NOTIFIER M710E-CZ Single Input Module Instruction Manual
- June 8, 2024
- NOTIFIER
Table of Contents
NOTIFIER M710E-CZ Single Input Module
INSTALLATION INSTRUCTIONS – M710E-CZ CONVENTIONAL ZONE INTERFACE MODULE
This manual is intended as a quick reference installation guide. Please refer
to the control panel manufacturers installation manual for detailed system
information.
The M700 series of modules are a family of microprocessor controlled interface
devices permitting the monitoring and/or control of auxiliary devices. The
M710E-CZ provides an interface between a zone of System Sensor manufactured
conventional type fire detection devices and an intelligent signaling loop.
A single tri-cooler LED indicates the status of the module. In normal
conditions, the LED can be set by command from the control panel to blink
green when the module is polled. In the case of a fire alarm on the
conventional zone, the LED is switched on constant red by panel command. If a
fault is detected on the conventional zone or the zone supply voltage drops
below 18V, or a fault with the external power supply is signaled, the LED will
blink yellow if enabled on the control panel. When a short circuit is detected
on the loop to either side of the module, the LED is switched to show a
constant yellow light.
This module does not require maintenance.
DIMENSION
SPECIFICATIONS
Intelligent Loop
- Operating Voltage Range: see S00-7100
- LED Cutoff Voltage: 16.5VDC
- Max. Standby Current (µA @24 V and 25o C) External Supply
- Conventional Zone:
- No Communication: 120
- Max. Standby Current (mA @24 V and 25o C) Conventional Zone connected to Capacitive EOL only, Loop Powered Conventional Zone:
- No Communication: 1.3
- LED Current (Red) 1.3mA
- LED Current (Yellow): 4.5mA
- Isolator Features: see S00-7100
Conventional Zone
- Supply Voltage: 18 to 32 VDC (either from loop or external supply)
- Maximum Standby Load Current: 3mA for detectors
- Maximum Zone Load: 17.5mA (Limited internally)
- Maximum Conventional Line Resistance: 50 Ohm (both legs)
- End of Line Capacitor: 47μF non-polarised. M200E-EOL-C supplied
General
- Humidity: 5% to 95% relative humidity (non-condensing)
- Ingress protection: IP44 (Mounted in M200E-SMB)
- Maximum Wire Gauge: 2.5mm²
INSTALLATION
Note: These modules must only be connected to control panels using
compatible proprietary analogue addressable communication protocols for
monitoring and control.
M700 series modules can be mounted in several ways ( See Figure 1 ):
1:1 An M200E-SMB custom low profile surface-mounting box. The SMB Base is
affixed to mounting surface, and then the module and cover are screwed onto
the base using the two screws supplied. Box dimensions: 132mm(H) x 137mm(W) x
40mm(D)
1:2 The DIN bracket on top allows mounting onto standard 35mm x 7.5mm
“Top Hat” DIN rail inside a control panel or other suitable enclosure. Install
and remove as shown in Figure 1:2
Wiring to all series M700 modules is via plug in type terminals capable of
supporting conductors up to 2.5mm²
CAUTION
Disconnect loop power before installing modules or sensors.
The module address is selected by means of rotary decade address switches
(see
Figure 3). A screwdriver should be used to rotate the wheels to select
the desired address, either from the front or the top of the module.
Note: The number of addresses available will be dependent on panel
capability, check the panel documentation for information on this.
Short Circuit Isolators
All M700 series modules are provided with short circuit monitoring and
isolators on the intelligent loop. If required the isolators may be wired out
of the loop to facilitate the use of the modules on high current loaded loops,
for example if sounders are used. To achieve this, the loop out positive
should be wired to terminal 5 rather than terminal 2. See Figure 2 for
details.
CAUTION
Electrostatic Sensitive Device Observe precautions when handling and making
connections
M710E-CZ Wiring
The M710E-CZ can be wired so as to power the conventional zone either from an
external supply, or directly from the communications loop provided it can
supply sufficient current. When using an external power supply, the
conventional zone is fully isolated from the communications loop.
If the conventional zone is to be powered from the loop, it is necessary to
connect the communication line to the zone power supply terminals in addition
to the loop inputs.
Note that if a short circuit occurs on the communications loop on the side
powering the conventional zone, it will be reported as a conventional zone
loss of power supply fault to the control panel, via the non-isolated leg of
the loop.
Wire as follows (see Figure 2) :
a: T1 Loop Output -. b: T2 Loop Output +. c: T3 Loop Input -. d: T4 Loop
Input +
e: T5 Loop Output +. If short circuit isolation is not required, loop
output+ should be wired to terminal 5 and not 2. Terminal 5 is internally
connected to terminal 4.
f: If the conventional zone is to be powered from the communications
loop, then the loop should be connected both to the loop input (terminals 3
and 4) and to the conventional zone supply (terminals 6 and 7).
If an external power supply is to be used, it should be connected to the
conventional zone supply (Terminals 6 and 7), and the communications loop
input should be connected only to the loop input (Terminals 3 and 4).
g: Fault Monitor: The fault monitor is an external input, which is used
to monitor an external contact, for example an external power supply fault
such as mains failure.
The fault is signaled by switching the fault terminal to the external power
supply negative. Terminal 12 is internally connected to terminal 6.
h: Conventional Fire Detection Zone: The M710E-CZ can monitor most System
Sensor manufactured conventional detectors mounted in standard bases or 470
Ohm resistor bases.
The maximum recommended number of conventional devices used with each CZ
module is 20 (Series 300 and ECO1000 Series detectors).
i: Reset Output: This terminal may be used to monitor for the
conventional zone reset. It switches low during a zone reset.
CUSTOMER SUPPORT
DOP-IOD100
EN 54-17: 2005, EN 54-18: 2005
Notified by Honeywell
Pittway Technological S.r.l
Via Cabot 19/3
34147 Trieste, Italy