SILENT KNIGHT SK-2-E Fire Alarm Control Panel Instruction Manual
- June 9, 2024
- SILENT KNIGHT
Table of Contents
SILENT KNIGHT SK-2-E Fire Alarm Control Panel
Operating Instructions
WHEN AUDIBLE DEVICES ARE SOUNDING
To return to normal after an alarm
- Do not enter the protected area until safe to do so.
- Clear all initiating devices. Smoke detectors will not reset if there is still smoke in the area.
- Reset the control panel (PRESS the RESET key)
Power failure or brownout
If AC power drops too low or fails, the AC POWER LED will go out, the SYSTEM TROUBLE LED will turn on, the POWER TROUBLE LED will turn on and the panel buzzer and any other audible trouble devices will sound. Contact authorized service personnel immediately. See below.
Manual activation (Fire Drill or otherwise)
Notification Appliance Circuits (NACs) can be activated by activating a Manual Pull Station.
NOTE: You may want to disconnect municipal box by sliding DISCONNECT switch, located on SK-4XTM module, to its disconnect position (to the right). If a DACT is connected, notify the monitoring service before conducting any fire drills or tests.
Alarm Silencing
Notification Appliance Circuits may be silenced by pressing the ACKNOWLEDGE
key and then the ALARM SILENCE key. The ALARM SILENCE LED will turn on.
Subsequent alarms will reactivate circuits. Press the RESET key to clear the
“silenced” condition.
NOTE: Notification Appliance Circuits may be programmed as nonsilenceable.
Also, Signal Silence Inhibit, if enabled, will prevent silencing of NACs for
one minute after an alarm (see manual).
To test the lamps and piezo sounder
Press and release the RESET key and check all LEDs. Every LED should be on and
the piezo should sound.
For more information, refer to the SK-2/E & SK-4/E Manual, Document #52604. It
is kept in the following location:
THIS SHEET SHALL BE FRAMED ADJACENT TO THE CONTROL PANEL