Thread room sensor
QAA2890/WI, QFA2890/WI, QPA2892/WI
Thread room sensor
-
Wireless communication KNX IoT over Thread
-
Battery-powered:
QAA2890/WI, QFA2890/WI: 3 x alkaline batteries type AAA, 1.5 V QPA2892/WI: 2 x alkaline batteries type AA, 1.5 V -
Temperature accuracy: ±0.3 K@21…25 °C, ±0.7 K@15…21 °C/25…35 °C,±1 K@0…15 °C/35…50 °C
-
Relative humidity accuracy: ±2 % r.h.@30…70 % r.h.,
±5 % r.h.@0…30 % r.h./70…100 % r.h. -
CO2 accuracy: ±50 ppm / ±2 % m.v. @0…2000 ppm
-
Range of use: -15…+50 °C / 0…100 % r.h. (non-condensing) / 0…5000 ppm
Use
Sensors acquire the following values in ventilation and air conditioning plants:
- Temperature
- Relative humidity
- CO2 concentrations
Wireless communication KNX IoT over Thread exchanges sensor data with controllers, tools or the cloud over a wireless Thread network.
Functions
Relative humidity
The sensor acquires relative humidity via a digital capacitive relative
humidity sensor with bandgap temperature sensor.
The electronic measuring circuit converts the sensor element’s humidity signal
to a wireless digital signal (0…10000), corresponding to a relative humidity
range of 0…100 %.
Temperature
The sensor acquires the temperature via a digital humidity and temperature
sensor.
The temperature signal from sensing element is converted to wireless digital
signal (0…10000), corresponding to a temperature range of 0…50 °C.
CO2 concentration
The SymaroTM air quality sensor acquires the CO2 concentration by infrared
absorption measurement (NDIR).
The resulting wireless digital output signal (0…5000) is proportional to the
CO2 content of the ambient air, corresponding to a CO2 concentration range of
0…5000 ppm.
Mechanical design
Thread room sensors are designed for wall mounting, flush mounting and tape
mounting. They are suitable for use with most commercially available recessed
conduit boxes.
The device has 2 parts:
- Plastic housing with electronic components
- Mounting plate
Type summary
Product number| SSN NO.| Temperature measuring range| Humidity measuring range| CO 2
measuring range
| Operating voltage| Output signal
---|---|---|---|---|---|---
QAA2890/WI| S55720-S550| 0…50 ℃| —| —| DC 4.5 V (3 x
1.5 V AAA alkaline batteries)
| Wireless digital signal
QFA2890/WI| S55720-S551| 0…50 ℃| 0…100 %| —| DC 4.5 V (3 x
1.5 V AAA alkaline batteries)
| Wireless digital signal
QPA2892/WI| S55720-S552| 0…50 ℃| 0…100 %| 0…5000 ppm| DC 3 V (2 x
1.5 V AA alkaline batteries)
| Wireless digital signal
Delivery
When ordering, specify name and product number, e.g.: Thread room sensor
QFA2890/WI.
Inbox items
Name | Quantity |
---|---|
Sensor | 1 |
Mounting plate | 1 |
Set of screws and plastic insert | 1 |
Mounting instructions | 1 |
Batteries | QAA2890/WI, QFA2890/WI: 3 x 1.5 V AAA alkaline batteries |
QPA2892/WI: 2 x 1.5 V AA alkaline batteries
Tape| 1
Equipment combinations
Type of units | Product number | SSN NO. |
---|---|---|
KNX-IoT to BACnet gateway 1) | OCT200.KNBA | S55812-Y102 |
Thread mesh extender | OCT100.R | S55812-Y101 |
- Power adapter needs to be ordered separately.
All documents can be downloaded from http://siemens.com/bt/download.
Product documentation
Title | Document ID |
---|---|
Mounting instruction | A6V12816395 |
Quick start guide | A6V12905642 |
CE declarations | A5Wxxx |
RCM | A5Wxxx |
UKCA | A5Wxxx |
FCC | A5Wxxx |
Environmental product declaration | A5Wxxx |
Related documents such as environmental declarations, CE declarations, etc.,
can also be downloaded at the following Internet address:
www.siemens.com/bt/download
Notes
Safety
CAUTION
**| National safety regulations**
Failure to comply with national safety regulations may result in personal injury and property damage.
- Observe national provisions and comply with the appropriate safety regulations.
WARNING
| Explosion due to fire or short-circuit, even with discharged batteries
Risk of injury due to flying parts
- Prevent the batteries from coming in contact with water.
- Do not recharge batteries.
- Do not damage or disassemble batteries.
- Do not heat batteries over 85 °C.
WARNING
| Risk of explosion
Personal injury and property damage
- Install the battery at the correct polarity (+/-) using the illustration in the battery compartment.
- Install only the correct battery types according to the indication in the battery compartment.
- In case of a leakage, avoid contact with skin, eyes and mucous membranes.
- Remove leaking battery from the battery compartment with a cloth.
Observe the following:
- The batteries must be new and undamaged.
- Do not mix new and used batteries.
- Store, transport and dispose of the batteries in compliance with local requirements, regulations and laws and observe the instructions of the battery manufacturer.
NOTICE
❗
| Radio frequency energy
Interference to radio communications
- Install and use equipment in accordance with installation guide.
- Read all regulatory compliance information.
Mounting
Location
- The device is designed for wall mounting, flush mounting and tape mounting.
- Inside wall (not an outside wall!) of the room; not in recesses, behind curtains, above or close to heat sources or shelves and not on walls where a chimney is located. Do not expose the unit to spot lights or direct sunlight.
- Install the sensor in the occupied space about 1.5 m above the floor and at least 20 cm from the next wall.
- Seal the end of the conduit at the sensor to prevent false measurements caused by draughts through the conduit.
Mounting instructions
Mounting instructions are enclosed in the package.
Chemical vapors
The humidity sensor is a sensitive measuring device and must be handled
with care. Chemical vapors at high concentration in combination with long
exposure times may distort the sensor reading.
NOTICE
❗
| Avoid direct contact with chemicals in any form. Do not touch sensitive components with bare hands or tools as this will negatively impact measurement accuracy.
Colors and patterns
LED
In the following table:
- Short press (<2 s) means short press the push button
- Long press (>20 s) means long press the push button.
LED color| Device status| LED pattern| Push button
operation
---|---|---|---
Off| Unpowered device / powered device without display| Off| N/A
Green| Start up (e.g. battery installation)| Fast flashing (100 ms on / 100 ms
off) for 3 s| N/A
Normal (connected)| On for 8 s| Short press to activate LED
Joining| Flashing 1 (¹/₄ s on / ⁷/₄ s off) during joining and is timeout after
120 s| Short press to activate LED, then short press within 8 s to join 1)
Orange| Initial state (no connection)| On for 8 s| Short press to activate LED
Factory reset| Fast flashing (100 ms on / 100 ms off) for 8 s| Long press to
start factory reset
Red| Connection lost 4)| Flashing 1 (¹/₄ s on / ⁷/₄ s off) for 8 s| Short
press to activate LED
Low battery / Hardware error| Fast flashing (100 ms on / 100 ms off) for 8 s
Programming mode| Permanent on during programming mode and is timeout after 4
minutes.| Short press to activate LED, then short press within 8 s to enter
programming mode 2) 3)
SRP service registration failure| Fast flashing (100 ms on / 100 ms off) for 8
s| N/A
Off and green| Firmware update| Constant off during firmware downloading, fast
flashing (100 ms on / 100 ms off) during new firmware startup.| N/A
Notes
- Device is in initial state (no connection).
- Before entering programming mode, device needs connect to Thread network.
- Device can enter programming mode via gateway. For details, see Quick start guide.
- If device connection is lost (LED flashes red) and users want to join, they need factory reset the device firstly.
Maintenance
Change of batteries
Check battery power by short press of the push button to activate the LED.
The batteries are almost empty if LED is red and keeps fast flashing (100 ms
on / 100 ms off) for 8 s and must be replaced.
For optimal performance, we recommend using high performance alkaline
batteries.
Disposal
****This symbol or any other national label indicate that the product, its
packaging, and, where applicable, any batteries may not be disposed of as
domestic waste. Delete all personal data and dispose of the item(s) at
separate collection and recycling facilities in accordance with local and
national legislation.
For additional details, refer to
www.siemens.com/bt/disposal.
Regulatory compliance information
FCC Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation
FCC Caution: Changes or modifications not expressly approved by Siemens Switzerland Ltd. could void user authority to operate the equipment. United States representative https://new.siemens.com/us/en/products/buildingtechnologies/home.html
IC Statement
This device complies with Industry Canada license-exempt RSS standard(s).
Operation is subject to the following two conditions:
- This device may not cause interference, and
- This device must accept any interference, including interference that may cause undesired operation of the device.
Radiofrequency radiation exposure statement
This equipment complies with FCC and IC radiation exposure limits set forth
for an uncontrolled environment. This equipment should be installed and
operated with a minimum distance of 20 cm between the radiator and your body.
This transmitter must not be co-located or operated in conjunction with any
other antenna or transmitter.
United Kingdom conformity assessed
Contact for regulatory topics: (GB) Siemens plc, Sir William Siemens House,
Princess Road, Manchester, M20 2UR
Radio equipment directive
Simplified EU Declaration of Conformity
Hereby, Siemens Switzerland Ltd declares that the radio equipment type
QAA2890/WI, QFA2890/WI and QPA2892/WI are in compliance with Directive
2014/53/EU. The full text of the EU declaration of conformity is available at
the following internet address:
https://siemens.com/bt/download.
IMDA standards
The device complies with IMDA standards.
Warranty
Technical data on specific applications are valid only together with Siemens products listed under “Equipment combinations”. Siemens rejects any and all warranties in the event that third-party products are used.
Technical data
Power supply
Operating voltage QAA2890/WI, QFA2890/WI QPA2892/WI| ****
DC 4.5 V (3 x 1.5 V AAA alkaline batteries) DC 3 V (2 x 1.5 V AA alkaline batteries)
Battery life QAA2890/WI
QFA2890/WI QPA2892/WI| ****
10 years (10 minutes transmission rate with COV on)
10 years (10 minutes transmission rate with COV on)
9 years (10 minutes transmission rate with COV on and CO2 indicator off)
Power consumption QAA2890/WI, QFA2890/WI QPA2892/WI| Max. 20 mA
Max. 250 mA
Radio communication
Frequency range| 2400…2483.5 MHz
Maximum transmission power| 7.73 dBm
Range| ≤ 10 m, depending on application and
building
Protocol| Open Thread
MAC protocol| IEEE 802.15.4
Zigbee channels| 11…26
Functional data of sensor
Humidity sensor
Range of use| 0…100 % r.h. (non-condensing)
Measuring range| 0…100 % r.h.
Measuring accuracy at 30…70 % r.h.
0…30 % r.h./70…100 % r.h.
| ****
±2 % r.h.
±5 % r.h.
Time constant t63| 20 s
Output signal| Wireless digital signal (0…10000)
Temperature sensor
Range of use| -15…+50 °C
Measuring range| 0…50 °C
Measuring accuracy at
21…25 °C
15…21 °C/25…35 °C,
0…15 °C/35…50 °C
| ****
±0.3 K
±0.7 K
±1 K
Time constant t63| ≤ 8.5 min (depending on air movement and
thermal coupling to the wall)
Output signal| Wireless digital signal (0…10000)
CO 2 sensor
Range of use| 0…5000 ppm
Measuring range| 0…5000 ppm
Measuring accuracy at 0…2000 ppm| ****
±50 ppm / ±2 % m.v.
Time constant t63| 5 min
Output signal| Wireless digital signal (0…10000)
Ambient conditions and protection classification
Protection degree of housing| IP30 according to EN60529
Protection class| III according to EN60730
Environmental conditions
Storage
Climatic conditions Temperature Humidity
Mechanical conditions Transport
Climatic conditions Temperature Humidity
Mechanical conditions Operation
Climatic conditions
Temperature (housing with electronics) QAA2890/WI & QFA2890/WI QPA2892/WI
Humidity
Mechanical conditions
| ****
-15…+50 °C
0…95 % r. h. (non-condensing) Class 1M2
-25…+70 °C
<95 % r.h.
Class 2M2
-15…+50 °C
0…50 °C
0…95 % r. h. (non-condensing) Class 3M2
Standards, directives and approvals
Product standard| EN 60730-1
EN 301489-1
EN 301489-17
EN IEC 62311
EN 300328
Electromagnetic compatibility (Applications)| For use in residential,
commerce, light- industrial and industrial environments
EU conformity (CE)| xx )
RCM conformity| xx )
UKCA conformity| xx )
FCC| xx )
Standards, directives and approvals
UL| UL 60730, http://ul.com/database
RoHS| Directive 2011/65/EU restriction of the use of certain hazardous
substances in electronic equipment
Environmental compatibility| The product environmental declaration (xxx *)
contains data on environmentally compatible product design and assessments
(RoHS compliance, materials composition, packaging, environmental benefit,
disposal).
General
Materials and colors| Makrolon 6485, RAL9003
Sensor (complete assembly)| Silicone
Packaging| Corrugated cardboard
Weight including package QAA2890/WI QFA2890/WI QPA2892/WI| Approx. 204.6 g
Approx. 204.6 g
Approx. 226.3 g
*) The documents can be downloaded from http://siemens.com/bt/download.
Dimensions
Dimensions in mm
Type | D |
---|---|
QAA2890/WI, QFA2890/WI | 14 |
QPA2892/WI | 18 |
Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies
© Siemens Switzerland Ltd, 2022
Technical specifications and availability subject to change without notice.
References
- Smart Information Delivery
- Product Sourcing and Certifications Database | UL Solutions
- SIOS
- Building technology - Siemens Global
- Building Technologies - Siemens USA
- Smart Information Delivery
- Smart Information Delivery
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>