NOTIFIER NFS-640 Fire Alarm Control Panel Instruction Manual

June 9, 2024
NOTIFIER

NFS-640 Fire Alarm Control Panel

Fire Alarm Control Panel
NFS-640
Installation Manual

B2 Document 51332
07/27/2004 Rev:

P/N 51332:B2

ECN 04-320

Technical Manuals Online! – http://www.tech-man.com
firealarmresources.com

Fire Alarm System Limitations

While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!

An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72-1999 (NFPA 72-1999), manufacturer’s recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a firstfloor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
· Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
· Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
· Smoke particles may be blown away from detectors by air outlets.
· Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).

Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
· Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
· Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
· In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer’s recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72-1999 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Precau-L-1-2004.fm

2

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation Precautions

Adherence to the following will aid in problem-free installation with long- term reliability:

WARNING – Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. The control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION – System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72-1999 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0°C to 49°C (32°F to 120°F) and at a relative humidity (noncondensing) of 85% at 30°C (86°F) per NFPA, and 93% ± 2% at 32°C ± 2°C (89.6°F ± 1.1°F) per ULC. However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.

Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
Precau-L-10-2003.fm

FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense.

Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications.
Le present appareil numerique n’emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.

Acclimate PlusTM, AWACSTM, HARSHTM, NOTI·FIRE·NETTM, and VeriFireTM are trademarks, and ONYX®, FlashScan®, UniNet®, and VIEW® are registered trademarks of NOTIFIER. NIONTM is a trademark of NIS. NISTM and Notifier Integrated SystemsTM are trademarks and NOTIFIER® is a registered trademark of Fire·Lite Alarms, Inc. Echelon® is a registered trademark and LonWorksTM is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

3

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information: · Product name and version number (if applicable) · Printed manual or online Help · Topic Title (for online Help) · Page number (for printed manual) · Brief description of content you think should be improved or corrected · Your suggestion for how to correct/improve documentation
Send email messages to:
[email protected]
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

4

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Table of Contents
Section 1 About This Manual ……………………………………………………………………………………………7 1.1 Standards and Other Documents ……………………………………………………………………………….7 1.2 Supplemental Documentation …………………………………………………………………………………..8
Section 2 System Overview ………………………………………………………………………………………………11 2.1 System Description ……………………………………………………………………………………………….11 2.1.1 Standard Features ………………………………………………………………………………………..11 2.1.2 Options ………………………………………………………………………………………………………12 2.1.3 System Limitations ……………………………………………………………………………………..12 2.2 System Components ……………………………………………………………………………………………..12 2.2.1 Basic Equipment Required …………………………………………………………………………..12 2.2.2 Control Panel Circuit Board ………………………………………………………………………..13 2.2.3 Main Power Supply …………………………………………………………………………………….13 2.2.4 Circuit Board Components …………………………………………………………………………..14 2.3 System Cabinets ……………………………………………………………………………………………………16 2.4 Optional Devices …………………………………………………………………………………………………..17 2.5 Intelligent Detectors ………………………………………………………………………………………………18 2.6 Addressable Modules ……………………………………………………………………………………………19 2.7 Annunciation Modules …………………………………………………………………………………………..21 2.8 Annunciators ………………………………………………………………………………………………………..21 2.8.1 Annunciators with 24- and 48-Point Capacity …………………………………………………21 2.8.2 Annunciators with 16- and 32-Point Capacity …………………………………………………22 2.8.3 Annunciator Fixed Modules ………………………………………………………………………..22 2.9 Peripheral Displays and Printers ……………………………………………………………………………..23 2.10 Panel Circuit Modules ………………………………………………………………………………………..23 2.11 Voice Alarm System …………………………………………………………………………………………….25
Section 3 Installation ……………………………………………………………………………………………………….27 3.1 Preparing for Installation ……………………………………………………………………………………….27 3.1.1 Standards and Codes ……………………………………………………………………………………27 3.2 Installation Checklist …………………………………………………………………………………………….28 3.3 Mounting a Cabinet ………………………………………………………………………………………………29 3.4 Laying Out Equipment in Cabinet and Chassis …………………………………………………………30 3.5 Installing the Control Panel ……………………………………………………………………………………32 3.5.1 Control Panel Circuit Board & Keypad/Display Unit ………………………………………32 3.5.2 Using NCA as Primary Display …………………………………………………………………….33 3.5.3 Loop Expander Module ……………………………………………………………………………….34 3.5.4 Network Control Module ……………………………………………………………………………..35 3.5.5 Panel Circuit Modules and Other Option Boards …………………………………………….35 3.5.6 Overview ……………………………………………………………………………………………………36 3.5.7 Connecting the Control Panel to AC Power ……………………………………………………37 3.5.8 Checking AC Power ……………………………………………………………………………………37 3.5.9 Installing and Connecting the Batteries ………………………………………………………..38 3.5.10 APS-6R Auxiliary Power Supply Connections ……………………………………………..38 3.5.11 External DC Power Output Connections ………………………………………………………38 3.5.12 NAC Connections & Releasing Circuits ………………………………………………………39 3.5.13 Output Relay Connections ………………………………………………………………………….39 3.5.14 Backup-Alarm Switches ……………………………………………………………………………40 3.5.15 Installing a Transmitter Module TM-4 …………………………………………………………40 3.6 UL Power-limited Wiring Requirements ………………………………………………………………….41 3.6.1 Labeling Modules and Circuits ……………………………………………………………………..41 3.7 Installing Panel Circuit Modules …………………………………………………………………………….42 3.7.1 Overview ……………………………………………………………………………………………………42 3.7.2 Mounting Expander Boards ………………………………………………………………………….42 3.7.3 Connecting Ribbon Cables for a CAB-4 Series Backbox …………………………………43 3.7.4 Installing the Panel Circuit Modules ……………………………………………………………..43 3.7.5 Connecting ICM-4RK and ICE-4 Modules …………………………………………………….44 3.7.6 Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z) ……………………………45 3.7.7 Connecting CRM-4RK/CRE-4 Modules ………………………………………………………..46 3.8 Auxiliary Relay Module (ARM-4): Product-Specific Details ……………………………………..47

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

5

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

3.8.1 Overview ……………………………………………………………………………………………………47 3.8.2 Installation …………………………………………………………………………………………………47 3.8.3 Field Wiring an Auxiliary Relay Module ……………………………………………………….48 3.9 Installing Remote Printers and/or CRT …………………………………………………………………….48 3.9.1 Custom Cable Fabrication ……………………………………………………………………………48 3.9.2 Installing and Configuring the PRN-5 Printer …………………………………………………48 3.9.3 Installing and Configuring a Keltron Printer …………………………………………………..50 3.9.4 Installing and Configuring a CRT-2 ………………………………………………………………51 3.9.5 Connecting a PC …………………………………………………………………………………………52 3.9.6 Connecting Multiple Printers, CRTs, or CRT/PRN Combination ……………………..53 3.10 Wiring a Signaling Line Circuit (SLC) …………………………………………………………………..54
Section 4 Applications ……………………………………………………………………………………………………..55 4.1 Overview ……………………………………………………………………………………………………………..55 4.2 NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit) 56 4.3 NFPA 72-1999 Proprietary Fire Alarm Systems ……………………………………………………….57 4.4 Fire/Security Applications ……………………………………………………………………………………..58 4.4.1 General Operation ……………………………………………………………………………………….58 4.4.2 Installing a Security Tamper Switch ………………………………………………………………58 4.4.3 Receiving Unit ……………………………………………………………………………………………59 4.4.4 Programming ……………………………………………………………………………………………..59 4.4.5 Wiring for Proprietary Security Alarm Applications ………………………………………60 4.5 Releasing Applications ………………………………………………………………………………………….61 4.5.1 Overview ……………………………………………………………………………………………………61 4.5.2 Programming ……………………………………………………………………………………………..61 4.5.3 Wiring ……………………………………………………………………………………………………….62 4.5.4 Connecting a Releasing Device to the Control Panel ……………………………………….62 4.5.5 Connecting a Releasing Device to the FCM-1 Module …………………………………….63 4.5.6 Connecting an NBG-12LRA Agent Release-Abort Station …………………………….64
Section 5 Testing the System ……………………………………………………………………………………………65 5.1 Acceptance Test ……………………………………………………………………………………………………65 5.2 Periodic Testing and Service …………………………………………………………………………………..65 5.3 Operational Checks ……………………………………………………………………………………………….65 5.4 Battery Checks and Maintenance ……………………………………………………………………………66
Appendix A Power Supply Calculations ………………………………………………………………………….. 67
A.1 Calculating AC Branch Circuit Current …………………………………………………………………..67 A.2 Calculating the System Current Draws …………………………………………………………………..67
A.2.1 Calculating the Maximum Secondary Power Fire Alarm Current Draw …………….70 A.3 Calculating the Battery Requirements …………………………………………………………………….71
A.3.1 Calculating the Battery Capacity ………………………………………………………………….71 A.3.2 Calculating the Battery Size …………………………………………………………………………72
Appendix B Electrical Specifications ……………………………………………………………………………….. 73
B.1 Electrical Specifications ………………………………………………………………………………………..73 B.2 Wire Requirements ……………………………………………………………………………………………….75
Appendix C Compatible Equipment………………………………………………………………………………… 77
C.1 UL-Listed Equipment ……………………………………………………………………………………………77 C.2 US Coast Guard & Lloyd’s Register ……………………………………………………………………..79
Appendix D Canadian Applications…………………………………………………………………………………. 81
D.1 Standalone Application …………………………………………………………………………………………81 D.1.1 NFS-640 with KDM-2 ………………………………………………………………………………..81 D.1.2 NFS-640 with NCA ……………………………………………………………………………………81
D.2 Local Network Application ……………………………………………………………………………………81 D.3 Automatic Alarm Signal Silence ……………………………………………………………………………81 D.4 Annunciator Applications ……………………………………………………………………………………..81 D.5 Releasing Devices ………………………………………………………………………………………………..81
Index ……………………………………………………………………………………………………………………………… 85

6

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Section 1 About This Manual
1.1 Standards and Other Documents
This Fire Alarm Control Panel complies with the following NFPA standards:
NFPA 12 CO2 Extinguishing Systems NFPA 12A Halon 1301 Extinguishing Systems NFPA 13 Sprinkler Systems NFPA 15 Water Spray Systems NFPA 16 Foam/Water Deluge and Foam/Water Spray Systems NFPA 17 Dry Chemical Extinguishing Systems NFPA 17A Wet Chemical Extinguishing Systems NFPA 72-1999 Central Station Fire Alarm Systems (Automatic, Manual and Waterflow) Protected Premises Unit (requires Notifier UDACT). NFPA 72-1999 Local (Automatic, Manual, Waterflow and Sprinkler Supervisory) Fire Alarm Systems. NFPA 72-1999 Auxiliary (Automatic, Manual and Waterflow) Fire Alarm Systems (requires TM-4). NFPA 72-1999 Remote Station (Automatic, Manual and Waterflow) Fire Alarm Systems NFPA 72-1999 Proprietary (Automatic, Manual and Waterflow) Fire Alarm Systems (Protected Premises Unit). NFPA 2001 Clean Agent Fire Extinguishing Systems
The installer should be familiar with the following documents and standards:
NFPA 72-1999 Initiating Devices for Fire Alarm Systems NFPA 72-1999 Inspection, Testing and Maintenance for Fire Alarm Systems NFPA 72-1999 Notification Appliances for Fire Alarm Systems Underwriters Laboratories UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers – Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1971 Visual Signaling Appliances UL 1076 Proprietary Burglar Alarm Systems Underwriters Laboratories of Canada (ULC) Standard CAN/ULC-S527-M99 CAN/ULC-S524-M91 Standard for the Installation of Fire Alarm Systems Other EIA-485 and EIA-232 Serial Interface Standards NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction C22.1-98 The Canadian Electrical Code, Part 1

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

7

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

About This Manual

Supplemental Documentation

1.2 Supplemental Documentation

The table below provides a list of documents referenced in this manual, as well as documents for selected other compatible devices. The document series chart (DOC-NOT) provides the current document revision. A copy of this document is included in every shipment.

Compatible Conventional Devices (Non-addressable) Device Compatibility Document Fire Alarm Control Panel (FACP) and Main Power Supply Installation NFS-640 Installation, Operations, and Programming Manuals Voice Alarm System Manual SLC Wiring Manual Note: For individual SLC Devices, refer to the SLC Wiring Manual Off-line Programming Utility VeriFireTM Tools CD help file Cabinets & Chassis CAB-3/CAB-4 Series Cabinet Installation Document Battery/Peripherals Enclosure Installation Document Power Supplies, Auxiliary Power Supplies & Battery Chargers ACPS-2406 Installation Manual APS-6R Instruction Manual CHG-120 Battery Charger Manual FCPS-24 Field Charger/Power Supply Manual Networking Noti·Fire·Net Manual, Network Version 4.0 & Higher NCM-W/F Installation Document NCS Network Control Station Manual, Network Version 4.0 & Higher System Components Annunciator Control System Manual Annunciator Fixed Module Manual AFM-16A Annunciator Fixed Module Manual ACM-8R Annunciator Control Module Manual LCD-80 Manual LCD-80TM Manual LDM Series Lamp Driver Annunciator Manual NCA Network Control Annunciator Manual SCS Smoke Control Manual (Smoke and HVAC Control Station) DPI-232 Direct Panel Interface Manual TM-4 Installation Document (Reverse Polarity Transmitter) UDACT Manual (Universal Digital Alarm Communicator/Transmitter) ACT-2 Installation Document VEC 25/50 Manual RM-1 Series Remote Microphone Installation Document

Document Number 15378
Document Number 51332, 51334, 51333
51252 51253
Document Number VERIFIRE-TCD
Document Number 15330 50295
Document Number 51304 50702 50641 50059
Document Number 51584 51533 51658
Document Number 15842 15048 15207 15342 15037 51082 15885 51482 15712 51499 51490 50050 51118 50686 51138

Table 1 Reference Documentation (Sheet 1 of 2)

8

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Supplemental Documentation

About This Manual

RA400Z Remote LED Annunciator Installation Document RFX Wireless Interface Manual UZC-256 Universal Zone Coder Manual UZC-256 Programming Manual XP Transponder Manual XP10-M Installation Document XP5 Series Manual XP6-C Installation Document XP6-MA Installation Document XP6-R Installation Document XPIQ Audio Transponder Manual
Table 1 Reference Documentation (Sheet 2 of 2)

I56-508 51012 15216 15976 15888 I56-1803 50786 I56-1805 I56-1806 I56-1804 51013

Cautions and Warnings
This manual contains cautions and warnings to alert the reader as follows:

CAUTION: Information about procedures that could cause programming errors, runtime errors, ! or equipment damage.

WARNING: Indicates information about procedures that could cause irreversible damage to the ! control panel, irreversible loss of programming data or personal injury.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

9

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Notes

10

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Section 2 System Overview
2.1 System Description
The NFS-640(E) control panel is a modular, intelligent fire alarm control panel (FACP) with an extensive list of powerful features. The control panel integrates a central processing unit (CPU), a 6 amp power supply, and a battery charger. This is combined with a mounting chassis and cabinet to create a complete fire alarm control system. The panel supports FlashScan protocol and has network capabilities. A single SLC loop is supported with the basic equipment package; a second SLC loop can be added by attaching an optional loop expander module (LEM-320). Modular devices mount to the chassis to provide additional output circuits, including voice and telephone modules to form a complete voice evacuation system. Five cabinet options for enclosing system components are available. The control panel has the capacity for installing up to 636 addressable points; 159 detectors and 159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
· Uses Notifier’s VIEW® early warning fire detection and the FlashScan® or Classic Loop Interface Protocol (CLIP) families of detectors and modules
· Four standard Notification Appliance Circuits (NAC), Class A or B · Alarm, Trouble, Supervisory and Security relays · Support for 32 annunciator addresses, with 10 special annunciator groups · Supports Style 4, Style 6, Style 7 SLC loops · Connections to easily mount an expander board to add a second SLC loop · Releasing service using on-board NACs or FCM-1 modules · Logic Equations · Display scroll selection · Alarm verification supervisory indication (NYC) · Supervisory duct detectors · Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms · Network operation · Battery charger supports 12-55 amp hour sealed lead-acid batteries · EIA-485 connections for wiring ACS annunciators (including LDM custom graphic annunciators),
TM-4 transmitter · EIA-232 connections for printer, CRT, printer/CRT, or network operation · Autoprogram feature for faster programming of new devices · The control panel provides 6.0 amps of usable output power in an alarm condition; it provides
3.0 amps of usable output power in normal or continuous operating conditions · Diagnostic LEDs and switches · Ground fault detection · Battery and battery- charger supervision, voltage-monitoring, and current-monitoring · Panel circuit modules support up to 64 circuits · Programmable for strobe synchronization

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

11

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

System Components

2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
· QWERTY silicone-rubber keypad with a 2×40 LCD display and eight indicator LEDs
· Optional LEM-320 provides a second SLC loop that is electrically identical to the one on the main board
· Optional devices include: UDACT Universal Digital Alarm Communicator/Transmitter, ACM8R remote relay module to increase point capacity, audio and voice components, and panel circuit modules
· Optional LCD-80 connected through an EIA-485 interface allows monitoring the system–up to 6,000 feet (1829 meters) from the control panel
2.1.3 System Limitations
System expansion must take into consideration the following:
1. The physical limitations of the cabinet configuration. 2. The electrical limitations of the system power supply. 3. The capacity of the secondary power source (standby batteries).
2.2 System Components
2.2.1 Basic Equipment Required
A basic NFS-640 system requires at least the following components:
1. The control panel. CPU-640 (120V operation) or CPU-640E (240V operation). This printed circuit board is the “control panel” itself and the heart of the system. It also includes an expander cable for connecting panel modules, a grounding cable, battery interconnect cables, and document kit.
2. One or more chassis. CHS-M2 mounts the CPU-640/CPU-640E. To mount additional rows of optional equipment, order one or more chassis from this list: CHS-M2, CHS-4N (included in shipkit CHS-4MB), CHS-4L.
3. A primary display. Generally this is a KDM-2 keypad/display, a DP-DISP dress panel, and two BMP-1 blank module panels. For information on using NCA as primary display instead of KDM-2, see Section 3.5.2 “Using NCA as Primary Display” and the NCA Manual.
4. A backbox and door: SBB-A4 and DR-A4 (one row of equipment) or SBB-B4 and DR-B4 (two rows of equipment) or SBB-C4 and DR-C4 (three rows of equipment) or SBB-D4 and DR-D4 (four rows of equipment) (For a solid-metal door add “B” to the part number; for a red door add “R”.)
5. A battery dress panel BP-4
6. Batteries (Refer to Appendix A.3 “Calculating the Battery Requirements” for system currentdraw calculations; CAB-4 series backboxes holds batteries up to 24 AH maximum.)

12

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Components

System Overview

2.2.2 Control Panel Circuit Board
The control panel electronics are contained on one four-layer printed circuit board (PCB) that incorporates a 6 amp power supply with battery charger, a signaling line circuit (SLC) and the central processing unit. A keypad/display unit can be installed over the power supply as shown Figure 1.

nfs640-panel.cdr

POWER

FIRE ALARM

PRE-ALARM

SECURITY SUPERVISORY SYSTEM TROUBLE

SIGNALS SILENCED

POINT DISABLED

ACKNOWLEDGE SCROLL DISPLAY

SIGNAL SILENCE

DRILL
HOLD 2 SECONDS

SYSTEM RESET

LAMP TEST

1 !

2 @

3 =

4,

5

6

%

:

7

8

9

.

0 ?

QWE R T Y U I O P

A SD FGHJ KL

Esc

Z X C V B N M SPACE

Enter

DETECTOR

+ NEXT
SELECTION

MODULE

­ PREVIOUS
SELECTION

& OUTPUT

RECALL LAST

(

ENTRY

BATTERY LEVELS

/

INCREMENT NUMBER

)

Figure 1 NFS-640 Control Panel with Optional Keypad/Display Unit Installed

2.2.3 Main Power Supply

The main power supply is an integral part of the control panel’s circuit board. It provides a total of 3 A (6 A in alarm) and contains an integral battery charger. This can be used for many functions including:
· Powering the NFS-640
· Powering a variety of UL-listed 24 VDC notification appliances from four built-in NAC outputs
· Providing up to 1.25 A of resettable power for four-wire smoke detectors
· Providing up to 1.25 A of non-resettable power for external devices such as the TM-4 Transmitter Module.

Figure 2 Main Power Supply on Control Panel

nfs-640-panel-iso.cdr

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

13

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

System Components

2.2.4 Circuit Board Components
The following two figures illustrate the location of the various connections, switches, jumpers and LEDs on the circuit board. Figure 3 shows wiring connections. Figure 4 shows jumpers, LEDs and switches. See Section 3 “Installation” for more details.

J8 – Zone Code Input
TB7 – DC Power (24 VDC power-limited, non-resettable) TB7 – DC Power (24 VDC power-limited, resettable)

TB8 – Alarm Relay TB9 – Trouble Relay TB10 – Supervisory Relay TB11 – Security Relay

See Section 3.5.13 “Output Relay Connections” for details.

TB12 – EIA-485 Terminal Mode Connection (supervised)

TB13 – EIA-485 ACS Mode Connection (supervised)

TB14 – EIA-232 Printer Connection

TB15 – EIA-232 PC/Terminal Connection (CRT)

J1 – Network/Service Connection (NUP) (power-limited, supervised)

+ – + – NO NC C NO NC C NO NC C NO NC C

+ – + – + – TX RX REF TX RX REF

TB16 – SLC #1 Connections (Detectors, Modules) (supervised)
B+ A+ B- A-

TB6 – NAC#1 TB5 – NAC#2 TB4 – NAC#3 TB3 – NAC#4

All NAC Circuits: power-limited, supervised

J7 – Accessory Power Connection

TB2 – AC Power Connection

B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A-

nfs640-board2.cdr

BATT+ BATT- EARTH NTRL HOT

10 Amp Slo-Blow Fuse P/N 12067
TB1 – Battery Connection (over-current protected)

J4 – KDM-2 Connection

J3 – LEM-320 Connector (SLC Loop #2)
J10 – Security Tamper Switch J11 – Auxiliary Trouble Input
J5 – Panel Circuits (supervised) J6 – Panel Circuits (supervised)

Figure 3 Circuit Board Components: Wiring Connections

14

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Components

NAC LEDs
+ – + – NO NC C NO NC C NO NC C NO NC C

SW1, SW5 Relay Switches
JP13 – General Board Ground Fault Jumper

+ – + – + – TX RX REF TX RX REF

B+ A+ B- A-

System Overview
D55 – Main SLC Ground Fault LED JP7 – Charger Disable Jumper
JP6 – Ground Fault Jumper (SLC #1) JP12 – 200MA Jumper

B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ A-

nfs640-board2.cdr

Disable – Enable Switches for Backup Alarm

BATT+ BATT- EARTH NTRL HOT

System Switches – No Keyboard Operation’ SW2 – Acknowledge SW3 – Silence SW4 – Reset D54 –AC ON’ / Power LED D75 – Fire Alarm LED D76 – Pre-Alarm LED
D77 – Security LED

D72 – General Board Ground Fault LED

D67 -LEM-320 Ground Fault LED
D82 – Power-on LED (AC or battery)

D81 – Point Disabled LED D80 – Signals Silenced LED D79 – System Trouble LED D78 – Supervisory LED
Figure 4 Circuit Board Components: Jumpers, LEDs and Switches

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

15

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

System Cabinets

2.3 System Cabinets
The control panel and modules are installed in a CAB-4 series backbox. There are four different sizes available, holding from one to four rows of equipment plus batteries (up to two 25AH batteries). Backboxes are ordered separately from doors. The doors can be mounted on the left or the right side of the cabinet; reversible hinges are provided so that this choice can be made in the field. Doors open a full 180 degrees and have locks. Mounting methods include surface-mounting or semi-flush mounting on a wall between 16 inch (40.64 cm) on-center studs. A trim ring option is available for semi-flush mounting.
External measurements for each backbox are provided below; door dimensions are larger. Refer to CAB-3/CAB-4 Series Cabinet Installation Document (shipped with the cabinet) for specific mounting drawings and door dimensions.

A-size backbox (one row)

24.00 in (60.96 cm) wide 20.00 in (50.8 cm) tall 5.218 in (13.254 cm) deep Uses optional trim ring TR-A4

B-size backbox (two rows)

24.00 in (60.96 cm) wide 28.5 in (72.39 cm) tall 5.218 in (13.254 cm) deep Uses optional trim ring TR-B4

C-size backbox (three rows)

24.00 in (60.96 cm) wide 37.125 in (94.297 cm) tall 5.218 in (13.254 cm) deep Uses optional trim ring TR-C4

D-size backbox (four rows)

24.00 in (60.96 cm) wide 45.75 in (1162.05 cm) tall 5.218 in (13.254 cm) deep Uses optional trim ring TR-D4

Optional trim ring TR-A4 Opening: 24.062 in (61.118 cm) wide; 20.062 in (50.881 cm) tall. Molding width: 1.375 in (3.493 cm)
Optional trim ring TR-B4 Opening: 24.062 in (61.118 cm) wide; 28.562 in (72.548 cm) tall. Molding width: 1.375 in (3.493 cm)
Optional trim ring TR-C4 Opening: 24.062 in (61.118 cm) wide; 37.187 in (94.455 cm) tall. Molding width: 1.375 in (3.493 cm)
Optional trim ring TR-D4 Opening: 24.062 in (61.118 cm) wide; 45.812 in (114.775 cm) tall. Molding width: 1.375 in (3.493 cm)

The control panel and adjacent first-row modules mount in chassis CHS-M2, typically in the first/top row of the backbox. Additional rows of modules can be mounted in chassis CHS-4N and/or CHS-4L.
Note: If using the new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in. (9.525 mm) if a CPU is being mounted above it. See warning and instructions in Section 3.5.1 “Control Panel Circuit Board & Keypad/Display Unit”.
Some additional components available in the CAB-4 series include:

DP-DISP

An Inner Dress Panel for covering the backbox area surrounding display panels and various modules (required for Canadian installations).

Note: For use with NCA, KDM-2, and primary displays.

BMP-1

Blank Module Plate for covering an unused dress-panel position. Provides another option for mounting modules such as TM-4, NCM-W, or NCM-F.

BP-4

Battery dress panel

VP-2B or MP-1B For covering top row(s) of backbox if control panel is mounted in a lower (with DP-1B) row. MP-1B is also used to mount panel circuit modules.

Note: When using trim rings, mount backbox with at least 1 inch (2.54 cm) between wall surface and front of backbox, to allow door to open fully past the trim ring.

16

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Optional Devices

System Overview

2.4 Optional Devices
Several optional components can be installed within the NFS-640 system. This list provides only a sample of common equipment; for a complete list of what is available, refer to Appendix C “Compatible Equipment” and for a list of conventional equipment, refer to the Device Compatibility Chart.
Network Control Annunciator – NCA. Provides a text-based, 24 VDC powered, display and control device for Noti·Fire·Net. It incorporates a large LCD display and a silicone-rubber QWERTY keypad. It will display all events from a Noti·Fire·Net system.
Network Control Module – NCM-W/F. The NCM is an interface between the panel and Noti·Fire·Net. It comes in two models: wire and fiber-optic cable. Refer to the NCM-W/F Installation Document for more information and installation instructions.
Loop Expander Module – LEM-320. The LEM plugs into the control panel, expanding the board’s function to control two Signaling Line Circuits (SLCs). Each NFS-640 can have one LEM. Refer to Section 3.5 “Installing the Control Panel” for installation instructions.
Auxiliary Power Supply – APS-6R. The optional Auxiliary Power Supply is a 150W cabinetmounted power supply, designed to power devices that require filtered, non-resettable power, such as XP Transponder modules, NAC modules, and addressable Notifier appliance circuit modules. The APS-6R provides three 24 VDC output circuits (6 A total in alarm, 4 A continuous): two power-limited circuits (3 A each) and one non-power-limited circuit (6 A). Refer to the APS- 6R Instruction Manual for further information and installation instructions.
Addressable Charger/Power Supply – ACPS-2406. The optional ACPS-2406 is an addressable loop-based power supply and battery charger. This cabinet-mounted unit provides four individually addressable Notification Appliance Circuits. In addition, each circuit can provide notification appliance synchronization without an additional module. The unit charges 7 to 25 AH batteries with full supervision. The ACPS-2406 provides up to four 24 VDC (filtered) output circuits (2.5 A max each, 5.0 A total continuous, 6.0 A during a fire alarm). Refer to the ACPS2406 Instruction Manual for further information, installation instructions, and battery calculations.
Batteries and Battery Boxes. The control panel uses only sealed lead-acid batteries for standby power. Maximum battery capacity is 55 AH (ampere-hour). Minimum battery capacity depends upon your system configuration; absolute minimum is 12 AH. CAB-4 Series backboxes provide space for two 25 AH (or smaller) batteries. Use external battery boxes if your installation requires larger capacity batteries. Battery boxes mount directly below the main cabinet. Battery box model NFS-LBB holds batteries up to 55 AH. Refer to Section 4.2 “NFPA 72-1999 Central or Remote Station Fire Alarm System (Protected Premises Unit)” and Section A.3 “Calculating the Battery Requirements” for further information. See Battery/Peripherals Enclosure document for backbox measurements and installation instructions.
Universal Digital Alarm Communicator/Transmitter (UDACT). Transmits system status to UL-listed Central Station Receivers over a public switched telephone network. Mounting is in a CAB-4 Series backbox or remotely in the ABS-8R enclosure. The unit connects to the EIA-485 annunciator port and 24 VDC (nominal) power. Refer to the UDACT Instruction Manual for further information and installation instructions.
Transmitter Module – TM-4. The TM-4 includes three reverse polarity outputs and a Fire Municipal Box Trip in a single module. It provides a means for the FACP to control Alarm, Trouble, and Supervisory reverse polarity outputs (15mA, 24 VDC nominal) or a Fire Municipal Box Trip output. All output circuits are supervised. The Transmitter Module communicates over the standard EIA-485 connection like an ACS device and mounts easily in standard module locations within the cabinet or external boxes. Refer to the Transmitter Module TM-4 installation document for further information and installation instructions.
Universal Zone Coder – UZC-256. A circuit board, used for NAC coding applications, that provides three NAC output circuits and up to 256 zone codes. Refer to the UZC-256 Universal

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

17

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

Intelligent Detectors

Zone Coder and UZC-256 Programming manuals for further information and installation instructions.
Field Charger/Power Supply – FCPS-24. A compact, cost-effective remote power supply and battery charger. It consists of a filtered, 24 VDC output that can drive up to four Notification Appliance Circuits (NACs). Refer to the FCPS-24 Field Charger/Power Supply manual for further information and installation instructions.
Battery Charger – CHG-120. Designed to charge lead-acid batteries that provide emergency standby power for a Fire Alarm Control Panel. Provides two (2) output circuits for connection to multiple loads. Can be mounted into the CAB-4 Series backbox or the NFS-LBB Battery Box. Refer to the CHG-120 Battery Charger manual for further information and installation instructions.
Liquid Crystal Display – LCD-80. An alphanumeric display module that is an ancillary device which has two basic modes of operation. In Terminal Mode it acts as a display interface and in ACS Mode as an alphanumeric annunciator. The LCD-80TM is also available and provides Terminal Mode only. Refer to the LCD-80 or LCD-80TM Liquid Crystal Display manuals for further information and installation instructions.
SCS-8 Series Smoke Control System. The Smoke Control Station (SCS-8) module uses eight groups of four annunciator points for fan shutdown control or other heating, ventilation or air conditioning functions. The Smoke Control Expander (SCE-8) is used to expand the SCS-8 by an additional eight groups of four annunciator points. Only one expander can be used per SCS-8. The Smoke Control Lamp Driver Station (SCS-8L) module uses eight groups of four annunciator points for fan shutdown control or other heating, ventilation or air conditioning functions. Must be mounted in custom graphic annunciator panel. The Smoke Control Expander (SCE-8L) is used to expand the SCS-8L by an additional eight groups of four annunciator points. Only one expander can be used per SCS-8L. Must be mounted in custom graphic annunciator panel. For more details on the SCS Smoke Control System, refer to the SCS Manual.
2.5 Intelligent Detectors
Introduction
Intelligent, addressable detectors provide analog information to the control panel on a Signaling Line Circuit (SLC). This allows the control panel to continually process this information to determine the status (alarm, trouble, maintenance, or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary switches. Each SLC loop can support up to 159 detectors. The sensitivity of each intelligent detector can be programmed (refer to Appendix C in the NFS-640 Programming Manual for details).
Note: A blinking LED on an intelligent detector indicates communication between the detector and the control panel.
Detectors
The FlashScan® algorithm provides high-speed communication between analog intelligent devices, by polling in groups unless new information is reported. If one of the devices within the group has new information, the control panel stops the group poll and concentrates on single points. CLIP (Classic Loop Interface Protocol) is standard polling of each intelligent devices.
FAPT-851 (Acclimate PlusTM). Intelligent detector that combines a photoelectric sensing chamber and fixed temperature heat detection (135°F/57.2°C). FlashScan capable.
FSI-851. Addressable, intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protection. FlashScan capable.
FSP-851. Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber. Listed for use in ducts. Designed to provide open area protection. FlashScan capable. The FSP-851T adds thermal sensors that will alarm at a fixed temperature of 135° F.

18

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Addressable Modules

System Overview

FST-851. Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection with 50 foot spacing capability. A fixed temperature sensor with 135°F fixed temperature alarm. FlashScan capable. The FST-851R incorporates a thermal rate of rise of 15°F (9.4°C). FlashScan capable. The FST-851H is a high temperature sensor with 190°F fixed temperature alarm.
FSI-751. Analog, addressable, low profile intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protection.
FSP-751. Same as FSI-751, but uses a photoelectric sensing chamber. The FSP- 751T adds thermal sensors that will alarm at a fixed temperature of 135°F (57°C). Designed to provide open area protection.
FST-751. Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection with 50 foot (15.24 m) spacing capability. The FST-751R incorporates a thermal rate of rise of 15°F (9.4°C).
FSD-751P. Photoelectric Duct Detector. The FSD-751RP includes an alarm relay. The FSD751PL and FSD-751RPL are low-flow detectors.
HPX-751 (HARSHTM). A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical. CLIP mode only.
FSH-751 (HARSHTM). A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical. FlashScan capable.
IPX-751. A microprocessor-based intelligent smoke detector that uses a combination of photoelectric, ionization, and thermal sensing technologies. CLIP mode only.
FAPT-751. Acclimate PlusTM is a Combination Photoelectric/Heat Detector. This intelligent, addressable, multi-sensing, low-profile detector can automatically adjust its sensitivity. It uses a combination of photoelectric and thermal sensing technologies that are designed to increase immunity to false alarms.
LPX-751. Early detection laser detector, similar to the FSL-751 VIEW®, but limited to CLIP mode operation only.
FSL-751 VIEW® Low Profile Laser Detector. An advanced intelligent photoelectric detector that uses a laser diode, special optics, and signal processing to obtain extremely high sensitivity. FlashScan capable.
Bases
Several bases, to which the detectors are affixed, are available:
B710LP. Standard U.S. Low-Profile base
B501. Standard European flangeless base
B501BH, B501BHT. Sounder base, includes B501 Sounder base with temporal sounder
B224RB. Low Profile Intelligent relay base
B224BI. Low Profile Intelligent isolator base
B710HD. HARSHTM base.
Accessories
RA400Z. A Remote Single LED Annunciator that can be wired directly off of an addressable detector for annunciation of that detector’s alarm status.
2.6 Addressable Modules
Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

19

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

Addressable Modules

with built-in rotary switches with the ability to select up to 159 addresses. An LED will blink on a monitor module to indicate communication between the module and the control panel.
Note: For a list of approved notification and initiating devices, refer to the Device Compatibility Document.
Monitor Modules – FMM-1, FZM-1 & FDM-1. Addressable monitor modules for monitoring conventional initiating devices. The FMM-1 is used for normally open contact alarm initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors, waterflow, and supervisory devices. Use the FZM-1 for interface to two-wire smoke detectors in addition to normally open contacts. The FDM-1 provides two independent 2-wire Initiating Device Circuits (IDCs) at two separate, consecutive addresses. Wire supervised IDCs as NFPA Style B (Class B) or Style D (Class A) circuits. The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
Monitor Module – FMM-101. An addressable module that is functionally similar to the FMM-1 Monitor Module–but offered in a smaller package for mounting directly in the electrical box of the device being monitored. (Class B input circuit only.)
Control Module, NAC – FCM-1. Addressable Control Module used as Notification Appliance Circuits (NACs) to power and supervise compatible, UL-listed notification appliances. Wired supervised NACs as NFPA Style Y (Class B) or Style Z (Class A). The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
Control Module, Relay – FRM-1. Similar to the FCM-1 except used as a Form-C control relay module.
Fault Isolator Module – ISO-X. This module is not addressable, but listed here due to its use in an SLC. Protects the system against wire-to-wire short circuits on the SLC. It should be placed between groups of sensors in a Style 6 or Style 7 SLC to isolate short- and open-circuit problems and protect the rest of the loop so it can continue to operate normally.
Pull Station – NBG-12LX. An addressable manual pull station with key-lock reset feature. The addressable module is housed within the pull station.
Transponder – XP5-M. Supervises five Class-B addressable Initiating Device Circuits each with a maximum loop resistance of 1,200 ohms. These circuits monitor normally open contact initiating devises (manual pull stations, heat detectors, four-wire smoke detectors, security contacts, etc.). One XP5-M occupies five consecutive addresses on the signaling line circuit (SLC). Each circuit has one red LED status indicator that blinks when it is not active, and produces a steady glow when active. For more information see the XP5 Series Transponder Manual.
Transponder – XP5-C. Each of the five circuits of the XP5-C can act as a notification appliance/speaker/telephone circuit (Class B only) or a Form-C relay. A push-button switch changes the circuit to a Form-C relay. One XP5-C occupies five consecutive addresses on the SLC. Each circuit has one green LED status indicator that blinks when it is not active, and produces a steady glow when active. For more information see the XP5 Series Transponder Manual.
Quad Intelligent Audio Transponder – XPIQ. The XPIQ is an integrated audio amplification and distribution subsystem that can direct up to four low-level audio signals through four audio amplifiers to integrated, continuously supervised speaker circuits. An on-board power supply charges and supervises battery backup.
Multi-Input/Output Modules – XP6-C, XP6-R, XP10-M, XP6-MA. FlashScan capable multiinput/output modules are available for use on the SLC loop. All are FlashScan capable.
· XP6-C controls six NAC or speaker/telephone circuits. Applications are equivalent to those for XP5-C set as a notification appliance/speaker/telephone circuit.
· XP6-R controls six Form-C relays. Applications are equivalent to those for XP5-C set as a Form-C relay.
· XP10-M supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices. Applications are equivalent to those for XP5-M.

20

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Annunciation Modules

System Overview

· XP6-MA enables an intelligent alarm system to monitor six zones of conventional two-wire detectors.
For installation instructions, refer to the documentation provided with the modules.
2.7 Annunciation Modules
Introduction
This section contains brief descriptions and model numbers of annunciator modules that can be connected to the control panel. Communication between the control panel and annunciators takes place over a two-wire serial interface connected to the control panel’s EIA-485 ACS Mode connection. Section 2.8 “Annunciators” contains more detailed information.
Description
Below are descriptions of the Annunciator Modules and Expander Modules used with the control panel.
Annunciator Control Module – ACM-8R. Provides the control panel with a mappable relay control module. Relays can be selected for mapping anywhere in the system memory (in groups of eight). Provides eight Form-C relays with 5 A @ 125 VAC (resistive) or 5 A @ 30 VDC (resistive) or 2 A @ 125 VAC (inductive) contacts. Tracks any group of eight zones within the system.
Refer to ACM-8R Annunciator Control Module manual for more information.
Lamp Driver Annunciator Module – LDM-32. Provides 32 alarm lamp driver outputs for connection to a custom graphic annunciator. DIP switch selectable for 32 alarm outputs or 16 alarm/16 trouble outputs, and 16 switch inputs for control of system control functions as Signal Silence and System Reset.
Refer to the LDM Series Lamp Driver Annunciator Modules manual for more information.
Lamp Driver Annunciator Expander Module – LDM-E32. Expands the LDM-32 by 32 system points, to a maximum of 64 points.
Lamp Driver Relay Expander Module – LDM-R32. Provides the LDM-32 or LDM-E32 with 32 dry Form-A (normally open) contacts.
2.8 Annunciators
The Annunciator Control System provides the control panel with 32 remote annunciators. The number of points a particular annunciator can support is reflected in the part number. For example, an ACM-24AT has 24 points and an ACM-48A has 48 points. The number of points on an Annunciator Expander Module must match the number of points on the Annunciator Control Module it is expanding. One Annunciator Fixed Module can also be used per system. Connections are through an EIA-485 ACS Mode connection on the Control Panel.
Note: The NFS-640 can only support 64 points per annunciator address regardless of the model used.
Brief descriptions follow of specific modules used with the control panel. For detailed information, refer to the specified product manual.
2.8.1 Annunciators with 24- and 48-Point Capacity
For specific installation information, refer to the Annunciator Control Module manual. For Canadian requirements, see Appendix D “Canadian Applications”.
Annunciator Control Module – ACM-24AT. A one-channel Class-B unit with 24 switch controlled annunciator points. Each point is controlled by a silicone- rubber switch with indicator LED. Multi-color LEDs can be programmed to produce one of three colors: red, green or yellow.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

21

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

Annunciators

Annunciator Expander Module – AEM-24AT. An expander board for the ACM-24AT that provides an additional 24 points and is identical in size and appearance. Up to three expanders can be used with an ACM-24AT.
Note: An AEM-24AT cannot be used to expand an ACM-48A.
Annunciator Control Module – ACM-48A. A one-channel Class- B unit with 48 annunciator points for indicating current system status. Each annunciator point has a red LED for alarm, and a green LED for normal; each module has a yellow unit-trouble LED at the top.
Annunciator Expander Module – AEM-48A. An expander board for the ACM-48A that provides an additional 48 points and is identical in size and appearance. One expander can be used with an ACM-48A.
Note: An AEM-48A cannot be used to expand an ACM-24AT.
2.8.2 Annunciators with 16- and 32-Point Capacity
Models with several other LED color combinations are available for use in areas with specific color requirements. Refer to the Annunciator Control System manual for detailed information. For Canadian requirements, see Appendix D “Canadian Applications”.
Annunciator Control Module – ACM-16AT. Provides features for audible and visual indication of alarm and trouble conditions at each annunciator point. They include:16 red alarm LEDs, 16 yellow trouble LEDs, 16 momentary touch-pad switches for controlling each point, System trouble LED, Online/Power LED, Local sounder, Silence/Acknowledge switch, and Remote functions.
Annunciator Expander Module – AEM-16AT. Expands the ACM-by 16 system points and is identical in size and appearance. Three expander modules are supported by one control module providing a maximum of 64 system points.
Note: An AEM-16AT cannot be used to expand an ACM-32A.
Annunciator Control Module – ACM-32A. Provides features for audible and visual indication of alarm and trouble conditions at each annunciator point. They include: 32 red alarm LEDs, System trouble LED, Online/Power LED, Local sounder, and Silence/Acknowledge switch.
Annunciator Expander Module – AEM-32A. Expands the ACM-32A by 32 system points and is identical in size and appearance. One expander module is supported by the control module providing a maximum of 64 system points.
Note: An AEM-32A cannot be used to expand an ACM-16AT.
2.8.3 Annunciator Fixed Modules
Introduction
Provide the control panel with discrete display and control points. Fixed modules turn their LEDs on and off as directed by the control panel, and also report switch activations to the control panel for action. You can only use one fixed module in a system. Each annunciator’s address is fixed at address

  1. Refer to the Annunciator Fixed Module manual for further information.
    Description
    Annunciator Fixed Module – AFM-16AT. Contains 16 red alarm and 16 yellow trouble LEDs, a system trouble LED, an Online/Power LED, and a local sounder, and switches for control panel Acknowledge, Alarm Silence, and System Reset. Use the AFM-16AT for systems that require 16 or fewer annunciation points.

22

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Peripheral Displays and Printers

System Overview

Annunciator Fixed Module – AFM-32A. Contains 32 red alarm LEDs, a system trouble LED, an ON LINE/POWER LED, and a local panel sounder with a silence/acknowledge switch. The AFM-32A is fixed at address 1, and will not accept expander modules.
2.9 Peripheral Displays and Printers
The control panel is compatible with the following printers and display devices:
· PRN-5 Printer
· Keltron Remote Printer VS4095
· CRT-2 Display Terminal
All EIA-232 devices must be located in the same room within 50 feet (15.24 m) of the control panel.
Printer – PRN-5. The PRN-5 is an optional printer that connects directly to the control panel through an EIA-232 interface (TB14) and can be located up to 50 feet (15.24 m) from the control panel. It creates a printed record (80 columns of data on standard 9″ x 11″ tractor-feed paper) of all system events (alarm, trouble) and status changes within the system. The printout is time- stamped with the current time-of-day and date.
Keltron Remote Printer. The VS4095 is a two-color (red/black), 40-column, 24 VDC printer that can print 50 messages in 90 seconds. This printer connects to the control panel through an EIA232 interface (TB14) and mounts in a separate cabinet next to the control panel. The VS4095 meets UL fire and security requirements for an ancillary device.
For more information, contact the manufacturer (Keltron Corp., Waltham, MA)
Display Terminal – CRT-2. This optional display terminal connects to the control panel through an EIA-232 interface (TB15). The terminal can control and view events, points and history reports, control the system (Acknowledge, Alarm Silence, and System Reset). The terminal displays 26 lines by 80 columns and can be located up to 50 feet (15.24 m) from the control panel within the same room.
Note: The CRT cannot be connected at the same time as the network.
2.10 Panel Circuit Modules
Introduction
The control panel supports the following modules to control external circuits and relays:
· Indicating Circuit Module (ICM-4RK) & Indicating Circuit Expander (ICE-4)
· Control Relay Module (CRM-4RK) & Control Relay Expander (CRE-4)
· Auxiliary Relay Module (ARM-4)
· Voice Control Module (VCM-4RK), Dual Channel Module (DCM-4RK) & Voice Control Expander (VCE-4)
Up to eight of these modules (in any combination) can be controlled by the panel. Below are brief descriptions of the modules; for a description of VCM- 4RK and DCM-4RK, see Section 2.11 “Voice Alarm System”.
Indicating Circuit Module – ICM-4RK
Provides four (4) NACs for Style Y (Class B) or Style Z (Class A) operation. Circuits are fieldprogrammable to respond to a single initiating zone, a group of zones, or all initiating zones. Maximum signaling current is 3 A per circuit or 6 A per module, limited by the power supply. An Auxiliary Power Harness (P/N 71091) is provided. Note: ICM-4RK is not listed for use with NFS-640 in releasing applications.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

23

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

Panel Circuit Modules

Indicating Circuit Expander – ICE-4
An attaching circuit board that expands the ICM-4RK to a total of eight Style Y (Class B) or Style Z (Class A) NAC’s. Maximum signaling current is 3 A per circuit or 6 A per module, limited by the power supply. An Auxiliary Power Harness (P/N 71091) is provided.
Control Relay Module – CRM-4RK
Provides four (4) standard dry Form-C relay contacts. Each relay is field- programmable to respond to a single initiating device circuit, a group of circuits, or all initiating device circuits. Each relay features manual On/Off control switches and can be disabled or enabled. Contacts rated for 5 A at 120 VAC or 28 VDC (resistive). Note: CRM-4RK is not listed for use with NFS-640 in releasing applications.
Control Relay Expander – CRE-4
An attaching circuit board that expands the capacity of the Control Relay Module (CRM-4RK) to eight (8) Form-C alarm relays. May also be used to expand the ICM-4RK to provide four (4) FormC control relays. Contacts rated for 5 A at 120 VAC or 28 VDC (resistive).
Auxiliary Relay Module ARM-4
Provides four (4) auxiliary Form-C relays that can be controlled by a CRM-4RK or CRE-4 relay module. Normally-open contacts rated for 20 A and the normally- closed contacts are rated for 10 A at 125 VAC and 30 VDC (resistive). An Auxiliary Power Harness (P/N 71092) is provided.

24

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Voice Alarm System

System Overview

2.11 Voice Alarm System
Introduction
Voice Alarm equipment provides a manual or automatic supervised paging system for transmitting voice messages (information, instructions, directions) on a selective or all call basis. For more information and installation instructions refer to the Voice Alarm System manual.
Configuration
VCC-1B Voice Control Center. Basic equipment package for single-channel audio evacuation system that includes: AMG-1 Audio Message Generator (with microphone), CHS-4L Chassis, DPSW-1B Single-well Dress Panel, and Cable assemblies required to connect to control panel.
VTCC-1B Voice/Telephone Control Center. Basic equipment package for single- channel audio evacuation system employing a Fire Fighter’s Telephone system that includes: FFT-7 Fire Fighter’s Telephone, AMG-1 Audio Message Generator (with microphone), CHS-4L Chassis, DPDW-1B Double-well Dress Panel, and Cable assemblies required to connect to control panel.
TCC-1B Telephone Control Center. Basic equipment package for a Fire Fighter’s Telephone system with no voice evacuation or paging capabilities that includes: FFT-7 Fire Fighter’s Telephone, CHS-4L Chassis, TBP-1B Blank Panels (2), DPDW-1B Double-well Dress Panel, and Cable assemblies required to connect to control panel.
Descriptions
Audio Message Generator (AMG-1 & AMG-E). Provides a variety of tones and a built-in microphone allows for paging through speaker circuits. Optionally, you can install up to four digitally-recorded voice messages into the AMG-1: two factory prerecorded voice messages, two user-defined messages. You can create both user-defined messages through the AMG-1 built-in microphone, or download messages from a standard audio cassette recorder. The AMG-E is an AMG-1 without a microphone. It is used for applications that require multiple Audio Message Generators.
Fire Fighters Telephone (FFT-7 and FFT-7S). Provides the Voice Alarm System with fire fighter’s telephone capability. With these units, up to seven telephones can be used to hold a simultaneous conversation. The FFT-7S does not provide paging capability.
Voice Control Module (VCM-4RK). Provides the system with up to four (4) Style Y (Class B) or Style Z (Class A) speaker circuits, or up to four Style Y (Class B) telephone circuits. Moving a jumper on the module configures it for driving FFT-7 circuits. When configured for telephone circuits, the VCM-4RK accepts its signal directly from a Fire Fighters Telephone. Add an optional Voice Control Expander (VCE-4) to the back of the module to provide four additional telephone or speaker circuits.
Dual Channel Module (DCM-4RK). Provides the system with the capability to select one of two types of audio sources for switching to a specified speaker circuit. The module provides up to four circuits.
Audio Amplifiers. The control panel uses three types of audio amplifiers with an installed Voice Alarm System:
· AA-30 ­ Provides up to 30 watts of audio power for driving 25 Vrms speaker circuits.
· AA-100 ­ Provides 100 watts of audio power for driving 25 Vrms and 70.7 Vrms speaker circuits.
· AA-120 ­ Provides 120 watts of audio power for driving 25 Vrms speakers.
Each AA amplifies the audio signal coming in from an Audio Message Generator (AMG-1 or AMG-E).

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

25

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

System Overview

Voice Alarm System

Audio Coupling Transformer ACT-1. Couples low-level audio to audio amplifiers or other audio inputs, such as the AMG-1 Audio Message Generator. Provides Common Mode Noise Rejection (CMNR), greatly reducing crosstalk from the SLCs. For more information and installation instructions refer to the Voice Alarm System manual.
Audio Coupling Transformer ACT-2. When used with an AMG-1/-E, RM-1 and AA-30 this unit provides a means to drive thousands of amplifiers in large audio system applications. The ACT-2 provides electrical isolation between its input & output and attenuates the signal from highlevel audio to low-level audio. For more information and installation instructions refer to the ACT-2 Product Installation Drawing.
Additional Devices
The following devices are not part of the Voice Control System, but are listed here for continuity.
Remote Microphone (RM-1 and RM-1SA). Provides paging capabilities to speaker systems driven by the low level audio source of the AMG-1. The RM-1 assembly can be installed in a CAB-4 Series backbox, while the RM-1SA is installed in a CAB-RM cabinet. For more information and installation instructions see the RM-1 Series Remote Microphone installation document.
Quad Intelligent Audio Transponder – XPIQ. See product description on Page 20.

26

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Section 3 Installation
3.1 Preparing for Installation
Choose a location for the fire alarm system that is clean, dry, and vibration- free with moderate temperature. The area should be readily accessible with sufficient room to easily install and maintain it. There should be sufficient space for cabinet door(s) to open completely. Carefully unpack the system and inspect for shipping damage. Count the number of conductors needed for all devices and find the appropriate knockouts. (Refer to Section 3.6 “UL Power- limited Wiring Requirements” for selection guidelines.) Before installing the fire alarm system, read the following:
· Review the installation precautions at the front of this manual, including temperature and humidity limits for the system (Page 3).
· All wiring must comply with the National and Local codes for fire alarm systems. · Do not draw wiring into the bottom 9 inches (22.86 cm) of the cabinet except when using a
separate battery cabinet; this space is for internal battery installation.
· Review installation instructions in Section 3.2 “Installation Checklist”.
CAUTION: Make sure to install system components in the sequence listed below. Failure to do so ! can damage the control panel and other system components.
WARNING: This system contains static-sensitive components. Always ground yourself with a ! proper wrist strap before handling any circuits. Use static- suppressive packaging to protect
electronic assemblies removed from the unit.
3.1.1 Standards and Codes
In addition, installers should be familiar with the following standards and codes: · NEC Article 300 Wiring Methods. · NEC Article 760 Fire Protective Signaling Systems. · Applicable Local and State Building Codes. · Requirements of the Local Authority Having Jurisdiction. · C22.1-98 The Canadian Electrical Code, Part 1. · CAN/ULC-S5524-01 Standard for the Installation of Fire Alarm Systems.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

27

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installation Checklist

3.2 Installation Checklist
Table 2 provides an installation checklist for installing, wiring, and testing the NFS-640 system. It has references to installation information included in manuals listed in Section 1.2 “Supplemental Documentation”.

Seq Task

Refer to

Mount the cabinet backbox to the wall.

Section 3.3 “Mounting a Cabinet”

Install all required chassis in cabinet.

Section 3.5 “Installing the Control Panel”

Install control panel onto chassis.

Section 3.5.1 “Control Panel Circuit Board & Keypad/Display Unit”

Optional: Install auxiliary power supply and/or

external battery charger

Auxiliary power manuals

Calculate the proper battery rating.

Appendix A “Power Supply Calculations”

Connect AC wiring, place batteries into backbox

Section 13 “Mounting Single-space Blank Plate with

without connecting them, and run cable to optional Optional Module Connecting the Power Cables”

power supplies, DC power outputs, NACs, and

relays.

CAUTION: Do not apply AC or DC power at this

time.

Set switches for backup alarm (SW6-SW9).

Section 3.5.14 “Backup-Alarm Switches”

Optional: Install and wire Auxiliary Relay Module

(ARM-4).

Section 3.8 “Auxiliary Relay Module (ARM-4): ProductSpecific Details”

Optional: Install Panel Circuit Modules (ICM-4RK,

Section 3.7 “Installing Panel Circuit Modules”, and

CRM-4RK, VCM-4RK, DCM-4RK) and Voice Alarm Voice Alarm System Manual

System components (AMG-1, FFT-7, Audio

Amplifiers)

10. Optional: Install output devices such as a printer, or Section 3.9 “Installing Remote Printers and/or CRT” CRT terminal.

11. Optional: Install NCA or NCS.

NCA Manual or NCS Manual

12. Secure any unused mounting holes in control panel Figure 8 circuit board.

13. Wire the Signaling Line Circuits.

Section 3.10 “Wiring a Signaling Line Circuit (SLC)”

14. Connect wire shielding as instructed.

SLC Wiring Manual

15. Apply AC power to the control panel by placing the external circuit breaker to the ON position. Do NOT connect batteries.

16. Check AC power.

Table 4 in Section 13 “Mounting Single-space Blank Plate with Optional Module Connecting the Power Cables”

17. Connect the batteries using interconnect cable, P/N 75560 and 75561.

18. Install the CAB-4 series door.

CAB-3/CAB-4 Series Cabinet Installation Document

19. Program the control panel.

NFS-640 Programming Manual.

20. Field test the system.

Section 5 “Testing the System”

Table 2 Installation Checklist

28

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Mounting a Cabinet

Installation

3.3 Mounting a Cabinet
This section provides instructions for mounting an CAB-4 Series backbox to a wall. Follow these guidelines when mounting the backbox:
· Locate the backbox so that the top edge is 66 inches (1.6764 m) above the surface of the finished floor.
· Allow sufficient clearance around cabinet for door to swing freely. (See Section 2.3 “System Cabinets”.)
· Use the four holes in the back surface of the backbox to provide secure mounting. (See Figure 5.)
· Mount the backbox on a surface that is in a clean, dry, vibration-free area.
CAUTION: Unless you are familiar with the placement of components within this backbox, only ! use the knockout locations provided for conduit entry.
Follow the instructions below.
1. Mark and pre-drill holes for the top two keyhole mounting bolts (0.25 inch, 0.635 cm). Use mounting hardware appropriate for the mounting surfaces; see UL 2017 Pull-Test Requirements.
2. Select and punch open the appropriate knock-outs. (For selection guidelines, see Section 3.6 “UL Power-limited Wiring Requirements”.)
3. Using the keyholes, mount the backbox over the two screws.
4. Mark the location for the two lower holes, remove the backbox and drill the mounting holes.
5. Mount the backbox over the top two screws, then install the remaining fasteners. Tighten all fasteners securely.
6. Feed wires through appropriate knockouts.
7. Install control panel and other components according to Section 3.5 “Installing the Control Panel” before installing hinges and door according to CAB-3/CAB-4 Series Cabinet Installation Document.

CAB-4 Series Backbox, A-size (onerow)

Keyholes 2 places
Mounting holes 2 places

CAB-4 Series Backbox, D-size (four-row)

nfs640cabinetmountingholes.cdr

Figure 5 Mounting Holes of a Backbox

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

29

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Laying Out Equipment in Cabinet and Chassis

3.4 Laying Out Equipment in Cabinet and Chassis
The NFS-640 allows for flexible system design. Follow these guidelines when deciding where to locate equipment in the backbox.
The first row of equipment mounts in chassis CHS-M2. Mount second, third, or fourth rows of equipment in chassis CHS-4N (panel circuit modules, see Section 3.7 “Installing Panel Circuit Modules”), or in chassis CHS-4L (voice components, see the Voice Alarm System Manual). Some equipment, such as the NCA and annunciators, may be door-mounted; refer to the equipment’s documentation for instructions.
There are four basic positions available on a chassis (side-by-side); the number of modules that can be mounted in each position depends on the chassis model and the module size.
The CHS-M2 accepts four layers of equipment, including the control panel. The control panel fills three positions in the first-installed layer, its integral power supply occupies two positions in the next two layers, and the optional display occupies the two left-most slots in the fourth layer (flush with the door). Panel circuit modules and other modules of the same sizing can be mounted in several layers, depending on the desired configuration; see Table 3 to determine hardware. Some equipment, such as the NCA, may be door-mounted directly in front of the control panel. The BMP-1 Blank Module Plate covers unused positions in a dress-panel, providing another mounting location for some modules, such as TM-4 (see BMP-1 Product Installation Drawing for details).

Mounting location for LEM-320
Typical mounting location for NCM-W/F or TM-4

nfs640-chs-m2-11-03.wmf

KDM-2

Panel circuit module mounted on flanges above control panel

Available mounting slots for panel circuit modules, TM-4, and NCM-W/F.

Figure 6 Equipment Mounting Locations (First-Row Chassis CHS-M2)
Note: When designing the cabinet layout, consider separation of power-limited and non-powerlimited wiring as discussed in Section 3.6 “UL Power-limited Wiring Requirements”.

30

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Laying Out Equipment in Cabinet and Chassis

Installation

From…

To…

Required Stand-off or Hardware

Chassis CHS-M2
Control panel or Option board, 1st layer Option board, 2nd layer

Control panel or module on first layer
Option board, 2nd layer (includes LEM-320)
Option board, 3rd layer

Chassis Chassis Control panel

Option board, 4th layer (flush with door)
Panel circuit module (flush with door)
KDM-2 (upper edge)

Chassis rail
Dress panel DP-DISP or ADP-4B Dress panel DP-DISP or ADP-4B

KDM-2 (lower edge) NCA Option board

Not applicable; integral to the chassis.
4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
4 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Attaches directly to flanges on chassis. (Screws provided with option boards & panel circuit modules)
Attaches directly to flanges on chassis. (Screws provided with option boards & panel circuit modules)
2 stacks of male-female stand-offs: ·P/N 42185 (2.0 inch, 50.8 mm) and ·P/N 42186 (1.312 inch, 33.33 mm)
2 male-female stand-offs of length 0.937 inch (23.8 mm) P/N 42166.
Attaches directly to dress panel. (Nuts provided with NCA.)
BMP-1 attaches to dress panel; option module attaches to BMP-1 (screws provided with option module).

Table 3 Stand-off Lengths

Note: The initial release of chassis CHS-M2 used L-brackets and stand-offs of different lengths than the current model; refer to Doc. 51332, Rev A.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

31

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing the Control Panel

3.5 Installing the Control Panel
3.5.1 Control Panel Circuit Board & Keypad/Display Unit
The control panel mounts in chassis CHS-M2, which is usually positioned in the top row of the backbox. The control panel’s CPU occupies three positions at the back of the chassis; the KDM-2 occupies two positions flush with the door. The NCA may be door-mounted directly in front of the control panel if no KDM-2 is being used; see the NCA Manual for details and restrictions.
Note: For initial release of NFS-640, mounting instructions were different. Refer to the installation manual shipped with the panel (Rev A).
1. Verify height of the mounting stud in the backbox. In older backboxes, the stud must be shortened to prevent damage to the CPU-640. All electronics must be removed from the backbox before shortening. See instructions in the warning below.
WARNING: For retrofit applications, verify the height of the backbox’s mounting stud on left side ! under CPU, as shown in Figure 7 below. Stud height must not exceed 0.375 in. (9.525 mm). Early
versions of the CAB-4 Series backboxes and all CAB-3 Series backboxes have studs that require shortening. Failure to shorten this 0.625 in. (15.875 mm) mounting stud will cause damage to the control panel’s CPU. Remove electronics from backbox, permanently mount empty CHS-M2 chassis to backbox, apply nut to mounting stud to protect threading, then cut stud to proper length. Reinstall electronics as discussed in the steps below. WARNING: Do not cut without washers and nuts in place to protect threading. ! Wear protective eye covering.

If using a new CHS-M2 in a CAB-3 series backbox or in a CAB-4 series backbox manufactured before October 2002, verify stud height and cut any stud that exceeds 0.375 in. (9.525 mm) as per Step 1 above if a CPU is being mounted above it. Reinstall electronics as discussed in the steps below.

CHS-M2-11-03-CAB-3.wmf

Figure 7 Using the Redesigned CHS-M2 with Older Backboxes
2. Screw chassis to the backbox.
3. Attach CPU-640 to the chassis. Slide control-panel tabs into slots on chassis and lay the board onto stand-offs so that mounting holes line up with those on the chassis. Secure with six (6) screws (four across the top of the board, and two to the left of the power supply) provided with the chassis. (See Figure 8.)
4. If installing KDM-2, install the stand-offs included with the keyboard kit. (See Figure 8.)
· The upper edge of the keyboard mounting plate rests on two stacked pairs of male-female stand-offs. Connect P/N 42185 (2.0 inch, 50.8 mm) to P/N 42186 (1.312 inch, 33.33 mm).

32

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing the Control Panel

Installation

· Thread the stacked pairs of stand-offs through mounting holes on the control panel as shown in Figure 8.
· Thread two P/N 42166 (0.937 inch, 23.8 mm) male-female stand-offs through mounting holes in the chassis rail.
· Attach ribbon cable from keypad to J4 connector on control panel. (See Figure 3.)
· Align the keypad with the stand-offs and screw it down.
5. If using the NCA instead of the KDM-2, refer to Section 3.5.2 “Using NCA as Primary Display” and the NCA Installation Manual.
6. If not using an LEM-320, secure the last 4 mounting holes with screws.

CAUTION: It is critical that all mounting holes of the NFS-640 are secured with a screw or ! standoff to insure continuity of Earth Ground.

Stack of two male-female stand-offs: connect P/N 42185 (2.0 inch, 50.8 mm)
to P/N 42186 (1.312 inch, 33.33 mm).

Note: If not using this location, secure these mounting holes with screws.

CHS-M2-0604-assy.wmf

Attach two (0.937 inch, 23.8 mm) stand-offs to chassis rail; screw keypad mounting plate to the stand-offs.

Lower edge of panel circuit modules slide into chassis slots, and upper edge mounts onto PEM studs on the chassis flange.

Figure 8 Locating and Aligning Stand-offs for Keypad/Display and Panel Circuits (Chassis CHS-M2 shown)
3.5.2 Using NCA as Primary Display
The NFS-640 can be set up to use an NCA instead of a KDM-2. In this system design, connect the network port on the NFS-640 (J1) directly to the network port on the NCA (J3); see the NCA Manual for specific instructions.
Note: This system design is required in Canadian stand-alone applications.
If the NFS-640 and NCA are being used as a stand-alone pair, each device must be programmed separately using VeriFire Tools in its off-line programming mode. Because the VeriFire Tools computer also uses the network port, NFS-640 and NCA must be temporarily disconnected for programming. If the NFS-640 with NCA is connected to a network, there are two additional options for programming: either connect the VeriFire Tools programming PC to the network port on the NCM board, or program the NFS-640 through another network node. (See VeriFire Tools on-line help for details.)

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

33

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing the Control Panel

TB1 TB1

3.5.3 Loop Expander Module
Installing a Loop Expander Module adds a second SLC loop to the control panel. Refer to the Figure 10 for connector illustrations.

B+ A+ B- A-

1. Thread four (4) 0.937 inch (23.8 mm) stand-offs through indicated holes in the CPU-640 board.
2. Plug stacker-connector into J3 on the CPU-640.

B+ A+ B- A-

3. Lay the LEM onto the standoffs and connect the Loop Expander Module (LEM) into the stacker-connector attached to J3.

4. Attach LEM using screws provided with

LEM-320PCA

J1

the module.

Figure 9 SLC Connections for LEM-320

5. After LEM is mounted on the control

panel, connect the SLC loops to TB1 on

the LEM and TB16 on the CPU-640.

This system supports either FlashScan or CLIP mode devices. Refer to the SLC loop manual

for wiring requirements and specific details.

Lem-slc.cdr

Stacker-connector

LEM-320

CPU-640

J3
J1
The short-pin end plugs directly into the top of the CPU-640 plug. The long- pin end plugs into the back of the LEM board.
CAUTION: If the stacker-connector is installed incorrectly, the short-pin end of the plug can ! to make a secure connection when plugged through the back of the LEM.
Figure 10 Mounting LEM-320 with the Stacker-connector

34

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing the Control Panel

Installation

3.5.4 Network Control Module
If networking two or more control panels (including NCAs), each unit requires a Network Control Module (NCM); wire and fiber versions are available. The NCM-W/F can be installed in any panel circuit module position (see Section 3.5.5 “Panel Circuit Modules and Other Option Boards”); the default position is immediately to the right of the control panel.
1. Mount the NCM in the selected position. If another board is going to be mounted in the slot immediately in front of it, use stand-offs provided with the next board to secure it in place. Otherwise use the screws provided with the NCM.
2. Connect J1 on the control panel to J3 on the NCM using the network cable provided (P/N 75556) as described in the NCM Installation Document. Do not connect two NCMs via NUP ports (aka NUP to NUP).
3. Connect Channel A and/or Channel B as described in the NCM Installation Document.
Note: See the Noti·Fire·Net Manual and NCM Installation Document for wiring diagrams and system configuration information. See the BMP-1 Product Installation Drawing if considering mounting the module behind blank module plate in a dress plate or annunciator backbox.
3.5.5 Panel Circuit Modules and Other Option Boards
If installing option boards into a CAB-4 Series backbox, mount and connect those boards at this time. General instructions follow; the sections about individual option boards contain any modulespecific instructions. Option boards can be mounted in the front (fourth) layer of CHS-M2 (see flanges as shown in Figure 8), or in any position on the other row(s) of equipment, using 0.937″ (23.8 mm) standoffs between layers.
Note: An option board can be mounted above a Loop Expander Module or Network Control Module; for ease of access, be sure to complete installation of those devices before mounting a second layer.
1. Slide the tabs at the bottom of the option board into slots on the chassis as shown in Figure 11.
2. Lay the board back onto the flanges so that the studs line up with mounting holes on the option board.
3. Attach the option board using screws provided with the module.

Module Screw

Slots

nfs640-mnticm.cdr

Shown with CHS-M2

Shown with CHS-4N

Figure 11 Inserting a Module into a Chassis

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

35

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Chassis CHS-4N

Installing the Control Panel
Install stand-offs on these two (2) studs in any one of four positions along chassis.

CHS-4studpos.cdr tm4adp4.cdr

Figure 12 Location of Stand-offs on Module Chassis Note: See the BMP-1 Product Installation Drawing for details if considering mounting the module behind blank module plate in a dress plate or annunciator backbox. This dress plate is suitable for modules that do not need to be visible or accessible when the door is closed.
Mount single-space blank plate onto compatible dress panel or backbox trim ring
Single-space blank plate

Mount optional module onto standoffs on the blank plate

Fasten optional module to the plate with four screws (included).

Figure 13 Mounting Single-space Blank Plate with Optional Module Connecting the Power Cables
WARNING: Remove all power sources to equipment while connecting electrical components. ! Leave the external, main power breaker OFF until installation of the entire system is complete.
WARNING: Several sources of power can be connected to the control panel. Before servicing the ! control panel, disconnect all sources of input power including the battery. While energized, the
control panel and associated equipment can be damaged by removing and/or inserting cards, modules, or interconnecting cables.
3.5.6 Overview
Complete all mounting procedures and check all wiring before applying power. Electrical connections include the following:
· Primary AC power source ­ 120 VAC, 50/60 Hz, 3.0 A (NFS-640E uses 240 VAC, 50/60 Hz, 1.5 A) from line voltage source. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Code (NEC) and/or local codes. Use 12 AWG (3.1 mm2) wire (maximum) with a 600-volt rating.

36

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing the Control Panel

Installation

· Secondary power source ­ 24 VDC from batteries, installed in the control panel (or in an optional battery cabinet). Secondary (battery) power is required to support the system during loss of primary power.
· External power sources ­ 24 VDC power for Smoke Detectors (4 wire), NACs, and Annunciators.
See Appendix B “Electrical Specifications” for details and overall installation guidelines.
3.5.7 Connecting the Control Panel to AC Power
Connect primary power as follows (see Figure 14 below): 1. Turn off the circuit breaker at the main power distribution panel. 2. Remove the plastic insulating cover from TB2. 3. Connect the service ground to terminal marked EARTH. 4. Connect the primary neutral line to terminal marked NEUTRAL and the primary Hot line to
terminal marked HOT. 5. Reinstall the plastic insulating cover over TB2.
TB2
Hot

BATT+ BATT ­ EARTH NEUTRAL HOT nfs640-acdc.cdr

Neutral

Ground (Earth)
Battery (-)

Battery (+)

TB1
Figure 14 AC & DC Power Connections
3.5.8 Checking AC Power
Table 4 contains a checklist for checking the system with AC power applied: CAUTION: While checking AC power, make sure batteries are not connected. ! Follow the sequence of steps in Section 3.2 “Installation Checklist”, Table 2; this is Step 16.

Component
Control panel circuit board
Each panel circuit module
Each auxiliary power supply

Status The green AC Power indicator on; the system Trouble indicator on because batteries are not connected. The yellow Trouble indicator may come on for approximately 10 seconds after applying AC power. (This only applies to an unconfigured system.) The yellow Trouble indicator comes on because batteries are not connected.
Table 4 AC Power Checklist

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

37

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing the Control Panel

3.5.9 Installing and Connecting the Batteries

WARNING: Battery contains sulfuric acid which can cause severe burns to the skin and eyes, and ! can destroy fabrics. If contact is made with sulfuric acid, immediately flush skin or eyes with
w
water for 15 minutes and seek immediate medical attention.
WARNING: Do not connect the Battery Interconnect Cables (P/N 75560 and 75561) at this time. ! Make this connection AFTER initial system primary powerup. Follow sequence of steps in Section
3.2 “Installation Checklist”, Table 2; this is Step 17.
Batteries (2) are installed in the control panel cabinet or in a separate battery cabinet which can be mounted below the control panel or up to 20 feet (6.096 m) away from the control panel, in the same room.
Connect the battery as follows (see Figure 14 above):
1. Install batteries (2) into bottom of cabinet or into separate battery cabinet.
2. Connect the red cable from TB1(+) on the control panel to the positive (+) terminal of one battery.
3. Connect the black cable from TB1(­) on the control panel to the negative (­) terminal of the other battery.
4. Connect the remaining cable between the negative (-) terminal on the first battery to the positive (+) terminal on the second battery.
3.5.10 APS-6R Auxiliary Power Supply Connections
If an optional APS-6R power supply is installed in the cabinet, connect it with no power applied; follow sequence of steps in Section 3.2 “Installation Checklist”, Table 2; this is Step 4. For all information pertaining to these connections see the APS-6R Instruction Manual.
3.5.11 External DC Power Output Connections
Terminal TB7 provides two (2) power outputs, resettable and non-resettable. Each output is powerlimited. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 2; this is part of Step 6.

Non-resettable Power

Resettable Power

+ ­ + ­

TB7
nfs640-dcout.cdr

Figure 15 Power Supply DC Outputs – TB7
24 VDC Resettable Power Circuit (Four-Wire Smoke Detectors). The power supply provides a single 24 VDC filtered, power-limited, resettable power circuit for devices that require resettable power (such as four-wire smoke detectors). This circuit is power-limited, but must be supervised. To provide supervision, install a UL-listed end-of-line power supervision relay (such as the A77-716B) after the last device. Connect the power supervision relay normally open contact in series with an Initiating Device Circuit (IDC). The four-wire power circuit energizes the power supervision relay. When you reset the system, the control panel removes power from these terminals for approximately 15 seconds.
Connect external field wires to the power supply terminals TB7 RESET(+)and(­) to provide up to 1.25 A of current for powering four-wire smoke detectors. See Figure 15 above.

38

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing the Control Panel

Installation

24 VDC Non-resettable Power Circuit. The power supply provides one 24 VDC filtered, power-limited, non-resettable power output, capable of up to 1.25 A. Use this circuit to power devices that require low-noise 24 VDC power (such as annunciators or the TM-4).
Connect external field wires to power supply terminals TB7 NONRST(+)and(­) to provide up to 1.25 A of non-resettable current for powering external devices such as annunciators. See Figure 15 above.
CAUTION: During system reset, power remains at terminals TB7 NONRST(+)and(­). !

3.5.12 NAC Connections & Releasing Circuits

The control panel provides four NAC terminals as shown in Figure 16. Each can be configured as Style Y (Class B) or Style Z (Class A) as shown in Figure 17. Each circuit can provide 2.5 A of current, but the total current drawn from the main power supply cannot exceed 6.0 A in alarm condition (refer to Table 12). NAC circuits are supervised and power-limited. Use ULlisted 24 VDC notification appliances only (refer to the Notifier Device Compatibility Document).
Note: Any NAC can be programmed as a releasing circuit, but only one releasing device per circuit is allowed. For more information, refer to Section 4.5 “Releasing Applications” in this manual and the NFS-640 Programming Manual. Refer to the Device Compatibility Document, for UL-listed compatible releasing devices. Sample connections for NAC terminals are shown in Figure 17. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 2; this is part of Step 6.

TB6 – NAC#1 TB5 – NAC#2 TB4 – NAC#3 TB3 – NAC#4
Figure 16 NAC Terminals

B+ B- A+ A- B+ B- A+ A- B+ B- A+ A- B+ B- A+ Anfs640-NACS.cdr

UL-listed ELR-2.2K, 1/2 W (supplied)

nfs640-nacout.cdr

B+ B­ A+ A­

B+ B­ A+ A­

B+ B­ A+ A­

Unused Circuits

Style Y (Class B) Connection

Style Z (Class A) Connection

Figure 17 Notification Appliance/Releasing Circuit Connections

3.5.13 Output Relay Connections

The panel provides a set of Form-C relays. These are rated for 2.0 A at 30 VDC (resistive): · Alarm – TB8 · Trouble – TB9 · Supervisory – TB10 · Security – TB11

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

39

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing the Control Panel

The Supervisory and Security contacts can also be configured as Alarm contacts by setting switches SW1 and SW5 away from the factory default positions shown in Figure 18. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 2; this is part of Step 6.

ALARM RELAY NO NC C

TROUBLE RELAY SUPERVISORY RELAY SECURITY RELAY

NO NC C

NO NC C

NO NC C

TB11

SW1 set to Supervisory

TB8

TB9

TB10

SW1

SW5

SW5 set to Security

SUPV ALARM

Move switch to opposite SECUR ALARM position to set to Alarm.

nfs640-relay.cdr

Figure 18 Form-C Relay Connections
3.5.14 Backup-Alarm Switches

WARNING: Do not enable the BACKUP option switch for any of the four Notification Appliance ! Circuits (NACs) if they are used for releasing functions!

SW9 SW8

Backup alarm switches are provided that enable NACs and the alarm relay to activate during a backup alarm condition. If the main board’s microcontroller fails and an alarm is reported by any detector or a monitor module that has backup reporting enabled, the NAC will turn on if the corresponding switch was enabled. The alarm will activate during microcontroller failure regardless of the settings of Switch 6-9.

SW7

SW6

DISAB ENAB

1 NAC 3

2

4

nfs640-sw6-9.cdr

· Switch 6 – NAC#1

· Switch 7 – NAC#2 · Switch 8 – NAC#3

Figure 19 Backup Alarm Switches

· Switch 9 – NAC#4

So, for example, if Switch 6 and Switch 8 were enabled at the time of an alarm during microcontroller failure, NAC#1 and NAC#3 would activate. Follow sequence of steps in Section 3.2 “Installation Checklist”, Table 2; this is Step 7.

3.5.15 Installing a Transmitter Module TM-4

TM-4 is power-limited. Connections are on TB7 nonresettable output and TB13 EIA-485 ACS Mode. Refer to the Transmitter Module TM-4 installation document for installation details.

40

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

UL Power-limited Wiring Requirements

Installation

3.6 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any nonpowerlimited circuit wiring. All power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockout and or conduits. To maintain separation, group non-power limited modules together, i.e., group modules on the same side of the enclosure or in separate rows.
Figure 20 shows one configuration that meets these UL requirements. The first two rows of modules are configured with at least a 0.25 inch (6.35 mm) separation between power-limited and nonpower-limited wiring; AC and battery wiring is routed away from power-limited wiring.

Power-limited Circuits

Nonpowerlimited circuits

Powerlimited circuits

nfs640-pwrlmtwir.cdr

To cabinet-mounted battery
Figure 20 Typical Wiring for UL Power-limited Wiring Requirements
Note: AC and battery wiring are not power-limited. Maintain at least 0.25 inches (6.35 mm) between power-limited and non power-limited circuit wiring. Install tie wraps and adhesive squares to secure the wiring. Use a power- limited source for relay output on terminals TB8 ­ TB11.
3.6.1 Labeling Modules and Circuits
At the time of installation, each nonpower-limited circuit connected to ACM- 8R, ARM-4, CRM4RK, CRE-4, and LDM-R32 modules must be identified in the space provided on the cabinet door label when connected to a non-power-limited source of power.
The label lists all compatible power-limited modules and circuits; also see Figure 3 at the start of this manual.
The following devices are power-limited only when connected to power-limited sources: ARM-4, CRM-4RK, CRE-4, LDM-R32. When one of these devices is connected to a non-power-limited source, the power-limited marking must be removed.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

41

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing Panel Circuit Modules

3.7 Installing Panel Circuit Modules

3.7.1 Overview

Installation of a panel circuit module is divided into five (5) operations: · Mounting an optional expander board to the module (e.g. mounting ICE-4 onto an ICM4RK). · Connecting communication ribbon cables from Control Panel to the module. · Installing the module onto a chassis. · Connecting modules to the power supply. · Field wiring the module.
Refer to Section 2.10 “Panel Circuit Modules” for a complete list of modules and their expanders.

3.7.2 Mounting Expander Boards

Expander Board Modules, such as ICE-4 or CRE-4, need to be mounted onto their respective modules (ICM-4RK, CRM-4RK) prior to installation onto a chassis. To mount an Expander Module:
1. Remove one module support screw and set it aside for later use.
2. Replace the module support screw with one module stand-off.
3. Repeat Steps 1 and 2 for the three remaining module support screws.
4. Insert pins on the front of the expander board into connector on the back of the module. Make sure the pins are in line; then, press the two units together until they snap into place.
5. Install the four module support screws (removed earlier) through the back of the expander board and into the stand-offs. Tighten securely.
Figure 21 illustrates the steps.

Remove existing module support screw

Install module standoff

Plug in the expander board

Steps 1 & 2

Secure with module support screws

nfs640-pcmods.cdr

Steps 4 & 5
Figure 21 Expander Module Installation

42

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing Panel Circuit Modules

Installation

3.7.3 Connecting Ribbon Cables for a CAB-4 Series Backbox
Expander Row Ribbon Cables connect panel circuit modules to the Control Panel.
Figure 22 shows a typical wiring setup using two Expander Row Ribbon Cables (P/N 71088) to connect the control panel to two rows of four (4) panel circuit modules each below the Control Panel in a CAB-4 Series backbox.

J6 – Third Row

J5 – Second Row

nfs640-icmribbon.cdr

Expander Row Ribbon Cable (P/N 71088)

MODUL E TYPE
LAMPS
SWIT CH

MODULE TYPE
LAMPS
SWITCH

Group of panel modules in second cabinet row

P1.1­P1.8

MODULE TYPE
LAMPS SWIT CH

MODULE TYPE
LAMPS SWIT CH

MODULE TYPE
LAM PS SWITCH

MODULE TYPE
LAM PS SWITCH

MODUL E TYPE
LAMPS SWIT CH

MODUL E TYPE
LAMPS SWIT CH

P2.1­P2.8

P3.1­P3.8

P4.1­P4.8

Expander Row Ribbon Cable (P/N 71088)

Group of panel modules in third cabinet row

MODULE TYPE
LAMPS SWIT CH

MODULE TYPE
LAMPS SWIT CH

MODULE TYPE LAMPS
SWIT CH

MODULE TYPE LAM PS
SWITCH

MODULE TYPE LAM PS
SWITCH

MODULE TYPE LAM PS
SWITCH

MODUL E TYPE LAMPS
SWIT CH

MODUL E TYPE LAMPS
SWIT CH

P5.1­P5.8

P6.1­P6.8

P7.1­P7.8

Figure 22 Expander Row Ribbon Cable Setup

P8.1­P8.8

3.7.4 Installing the Panel Circuit Modules

To install a panel circuit module such as a ICM-4RK or CRM-4RK into the chassis:
1. Angle the module into the chassis so that the lower board edge slips into the chassis slots as shown in Figure 11.
2. Push the upper end of the module into the upper opening in the chassis.
3. Secure the module to the chassis with the two module screws (provided with the module). Tighten securely.
4. Connect the Ribbon Cable to the module.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

43

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing Panel Circuit Modules
3.7.5 Connecting ICM-4RK and ICE-4 Modules
The total current available for any group of Notification Appliance Circuits (NACs), other than the four NACs on the control panel, cannot exceed the following:
· 6.0 A when powered from the APS-6R · 1.25 A when powered from a NFS-640 DC power output terminal Shown below are the wire connectors on the bottom of the ICM-4RK and the ICE-4 modules.

nfs640-icmconn.cdr

J5 J6 J5 J6
Figure 23 ICM-4RK/ICE-4 Connectors
Power Supply Connections
The figure below illustrates typical connections from main power supply.

ICM-4RK ICE-4

Bell power cable (P/N 75400) or alternate Power Harness (P/N 71093, with lugs removed and wires stripped)
Black wire (­), Blue wire (+)
+ ­ + ­

Eight NACs that share 1.25 A
J5 J6 ICM-4

TB7

J5 ICE-4

24V NONRST 24V RESET
TB7 on Control Panel

Power Cable P/N 71091

Figure 24 Main Power Supply Connection
Multiple Power Supplies
Cut JP1 and JP2 on ICM-4RK when supplying 24V power from two separate sources to the ICM-4RK. ICM-4RK circuits 1-2 will receive their power from J5; ICM-4RK circuits 3-4 will receive their power from J6.
Cut JP1 and JP2 on ICE-4 when supplying power from separate sources to expander circuits 5-8. ICM-4RK circuits 5-6 will receive power from J5 on the ICE-4 and ICM-4RK circuits 7-8 will receive power from J6 on the ICE-4.
See Figure 25 for jumper locations.

nfs640-icmnac.cdr

44

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing Panel Circuit Modules

ICM-4RK/ICE-4 Jumpers
JP1 JP2

J5

J6

Installation

APS-6R #1 APS-6R #2

J5
ICM-4RK J6

Two circuits that share 3 A of one AVPS-24 (#1)
Two circuits that share 3 A of one AVPS-24 (#2)

Figure 25 Sample ICM-4RK Configuration for Multiple Power Supplies

3.7.6 Field-Wiring the ICM-4RK and ICE-4 (NFPA Style Y or Z)
Guidelines for field-wiring:
· Notification Appliance Circuits (NACs) are supervised, power-limited, and can connect to an energy-limited cable.
· Use only the compatible, UL-listed notification appliances listed in the Device Compatibility Document.
· Wire notification appliances according to the manufacturer’s instructions.
· Maximum current per circuit is 3.0 A. Maximum current per module depends on the type of power supply (standard or auxiliary).
· Canadian installations require model N-ELR End-of-Line Resistor Assembly (Style Y only).
· Size NAC wiring so the voltage drop does not exceed the minimum rated voltage of the notification appliance used as the last device on the circuit.
· For zone coded applications, refer to the UZC-256 Universal Zone Coder manual.
· The ICM-4RK is California Code programmable (microprocessor P/N 34077 Rev. B or higher). To program for California Code, cut diode D35 as shown in Figure 27. (See appendix section of the Programming Manual for more detail.)

Typical NFPA Style Y (Class B) NAC

Typical NFPA Style Z (Class A) NAC

4.7K, 1/2 watt ELR P/N 71252

UL-listed 24 VDC Polarized Devices

Jumpers for unused circuits

Jumpers for unused circuits

ICM4wire-YB.cdr

B+ A+ A­ B­ B+ A+ A­ B­

B+ A+ A­ B­ B+ A+ A­ B­

Figure 26 Field-Wiring an ICM-4RK/ICE-4

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

45

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing Panel Circuit Modules

icm-4rk-d35.cdr

Cut D35 on the circuit board to produce California code.
Figure 27 Location of D35 on ICM-4RK Circuit Board
3.7.7 Connecting CRM-4RK/CRE-4 Modules
Guidelines for field-wiring the CRM-4RK and the CRE-4: · Provide Form-C relay contacts (silver alloy) used for medium duty switching or pilot duty. · Terminals will accept wire sizes from 12 AWG to 18 AWG (3.1 to 0.78 mm2). · Activation of a module or expander relay occurs automatically when an alarm is detected on a programmed IDC. · UL contact ratings are 5 A at 125 VAC (resistive) or 30 VDC (resistive) and 2 A at 125 VAC (inductive). · For more information, refer to Section 3.6 “UL Power-limited Wiring Requirements”. · For typical field-wiring connections, refer to Figure 28.
Optional CRE-4 Control Relay Expander

CREEXPCO-RK.cdr

Typical connections for a Form-C control relay in normal position.

CRM-4RK

CONTROL RELAY

CONTROL RELAY

Figure 28 Field-Wiring a CRM-4RK or CRE-4 Module

46

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Auxiliary Relay Module (ARM-4): Product-Specific Details

Installation

3.8 Auxiliary Relay Module (ARM-4): Product-Specific Details
3.8.1 Overview
If a CRM-4RK/CRE-4 is to be incorporated into the control panel and an ARM-4 is being driven by it, note the following:
· Each ARM-4 must be supported by one CRM-4RK or one CRE-4.
· If using ARM-4’s for both modules, mount two ARM-4’s in separate positions.
· If mounted in FACP enclosure keep all non-power limited wiring separate from power limited wiring.
For ease of installation, service, and wiring mount the ARM-4 module in a position on the chassis that will not have any other module or expander board in front of it. However, you can install the ARM-4 directly behind the CRM-4RK or CRE-4.
ARM-4 mounts in the second, third or fourth row of a CAB-4 series backbox, against the back of a chassis CHS-4 or CHS-4L. The ARM-4 may be mounted in any of the 8 adjacent backbox positions the cable can reach.
3.8.2 Installation
To install the Auxiliary Relay Module in the chassis:
1. Select a mounting position for the module on the chassis.
2. Install two (2) mounting stand-offs onto the studs of the chassis, at the selected location, as shown in Figure 12. Tighten securely.
3. Install three (3) support stand-offs, with screws, onto the PC board in the locations shown in Figure 12 or in the two right-hand positions on the first row. Tighten securely.
4. Position module over the stand-offs on the chassis; fasten the module to the chassis with the two (2) retaining screws. Tighten securely.
5. Connect one end of the Cable (P/N 71092) to plug P1 on the ARM-4. Note: The other end of the cable is connected to jumper JP5 on the CRM-4RK or CRE-4.
6. Connect all available external wiring at this time. Refer to Section 3.8.3 “Field Wiring an Auxiliary Relay Module”.

Terminal Assignments (typ. 4 places)
These 2 holes for mounting stand-offs.

NC NO C Com K1 K2 K3 K4 NC NO C ­ + + ++

NC NO C

NC NO C

These 3 holes for support stand-offs.

P-1

P2

Connection for

Cable P/N 71092

P1

ARM-4.cdr

Figure 29 ARM-4 Stand-off & Terminal Locations

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

47

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing Remote Printers and/or CRT

3.8.3 Field Wiring an Auxiliary Relay Module

The figure above shows terminal assignments for ARM-4 module control relays K1-K4, which control nonpower-limited circuits. Power-limited and nonpower- limited circuit wiring must remain separated by at least 0.25 inch (6.35 mm) within the cabinet and exit the cabinet though different knockouts, conduits, or both.
Note: For more information, refer to Section 3.6 “UL Power-limited Wiring Requirements”.
The table contains contact ratings for relays K1-K4 on the ARM-4 module:

Resistive Load

Contacts

Normally Open (N.O.)

Normally Closed (N.C.)

125 VAC

20 A

10 A

30 VDC

20 A

10 A

Table 5 Contact Ratings for K1-K4 on the ARM-4 Module

3.9 Installing Remote Printers and/or CRT

3.9.1 Custom Cable Fabrication

A custom cable needs to be fabricated to connect the PRN-5 Printer, Keltron Printer or the CRT-2 Monitor to the system. Length of the cable will vary with each installation, but should not exceed a maximum length of 50 feet (15.24 meters). Printer must be installed in the same room as panel. Construct cable as follows:
1. Using overall foil/braided-shield twisted-pair cable, properly connect one end to the DB-25 Connector using the wiring specifications shown in the table below. (Custom cable kit P/N 90106 is provided.)
2. Tighten clamp on connector to secure cable.

DB-25 Connector (Custom cable kit 90106) TB14 on Control Panel

Pin 3 Pin 2 Pin 7

TX RX REF

3.9.2 Installing and Configuring the PRN-5 Printer

When connected to the Control Panel via an EIA-232 interface, the PRN-5 prints a copy of all status changes within the control panel and time-stamps the printout with the time of day and date the event occurred. It provides 80 columns of data on standard 9″ by 11″ tractor-feed paper.
Note: You can also use the EIA-232 printer interface with UL-listed I.T.E. equipment, such as personal computers, to monitor the control panel for supplementary purposes.
This section contains information on connecting a printer to the control panel and for setting the printer options.

Connecting a Remote PRN Printer
Remote printers require a 120 VAC, 50/60 Hz primary power source. If required for the fire alarm system configuration (for example, a Proprietary Fire Alarm System), a remote printer requires a secondary power source (battery backup). Because a secondary power source is not provided, use a separate Uninterruptable Power Supply (UPS) that is UL-listed for Fire Protective Signaling. You

48

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing Remote Printers and/or CRT

Installation

may use your building emergency power supply, so long as it meets the power continuity requirements of NFPA 72. Refer to NFPA 72 for further details.
Connect the remote printer to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control panel as shown in Figure 30.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the remote printer. Tighten securely.

DB-25 connector on PRN-5 (female socket shown)
Control Panel

Note: Outputs are power-limited but are not supervised.

Terminate one end of

shield at backbox

PRINTER

PC/CRT

TX RX REF TX RX REF

TB14

TB15

nfs640-prn5conn.cdr

Figure 30 Remote Printer Connections

Setting Printer Options
Refer to the documentation supplied with the PRN-5 for instructions on using the printer menu controls. Set the printer options (under the menu area) according to the settings listed in Table 6.

Option
Font LPI ESC Character Bidirectional Copy
CG-TAB Country Auto CR
Color Option Formlen
Lines Standard

Setting

Option

HS Draft 6 LPI ESC ON
Graphic E-US ASCII OFF
Not Installed
6LPI=60 Exec 10.5

CPI Skip Emulate I/O
Buffer Serial
Baud Format Protocol Character Set Sl.Zero Auto LF PAPER BIN 1 BIN 2 SINGLE PUSH TRA PULL TRA PAP ROLL

Table 6 PRN-5 Setup Options

Setting
10 CPI 0.5 Epson FX-850
40K
9600 or 2400 7 Bit, Even, 1 Stop XON/XOFF Standard On Off
12/72″ 12/72″ 12/72″ 12/72″ 12/72″ 12/72″

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

49

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing Remote Printers and/or CRT
3.9.3 Installing and Configuring a Keltron Printer
Connect the remote printer to the Control Panel as follows: 1. Connect the three (3) open leads of the custom cable to the TB14 terminal block on the control
panel as shown in the figure below. 2. Connect DC power from TB7 terminal block on the control panel as shown in the figure below. 3. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the Keltron printer.
Tighten securely.

Keltron printer
24 VDC
connections (14 AWG, 2.00 mm2)

DB-25 connector on Keltron Printer (female socket shown)

Terminate one end of shield at backbox

24V NONRST 24V RESET

+ ­

+ ­

Control Panel

PRINTER

PC/CRT

TX RX REF TX RX REF

TB14

TB15

TB7
nfs640-keltconn.cdr

Figure 31 Keltron Printer Connections
Setting up the Keltron Printer
Set up a Keltron printer as follows: 1. The printer communicates using the following protocol:
· Baud Rate: 9600 · Parity: Even · Data bits: 7 2. Set the printer DIP switches SP1 and SP2 according to settings in the table below:

SP1 On Off

1

X

2

X

3

X

4

X

5

X

6

X

7

X

8

X

SP2 1 2 3 4 5 6 7 8

On Off X X X
X X X
X X

Table 7 Keltron DIP Switch Settings

50

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing Remote Printers and/or CRT

Installation

3.9.4 Installing and Configuring a CRT-2
A CRT-2 can only be used in a non-networked application when used with the NFS-640. For further details on setting up the CRT-2, refer to the NFS-640 Operations Manual.
Connect a CRT-2 to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB15 terminal block on the control panel as shown in the figure below.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the CRT-2. Tighten securely.
3. Set parameters as discussed below.

DB-25 connector on CRT-2 (female socket shown)

Control Panel

PRINTER

PC/CRT

TX RX REF TX RX REF

TB14

TB15

Terminate one end of shield at backbox

nfs640-crt2conn.cdr

Figure 32 Connecting a CRT-2
Setting CRT-2 Parameters
The CRT-2 communicates with the control panel through a protocol defined by thirteen groups of parameters. To access a parameter group, press the corresponding function key (F1-F12) as shown in Table 8 below. You can then program parameters in each group.
Enter the CRT-2 setup menu by pressing and holding the key while pressing the key. Use arrow keys to move through the selections in each setup group; press the space bar to view the options for each parameter. When finished programming all setup groups, press the key. To save all changes, press .
Table 8 shows the standard settings for using the CRT-2 with the NFS-640; for one instance where these settings may change slightly see Section 3.9.6 “Connecting Multiple Printers, CRTs, or CRT/PRN Combination”. The basic settings for using the CRT-2 with NFS-640 are: · Baud Rate 9600 · Data format 8 1 N · Protocol xon/off.
Note: This section covers installation only; for information on how the CRT-2 functions as part of the fire alarm system, see the NFS-640 Operations Manual.

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

51

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installation

Installing Remote Printers and/or CRT

Function Key
F1: Quick (“Read Status” key)
F2:Genrl (“Alter Status” key)
F3: Displ (“Prog” key)
F4: Kybd (“Spl Funct” key)
F5: Keys (“Prior” key)
F6: Ports (“Next” key)
F7: Host (“Auto Step” key)
F8: Print (“Activ Signal” key) F9: Emul
F10 F11 F12: Prog (“Ack Step” key)

CRT-2 Parameters
Emulation=CRT-2 Comm Mode=Full Duplex Enhanced=On
Emulation=CRT-2 Auto Font Load=On Monitor Mode=Off Host/Printer=EIA/Aux
Page Length=24 Display Cursor=On Columns=80 Scroll=Jump
Language=U.S. Keyclick=Off Key Lock=Caps
Enter Key= Alt Key=Meta Pound Key=U.S.
EIA Baud Rate=9600 Aux Baud Rate=9600 EIA Xmt=Xon-Xoff Aux Xmt=Xon-Xoff EIA Break=Off Aux Break=Off
Comm Mode=Full Duplex Recv =Ignore Send Block Term=
Prnt Line Term=

EIA Baud Rate=9600 Aux Baud Rate=9600 Language=U.S.
Enhanced=On Auto Page=Off Bell Volume=09
Screen Length=26 Lines Cursor=Blink Line Width Change Clear=Off Refresh Rate=60 Hz
Char Set Mode=ASCII Key Repeat=Off Keyboard Present=Yes
Return Key= Disconnect=Pause
EIA Data Format=8/1/N Aux Data Format=8/1/N EIA Recv=Xon-Xoff(XPC) Aux Recv =Xon-Xoff(XPC) EIA Modem Control=Off Aux Modem Control=Off
Local=Off Send ACK=On Null Suppress=On
Prnt Block Term=

EIA Data Format=8/1/N Aux Data Format=8/1/N Host/Printer=EIA/Aux
Auto Wrap=Off Auto Scroll=On Warning Bell=On
Screen Video=Normal Auto Adjust Cursor=On Speed=Normal Overscan Borders=Off
Key Mode=ASCII Margin Bell=Off
Backspace=/ Desk Acc=Disabled
EIA Parity Check=On Aux Parity Check=On EIA Xmt Pace=Baud Aux Xmt Pace=Baud EIA Disconnect=2 sec Aux Disconnect=2 sec
Recv = Send Line Term=
Secondary Recv=Off

Attribute=Page WPRT Intensity=Dim WPRT Blink=Off Status Line=Off

Bright Video=Off WPRT Reverse=Off Display NV Labels=Off Fkey Speed=Normal

Page Edit=Off WPRT Underline=Off Save Labels=On

Setup Group F10 does not affect communications with the control panel.

Setup Group F11 does not affect communications with the control panel.

Program the function keys as follows: F1 ~A F2 ~B F3 ~C F4 ~D F5 ~E F6 ~F F7 ~G F8 ~H F9 ~I F10 ~J F11 ~K F12 ~L F13 ~M F14 ~N F15 ~O F16 ~P Shift F13 ~Q

Table 8 Standard CRT-2 Settings for Use with NFS-640

3.9.5 Connecting a PC
A PC can be hooked up to the Control Panel EIA-232 port (J1) to allow the VeriFire Tools programming utility to upload and download the operating program of the control panel. Refer to the insert in the VeriFire Tools CD and to the program’s on-line help function for instructions.
Note: Download operations that change the basic program of the control panel must be performed by responsible service personnel in attendance at the control panel. After downloading a program, test the control panel in accordance with NFPA 72-1999.

52

NFS-640 Installation Manual P/N 51332:B2 07/27/2004

Technical Manuals Online! – http://www.tech-man.com

firealarmresources.com

Installing Remote Printers and/or CRT

Installation

3.9.6 Connecting Multiple Printers, CRTs, or CRT/PRN Combination

Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu: · Set Host/Printer=EIA/AUX. · Set EIA Data F

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NOTIFIER User Manuals

Related Manuals