OPERATING INSTRUCTIONS
Description
The TMP2 series of overheat detectors, includes an electronic circuit for
signal conditioning generated by the transducer.
The electrical signal of the transducer is transformed into an engineered
output with different interface solutions.
The electronic card, reduced to the minimum size, is made using SMT technology
and placed directly into the unit probe.
Features
High reliability, dependable long-life.
High Immunity to EMI disturbances and virtually eliminate false alarms.
Two temperature set-point levels setting from -20°C to 110°C.
Supply Voltage | 10-30 Vdc |
---|---|
Supply current | 200 uA in normal condition |
20 mA in alarm condition
Supply fuse| 63 mA
Cable Type| 2 wires cable.
Automatic self diagnosis
Typical application
TMP2 detectors are particularly suitable in commercial and industrial plants
in presence of flammable or corrosive elements or condensing steams.
Suitable for use in explosive atmospheres.
Hazard material stores.
Extraction ducts.
TMP detectors are designed according to European requirements EN54 and ATEX
directive.
Interconnecting cable guidelines
The TMP2 heat detector requires an interconnecting cable having two
conductors. Note that the use of shielded cables is recommended.
Should more than one strand of wire be used in the wiring be sure that the
cable screen is continuous and that the conductors are soldered at the joints.
Furthermore it must be remembered that the protective shielding must be
earthed only on the side of the control unit or power supply, and must never
be connected to the detector.
The use of terminal leads is recommended, otherwise the joints on the power
cable must be clamped with flat tab connectors or soldered.
It is best to avoid connection, to the same power source used for the
detectors, inductive loads could generate ‘noises’ on the power supply to the
system.
In any case the use of auxiliary winding on the main power transformer is
recomended for supply suppression devices, actuators, sounders or other
devices.
Interconnection references for current loop with end of line resistor
The cable screen must be connected to safety earth in safe area.
TMP2 probe cable assignment
Brown cable| Terminal block +
White cable| Terminal block –
The sensor is calibrated in the factory specifically for the temperature
levels requested by the client.
Installation and maintenance must be carried out by suitably skilled and
competent personell only.
Maintenance
It is on-the-less good practice to check ever six months the response of the
sensor.
Before starting any verification procedures all personnell responsible for
security should be informed and all alarm systems which might be connected to
the system should be switched off.
NOTE: If you need more information of this product, you can visit our web
site: www.notifier.it
NOTIFIER by Honeywell Via Grandi, 22 – 20097 SAN DONATO MILANESE (MI)
Tel.: +39 02 51897.1 – Fax: +39 02 5189730 – E-mail:
notifier.milano@notifier.it
Numero Assistenza Tecnica: 039-9301410
Documents / Resources
|
NOTIFIER TMP2-D-X-S-1-A CPR Heat Detector
TMP
[pdf] Instruction Manual
TMP2-D-X-S-1-A CPR Heat Detector TMP, TMP2-D-X-S-1-A, CPR Heat Detector TMP,
Heat Detector TMP, Detector TMP, TMP
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>