CERBERUS PYROTRONICS ASC-1 MXLV Amplifier Supervisory Cards Instructions
- June 9, 2024
- CERBERUS PYROTRONICS
Table of Contents
CERBERUS PYROTRONICS ASC-1 MXLV Amplifier Supervisory Cards
FEATURES
- Amplifier Input And Output Supervision
- Variable Backup Amplifier Ratio
- Automatic Transfer To Backup Amplifier
- Plugs Into OMM-1 Cardcage
- UL Listed, ULC Listed, CSFM, NYMEA, City Of Chicago
Description
ASC-1
The ASC-1 is an MXLV card which plugs into one slot of the OMM-1 cardcage. It
supervises the output of up to three primary and optionally, one backup
amplifier. The amplifiers may be on the same or different audio channels. One
ASC-1 is required for each 3 primary amplifiers, even if no backup amplifiers
are being used. The ASC-1 monitors and compares the channel riser output on
the OMM-1 to the amplifier output. If it determines that the output of any
primary amplifier is incorrect, it will automatically transfer operation to
the backup amplifier. The backup amplifier may be shared by multiple ASC-1
cards providing the ability to determine the primary to backup ratio. If
desired, backup amplification can be provided on a one for one basis, using
one ASC-1 for each primary/backup amplifier set. Each ASC-1 occupies one OCC-1
sub-address. The address is set using an on-board DIP switch. A second DIP
switch is provided for configuration of the ASC-1. Connections between the
amplifiers, audio riser busses and the ASC-1 are made through the appropriate
OMM- 1 screw terminals. This equipment is approved for operation over the
temperature range of 0°C to 49°C.
ASC-2
The ASC-2 is an MXLV card which plugs into one slot of the OMM-1 cardcage. It
supervises the output of one primary and optionally, one backup amplifier. One
ASC-2 is required for each primary amplifier, whenever a high power audio
riser is to be connected to ICP Control modules, even if no backup amplifiers
are being used. The ASC-2 monitors and compares the channel riser output on
the OMM-1 to the amplifier output. If it determines that the output of any
primary amplifier is incorrect, it will automatically transfer operation to
the backup amplifier. The backup amplifier may be shared by multiple ASC-2
cards providing the ability to determine the primary to backup ratio. If
desired, backup amplification can be provided on a one for one basis, using
one ASC-2 for each primary/backup amplifier set. Each ASC-2 occupies one OCC-1
sub-address. The address is set using an on-board DIP switch. A second DIP
switch is provided for audio configuration of the ASC-2. Connections between
the amplifiers, audio riser busses and the ASC-2 are made through the
appropriate OMM- 1 screw terminals. This equipment is approved for operation
over the temperature range of 0°C to 49°C
Engineer and Architect Specifications
ASC-1
Supervision of primary and backup amplifiers shall be provided by a
configurable plug-in module, model ASC- 1. The card shall plug into one slot
in on the OMM-1 MXLV cardcage. Multiple ASC-1s may be used to supervise
additional amplifiers, both primary and backup, as necessary. Through the use
of the ASC-1, backup amplification shall be provided on either a one for one
or one for multiple basis. Backup amplifiers shall be capable of supporting
primary amplifiers in any of 3 channels. The amplifier supervisory card shall
monitor the input and output of each amplifier and check for proper audio
level. If a primary amplifier output is found to be defective, the supervisory
card shall annunciate a system fault condition and transfer operation to the
backup amplifier if supplied. The backup amplifier shall replace the first
failed primary amplifier. The ASC-1 card edge fingers shall be gold plated for
highest reliability. The module shall be provided with a key which when
inserted into the OMM-1 card slot will prevent any other type of module from
being inadvertently plugged into that slot. The ASC-1 shall occupy one of the
OCC-1 module subaddresses. This address shall be set using an on-board DIP
switch. A second dip switch shall be provided to configure the ASC-1
operation.
ASC-2
Supervision of primary and backup amplifiers shall be provided by a
configurable plug-in module, model ASC- 2. The card shall plug into one slot
in on the OMM-1 MXLV cardcage. It shall be capable of supervising one primary
and optionally, one backup amplifier. The ASC- 2 shall be used to supervise
high power audio risers when ICP remote control modules are controlling audio
zones. Multiple ASC-2’s may be used to supervise additional amplifiers, both
primary and backup, as necessary. Through the use of the ASC-2, backup
amplification shall be provided on either a one for one or one for multiple
basis. The amplifier supervisory card shall monitor the input and output of
each amplifier and check for proper audio level. If a primary amplifier output
is found to be defective, the supervisory card shall annunciate a system fault
condition and transfer operation to the backup amplifier if supplied. It shall
also initiate a system trouble condition regardless of whether or not a backup
amplifier is supplied. The ASC-2 card edge fingers shall be gold plated for
highest reliability. The module shall be provided with a key which when
inserted into the OMM-1 card slot will prevent any other type of module from
being inadvertently plugged into that slot. The ASC-2 shall occupy one of the
OCC-1 module subaddresses. This address shall be set using an on-board DIP
switch. A second dip switch shall be provided to configure the ASC-2
operation.
Electrical Ratings
ASC-1
- High Level Outputs : 25V RMS, 7.2A, 70.7V RMS 2.4A
- Backup Amp Input : 1V RMS
ASC-2
- High Level Outputs : 25V RMS, 7.2A, 70.7V RMS 2.4A
- Backup Amp Input : 1V RMS
Ordering Information
Model | Description | Part No. |
---|---|---|
ASC-1 | Amp Supervisory Card | 500-891187 |
Installation Instructions | 315-091263 | |
ASC-2 | Amp Supervisory Card | 500-892084 |
Installation Instructions | 315-092085 |
SPEAKER ZONE DECIBEL LOSS (25VRMS
| Gauge
---|---
Length| 14 AWG| 16 AWG| 18 AWG
(feet)| (Loss in decibels)
200
400
| 0.2
0.5
| 0.3
0.7
| 0.6
1.1
600| 0.7| 1.1| 1.6
800
1000
| 0.9
1.2
| 1.5
1.8
| 2.2
2.7
SPEAKER ZONE DECIBEL LOSS (70VRMS)
| Gauge
---|---
Length| 16 AWG| 18 AWG
(feet)| (loss in decibels)
200| 0.04| 0.06
400| 0.07| 0.11
600| 0.11| 0.17
800| 0.14| 0.22
NOTICE : The use of other than Cerberus Pyrotronics detectors and bases with Cerberus Pyrotronics equipment will be considered a misapplication of Cerberus Pyrotronics equipment and as such voids all warranties either expressed or implied in regard to loss, damage, liabilities and/or service problems
Cerberus Pyrotronics 8 Ridgedale Ave. Cedar Knolls, NJ 07927
- Tel : 201-267-1300
- FAX : 201-397-7008
10/95 10M CPY-IG Printed in U.S.A.