 10 holes in the tube exposed to the air stream.
[5.4.2] Installation For Ducts More Than 8 Feet Wide
NOTE: To install inlet tubes in ducts more than 8 feet wide, work must be
performed inside the air duct. Sampling of air in ducts wider than 8 feet is
accomplished by
using the ST-10 inlet sampling tube. If the tube is shorter than the width of
the air duct, install the end plug into the inlet tube as shown in Figure 4
and support the end opposite the duct smoke detector. Install the inlet tube
as follows:
-
Drill a 3/4-inch hole in the duct directly opposite the hole already drilled for the inlet tube. Make sure the hole is 1 to 2″ below the inlet hole on the opposite side of the
duct to allow for moisture drainage. -
Slide the inlet tube with the flange into the housing bushing that meets the air flow first. Position the tube so that the arrows point into the air flow. Secure the tube flange to the housing bushing with two #6 self-tapping screws.
-
From inside the duct, couple the other sections of the inlet tube to the section already installed using the 1/2-inch conduit fittings supplied. Make sure that the holes onboth of the air inlet tubes are lined up and facing into the air flow.
-
Trim the end of the tube protruding through the duct so that 1 to 2″ of the tube extend outside the duct. Plug this end with the end plug and tape closed any holes in the
protruding section of the tube. Be sure to seal the duct when the tube protrudes.
NOTE: An alternate method to using the ST-10 is to use two ST-5 inlet
tubes. Remove the flange from one of the tubes and install as described above.
After the installation, use electrical tape to close off some of the sampling
holes so that there are a total of 10 to 12 holes spaced as evenly as possible
across the width of the duct.
NOTE: Air currents inside the duct may cause excessive vibration,
especially when the longer sampling tubes are used. In these cases a 3 inch
floor flange (available at most plumbing supply stores) may be used to fasten
the sampling tube to the other side of the duct. When using the
flange/connector mounting technique, drill a 1-inch to 1
1/4-inch hole where the flange will be used.
[5.4.3] Modifications of Inlet Sampling Tubes
There may be applications where duct widths are not what is specified for the
installation. In such cases, it is permissible to modify an inlet sampling
tube that is longer than
necessary to span the duct width.
Use a 0.193-inch diameter (#11) drill and add the appropriate number of holes
so that the total number of holes exposed to the air flow in the duct is 10 to
12. Space the additional holes as evenly as possible over the length of the
tube.
NOTE: This procedure should only be used as a temporary fix. It is not
intended as a permanent substitute for ordering the correct length tubes.
[5.5] Install The Filters
To install the sampling tube filters, simply push the filters into the
sampling and exhaust tube holes, as shown in Figure 6. If a metal sampling
tube is used, install the filters
over the tube ends.
Figure 6. Sampling tube filter installation: CAUTION
Filters require periodic cleaning or replacement, depending on the amount of
dust and dirt accumulated. Visually inspect the filters at least quarterly;
inspect them more often if the dust accumulation warrants it. See Section [6]
for more information. Replacement filters can be ordered from System Sensor,
3825 Ohio Ave., St. Charles, IL 60174. (Exhaust tube/intake tube filter P/N
F36-09-00)
[5.6] Field Wiring
Wiring Installation Guidelines
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction. Proper wire gauges should be used.
The conductors used to connect smoke detectors to control panels and accessory
devices should be color-coded to prevent wiring mistakes. Improper connections
can prevent a system from responding properly in the event of a fire.
For signal wiring, (the wiring between interconnected detectors or from
detectors to auxiliary devices), it is usually recommended that single
conductor wire be no smaller than 18 gauge. The duct smoke detector terminals
accommodate wire sizes up to 12 gauge. The last foot of conduit should be
flexible conduit (available in electrical supply houses), which facilitates
easier installation and puts less strain on the conduit holes in the housing.
Solid conduit connections may be used if desired.
Smoke detectors and alarm system control panels have specifications for
allowable loop resistance. Consult the control panel manufacturer’s
specifications for the total
loop resistance allowed for the particular model control panel being used
before wiring the detector loop.
Wiring Instructions
The DH100ACDC detectors are designed for easy wiring.
The housing provides a terminal strip with clamping plates. Wiring connections
are made by stripping about 3 /8-inch of insulation from the end of the wire,
sliding the bare end under the plate, and tightening the clamping plate screw.
[5.7] Perform Detector Check
- Perform STANDBY AND TROUBLE TEST per Section [6.2.1].
- Perform MAGNET TEST per Section [6.2.2.1]. The RTS451 test of Section [6.2.2.2] may substitute for this requirement.
- Perform AIR FLOW TEST per Section [6.1.1].
- Perform SMOKE RESPONSE TEST per Section [6.1.2].
- Perform SENSITIVITY TEST per Section [6.2.3].
[5.8] Install The Cover
Install the cover using the four screws that are captured in the housing
cover. Be certain filters are installed as specified in Section [5.5]. Make
sure that the cover fits into
the base groove and that all gaskets are in their proper positions. Tighten
the four screws.
Duct Smoke Detector Maintenance And Test Procedures
Test and maintain duct detectors as recommended in NFPA 72. The tests
contained in this manual were devised to assist maintenance personnel in
verification of proper
detector operation.
Before conducting these tests, notify the proper authorities that the smoke
detection system will be temporarily out of service. Disable the zone or
system under test to prevent unwanted alarms.
[6.1] Smoke Entry Tests
[6.1.1] Air Flow
To verify sufficient sampling of ducted air, use a manometer to measure the
differential pressure created from air flow across the sampling tubes. The
pressure should measure no less than 0.03 inches of water and no greater than
1.4 inches of water. The air handler must be operating for this test.
[6.1.2] Smoke Response
To determine if smoke is capable of entering the sensing chamber, visually
identify any obstructions. Plug the exhaust and inlet tube holes to prevent
ducted air from carrying
smoke away from the detector head, then blow smoke such as cigarette, cotton
wick, or punk directly at the head to cause an alarm. REMEMBER TO REMOVE THE
PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT FUNCTION PROPERLY.
[6.1.3] Filter Replacement
The filters do not substantially affect smoke performance even when up to 90%
of the filter is clogged. Quarterly visual inspection usually suffices to
determine whether the
filters should be replaced because only a high percentage of contamination
affects performance. If further testing is required, compare differential
pressure readings with and without the filters installed. If the difference
exceeds 10% replace the filters. In no case should the pressure differential
fall below 0.03 inches of water.
[6.2] Standby, Alarm, And Sensitivity Tests
[6.2.1] Standby And Trouble
Standby — Look for the presence of the flashing green LED through the
transparent housing cover. The LED should flash approximately every 10
seconds.
Trouble — If the detector LED does not flash, then the detector lacks
power (check wiring, panel, or power supply), the detector board is missing
(replace), or the unit is defective (return for repair)
Test — The trouble condition can be caused intentionally to verify
correct operation of the system. Remove the detector board to cause a trouble
condition locally and at the
system control panel.
Cover Tamper — If the cover is removed for a period longer than 20
minutes, a trouble signal is generated to indicate the cover is missing.
[6.2.2] Alarm Tests
[6.2.2.1] M02-04-00 Magnet Test
-
Place the painted surface of the magnet onto the TEST locator on the bottom of the housing (Figure 11).
-
The red alarm LED on the detector should latch on, as should any accessories (i.e. RA400Z, RTS451). Verify system control panel alarm status and control panel ex-
ecution of all intended auxiliary functions (i.e. fan shutdown, damper control, etc.). -
The detector must be reset by system control panel, front cover reset button, or remote accessory.
Figure 7. System wiring diagram for 4-wire duct smoke detectors
(detectors powered from initiating circuit):
CAUTION
Do not loop wire under terminals when wiring detectors. Break wire runs to
provide system supervision of connections. Figure 8. Wiring diagram for DH100ACDC to
APA451: NOTE: Wiring diagram shown is
for DH100ACDC 4-wire duct smoke detector system equipped without a control
panel.
Figure 9. Wiring diagram for DH100ACDC to RTS451KEY and interconnect
feature:
NOTE: Wiring diagram shown is
for DH100ACDC 4-wire duct smoke detector system equipped without a control
panel.
IMPORTANT! ALL INTERCONNECTED UNITS MUST BE POWERED BY THE SAME,
INDEPENDENT POWER SUPPLY.
Figure 10. Wiring diagrams for optional accessories (see page 6 for
APA451 wiring diagram):
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE| STANDBY| ALARM
APA451| 12.5mA Max.| 30mA Max.
PA400| 0mA| 15mA Max.
RA400Z| 0mA| 10mA Max.
RTS451/RTS451KEY| 12mA Max.| 7.5mA Max.
When a unit is powered at the 120VAC or 220/240VAC input, any combination of
accessories may be used such that the given accessory loads are:
60mA or less in the standby state, 110mA or less in the alarm state.
Figure 11. Testing detector alarm: [6.2.2.2] RTS451/RTS451KEY Remote Test Station
The RTS451/RTS451KEY Remote Test Station facilitates test of the alarm
capability of the duct smoke detector as indicated in the RTS451/RTS451KEY
manual. The DH100ACDC duct smoke detector can be reset by the
RTS451/RTS451KEY. If a system control panel is used, the panel itself may also
require testing.
To install the RTS451/RTS451KEY, connect the device as shown in Figure 9; wire
runs must be limited to 25 ohms or less per interconnecting wire.
[6.2.3] Sensitivity Tests
[6.2.3.1] MOD400 or MOD400R Test
After verification of alarm capability, use the MOD400R test module with a
voltmeter to check detector sensitivity as indicated in the test module’s
manual. The housing cover must be removed to perform this test.
If test module readings indicate that the detector head is outside of the
acceptable range that is printed on the label of the detector, the detector
chamber requires cleaning per Section [7] of this manual.
Detector Cleaning Procedures
Notify the proper authorities that the smoke detector system is undergoing
maintenance, and that the system will temporarily be out of service. Disable
the zone or system
undergoing maintenance to prevent unwanted alarms and possible dispatch of the
fire department.
[7.1] Air Filters
- Turn off power to the system.
- Remove and inspect sampling tube filters.
- If filters are heavily coated with dirt, replace them with new filters. If they are not heavily coated, use a vacuum cleaner or compressed air nozzle to remove dust, then reinstall the filters.
[7.2] Photo Detector Boards
- Remove the screen by gently grasping on each side and pulling straight off.
- Lift the photo chamber in the same fashion. Vacuum the screen and cover. Use clean, compressed air to loosen and blow out any remaining debris. Replacement screens (S08-39-01) are available.
- Vacuum photo chamber, then use clean compressed air to blow area clean.
- Replace the chamber by pressing it onto the base. Press the screen into place. It should fit tightly on the chamber.
[7.3] Ion Detector Boards
- Brush or vacuum inside area of cover. Chamber may then be blown out using clean, compressed air.
- Vacuum sensing chamber before using clean, compressed air to loosen and blow out any remaining debris.
Board Replacement
[8.1] Detector Board Replacement
- Remove the two detector board mounting screws.
- Pull gently on the board to remove it.
- To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
- Secure board with the two mounting screws.
[8.2] Power Board replacement
- Disconnect wiring from the terminal block.
- Remove the two power board mounting screws.
- Pull gently on the board to remove it.
- To replace the board, align the board mounting features, holes, and the interconnect terminals. Push the board into place.
- Secure board with the two mounting screws.
- Re-connect wiring to terminal block.
Model DH100ACDC Air Duct Smoke Detector Specifications
Temperature:
DH100ACDCP| 32° to 131° F0| F0° to 55° C
DH100ACDCI| 32° to 120° F0| F0° to 49° C
Humidity:| 10% to 93% R.H. noncondensing|
Air Velocity:| 500 to 4000 ft./min.| 2.5 to 20.3 m/sec.
Dimensions:| 14.38″ L x 5.5″ W x 2.75″ D| 37cm L x 14cm W x 7cm D
Weight:| 3.75 pounds| 1.7 kg
Electrical Specifications
Power supply voltage:| 20-29 VDC| 24 VAC 50-60-Hz| 120 VAC 50-60 Hz| 220/240
VAC 50-60 Hz
---|---|---|---|---
Input capacitance:| 270 µF max.| 270 µF max.| N/A| N/A
Reset voltage:| 3.0 VDC min.| 2.0 VAC min.| 10 VAC min.| 20 VAC min.
Reset time (with RTS451):| .03 to 0.3 sec.| .03 to 0.3 sec.| .03 to 0.3 sec.|
.03 to 0.3 sec.
Reset time (by power down):| 0.6 sec. max.| 0.6 sec. max.| 0.6 sec. max.| 0.6
sec. max.
Power up time:| 34 sec. max.| 34 sec. max.| 34 sec. max.| 34 sec. max.
Alarm response time:| 2 to 17 sec.| 2 to 17 sec.| 2 to 17 sec.| 2 to 17 sec.
Sensitivity Test:| See detector label| See detector label| See detector label|
See detector label
Power Supply Voltage| 20 – 29 VDC| 24 VAC 50 – 60 Hz| 120 VAC 50 – 60 Hz|
220/240 VAC 50 – 60 Hz
---|---|---|---|---
CURRENT REQUIREMENTS (USING NO ACCESSORIES)
Max. standby current | 15 mA | 35 mA RMS | 25 mA RMS* | 15 mA RMS* |
---|---|---|---|---|
Max. alarm current | 70 mA | 125 mA RMS | 35 mA RMS* | 25 mA RMS* |
CONTACT RATINGS
Alarm initiation contacts (SPST) | 2.0A @ 30 VDC (resistive) |
---|---|
Alarm auxiliary contacts (DPDT) | 10A @ 30 VDC |
10A @ 250 VAC
Note: Alarm auxiliary contacts must switch 100 mA minimum at 5VDC. Alarm
auxiliary contacts shall not be connected to inititaing circuits of control
panels. Use the alarm initiation contact for this purpose.
Trouble contacts (SPDT)| 2.0A @ 30 VDC (resistive)
ACCESSORY CURRENT LOADS AT 24 VDC
DEVICE| STANDBY| ALARM
APA451| 12.5mA Max.| 30mA Max.
PA400| 0mA| 15mA Max.
RA400Z| 0mA| 10mA Max.
RTS451/ RTS451KEY| 12mA| 7.5mA Max.
- NOTE: When a unit is powered at the 120VAC or 220/240VAC input, any combination of accessories may be used such that the given accessory loads are:
60 mA or less in the standby state, 110 mA or less in the alarm state.
Three-Year Limited Warranty
System Sensor warrants its enclosed air duct smoke detector to be free from
defects in materials and workmanship under normal use and service for a period
of three years from date of manufacture. System Sensor makes no other express
warranty for this air duct smoke detector. No agent, representative, dealer,
or employee of the Company has the authority to increase or alter the
obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of
any part of the air duct smoke detector which is found to be defective in
materials or workmanship under normal use and service during the three year
period commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to:
System Sensor, Repair Department, RA #__, 3825 Ohio Avenue, St.
Charles, IL 60174. Please include a note describing the malfunction and
suspected cause of failure. The Company shall not be obligated to repair or
replace units which are found to be defective because of damage, unreasonable
use, modifications, or alterations occurring after the date of manufacture. In
no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence
or fault. Some states do not allow the exclusion or limitation of incidental
or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.