SYSTEM SENSOR PDRP-1002E Agent Release System Instruction Manual
- June 9, 2024
- SYSTEM SENSOR
Table of Contents
PDRP-1002/PDRP-1002E Agent Release System
Operating Instructions
PDRP-1002E Agent Release System
NORMAL – Only the GREEN A.C. POWER LED is on. All other LED’s are off.
PANEL KEY – The key to open the panel can be found at this location.
WHEN AUDIBLE DEVICES ARE SOUNDING Discharge of extinguishing agent has
occurred if “release” LED is on.
FOR ANALARM
-
Evacuate the protected area
-
Notify the monitoring service and/or the Fire Department immediately. Tell them briefly what happened and what your current status is.
Phones: ……………… Fire Department ………………..Monitoring Service -
If the Fire Department is responding, be prepared to provide directions to arriving firefighters.
FOR TROUBLE ONLY
1. Notify the monitoring service and/or Fire department if this panel is
connected to either one, and tell them what is happening.
2. Silence audible devices by unlocking and opening the panel and pressing
the TONE SILENCE switch. The yellow SYSTEM TROUBLE LED will remain on. Contact
authorized service personnel immediately! (See Below).
WARNING
DO NOT ALLOW TROUBLE CONDITIONS TO REMAIN LOGGED IN THE SYSTEM. THE PROTECTION
THE SYSTEM OFFERS HAS BEEN COMPROMISED, OR ELIMINATED WHEN A TROUBLE CONDITION
EXISTS.
To return to normal after an alarm –
- Do not enter the protected area until safe to do so.
- Clear all initiating devices. Smoke detectors will not reset if there is still smoke in the area.
- Reset the control panel (PRESS the RESET switch)
Power failure or brownout –
If AC power drops too low or fails, the POWER ON LED will go out, the SYSTEM
TROUBLE LED will turn on, and the panel buzzer and any other audible trouble
devices will sound. Contact authorized service personel immediately. See
below.
In the event of trouble, contact the local System Sensor Service
Representative
Name: __
Company: _
Address: ___
Telephone Number: ____
Manual activation (Fire Drill or otherwise)-
Alarm Signalling Circuits can be activated by pressing the ALARM ACTIVATE
switch.
NOTE: May want to disconnect municipal box by sliding DISCONNECT switch,
located on 4XTM module, to its DOWN position.
Alarm Silencing –
Alarm Signalling Circuits may be silenced by pressing the ALARM SILENCE
switch. The ALARM SILENCED LED will turn on. Subsequent alarms will reactivate
circuits. Press the RESET switch to clear the “silenced” condition.
NOTE: ALARM SILENCE switch may be disabled by dipswitch selection (see
manual)
To test the lamps
Press and hold the RESET switch and check all the LED’s.
Every one should be on as long as the switch is held on.
For more information, refer to the PDRP-1002/PDRP-1002E manual. It is kept in
the following location:
FRAME AND POST ADJACENT TO THE PANEL
Document 51136 Revision A ECN 99-017 3/12/99 P/N 51136:A
www.PDF-Zoo.com
firealarmresources.com
Documents / Resources
|
SYSTEM SENSOR PDRP-1002E Agent Release
System
[pdf] Instruction Manual
PDRP-1002, PDRP-1002E, PDRP-1002E Agent Release System, Agent Release System,
Release System
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>