SALUS VS35B Wired Thermostat with Digital Display Installation Guide
- June 6, 2024
- SALUS
Table of Contents
- SALUS VS35B Wired Thermostat with Digital Display Installation
- Introduction
- Button Functions
- LCD Icon description
- Installation
- Wiring diagrams
- Temperature setting
- NSB function – automatic mode
- Changing the HEATING / COOLING mode
- Offset function (temperature calibration)
- Installer settings
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
SALUS VS35B Wired Thermostat with Digital Display Installation
www.salus-controls.eu
SALUS Controls is a member of the Computime Group
Maintaining a policy of continuous product development SALUS Controls plc
reserve the right to change specification, design and materials of products
listed in this brochure without prior notice.
Introduction
The VS35 thermostat controls temperatures of individual heating zone in
underfloor heating systems. Thermostat allows for significant savings thanks
to the possibility of maximum reduction the set temperature.
The full version of the manual in PDF format is available on the website www
.salus-controls.eu
This product complies with the following EU Directives: Electromagnetic Compatibility 2014/30/EU, Low Voltage Directive 2014/35/EU and RoHS 2011/65/EU. Full information is available on the website www.saluslegal.com
Safety Information
Use in accordance with national and EU regulations. Use the device only as
intended, keeping it in a dry condition. The product is for indoor use only.
Installation must be carried out by a qualified person in accordance with
national and EU regulations.
Terminals description
Proper thermostat placement
Button Functions
LCD Icon description
- Current active mode
- Comfort mode
- Standard mode
- Economic mode
- Automatic mode
- Frost protection mode
- Temperature unit
- Manual mode / temp. override
- Current / set temperature
- Key lock
- Settings
- Additional temperature sensor
- Cooling
- Heating
Installation
The VS35 thermostat has been designed for flush mounting in a standard electrical box with a diameter of 60 mm.
Note: Use the rear plate of the VS35 thermostat only with this model.
Wiring diagrams
An additional temperature sensor T is optional.
VS35 thermostat in connection with wiring centre
In this diagram, the VS30 thermostat manages the NSB function, more details
about NSB function can be found on the next page.
Note: In the KL06 wiring centre, the SL terminal is marked with an arrow icon
NSB function and an additional temperature sensor is optional.
VS35 thermostat in connection with actuator or pump
Temperature setting
Press any button to highlight the screen, then follow the steps below:
Manual mode – temperature settings
There are 4 temperature levels available. In manual mode only one temperature level is active (icon in the frame indicates which mode is currently choosen). For each temperature levels you can set a different temperature.
Press any button to highlight the screen, then follow the steps below:
NSB function – automatic mode
The NSB (Night SetBack) function can automatically change temperatures on VS35
daily thermostats via VS30 programmable thermostat connected to a wiring
centre (or another external clock). NSB function switches between comfortable
temperature and economic temperature .
To activate the automatic mode, select the icon. On display together with the
icon, the controller indicates active temperature mode: or .Press any button
to highlight the screen, then follow the steps below:
Press any button to highlight the screen, then follow the steps below: Note: For the NSB function to work, it is necessary to connect the wirings properly. Connection diagrams can be found on the previous page.
Changing the HEATING / COOLING mode
Press any button to highlight the screen, then follow the steps below: Note: Heating / cooling mode can also be set using the service parameter d18.
Offset function (temperature calibration)
The VS35 thermostat allows you to adjust the displayed temperature ± 3.0°C.
You can do it according to the following steps:
Press any button to highlight the screen, then follow the steps below: Note: You can also set the Offset temperature value using the service parameter d02.
Installer settings
Press any button to highlight the screen, then follow the steps below: Note: To restore the thermostat’s factory settings, in step 2 set the PSuu to 47 code, and confirm the selection with the button.
dxx | Function | Value | Description | Default value |
---|
d01
|
Control method temperature
| 0| PWM algorithm|
0
1| Span ±0.5°C
2| Span ±1.0°C
d02
|
Offset temperature
|
from -3.0°C to +3.0°C
| If the thermostat indica- tes wrong temperature, you can correct
it by ± 3.0°C
|
0°C
d03
| Using a floor temperature sensor (S1, S2)| 0| No sensor|
0
1| Sensor is connected
d04
| External sensor used for air
or floor temperature measurement (Function is active , when d 03=1)
|
0
| Thermostat measures the temperature only on the external sensor|
0
1
| The sensor is used as a protection against overheating the floor
d05
| Cooling mode control method| 1| Span ±0.5°C|
2
2| Span ±1.0°C
d06
| Type of thermoelectric actuator| 0| NO – normally open|
1
1| NC – normally closed
d07
|
Valve protection
| 0| OFF|
1
1| ON
d08| Frost protection temperature| 5-17°C| Frost protection / Holiday mode
temperature| 5°C
d12
|
Heating temperature limit
|
5-35°C
| The maximum heating temperature that can be set by the user|
35°C
d13
|
Cooling temperature limit
|
5-40°C
| The minimum cooling temperature that can be set by the user|
5°C
d14
|
Maximum floor temperature
(this function is active in heating mode when d04 = 1 )
|
6-45°C
| In order to protect the floor from overheating, heating will be turned OFF, when the maximum temperature of the floor sensor will be reached|
27°C
d15
|
Minimum floor temperature
(this function is active in heating mode when d04 = 1 )
|
6-45°C
| In order to protect the floor, heating will be turned ON, when the minimum temperature of the floor sensor will
be reached
|
10°C
d16
|
Lower floor temperature limit for cooling
(this function is active when d04 = 1 )
|
6-45°C
| In order to protect the floor, cooling will
be turned OFF, when the minimum temperatu-
re will be reached
|
6°C
d18
| Operating mode HEATING / COOLING| 0| Heating system|
0
1| Cooling system
Error code | Description |
---|---|
Err02 | The maximum / minimum floor temperature has been exceeded |
Err03 | Temperature sensor is faulty |
Err04 | Temperature sensor is shorted |