CMS Electracom M3.1 Couplers Installation Guide

October 29, 2023
CMS Electracom

CMS Electracom M3.1 Couplers Installation Guide
CMS Electracom M3.1 Couplers

Installation couplers:

  • Are to be fully engaged; with no significant gap, and the retaining clip latched as shown –
    Instruction

  • Are to be engaged and dis-engaged without load only.

  • Are not suitable for readily accessible areas.

  • Are not to be considered as a replacement for the plug and socket outletsystems complying with AS/NZS 3112, AS/NZS 3123 and AS/NZS 61535.1

  • Are not to be placed under excessive strain; in case of doubt, fix cable and couplers.

  • Are to be placed to distribute the load between outlets as evenly as possible ensuring that the sum of all loads does not overload the input coupler and cable.

  • Dangerous compatability between different coupler systems is not automatically prevented by the couplers compliance with AS/NZS 61535.1

  • Are to be installed, connected and tested in accordance with AS/NZS 3000 (Australian/New Zealand Wiring Rules & Regulations).

  • Do not penetrate housings or lead as these contain live parts

Are to be fully engaged; with no significant gap, and the retaining clip latched as shown –

Instruction

Are to be engaged and dis-engaged without load only.

  • Are not suitable for readily accessible areas.

  • Are not to be considered as a replacement for the plug and socket outletsystems complying with AS/NZS 3112, AS/NZS 3123 and AS/NZS 61535.1

  • Are not to be placed under excessive strain; in case of doubt, fix cable and couplers.

  • Are to be placed to distribute the load between outlets as evenly as possible ensuring that the sum of all loads does not overload the input
    coupler and cable.

  • Dangerous compatability between different coupler systems is not automatically prevented by the couplers compliance with AS/NZS 61535.1

  • Are to be installed, connected and tested in accordance with AS/NZS 3000 (Australian/New Zealand Wiring Rules & Regulations).

  • Do not penetrate housings or cable as these contain live parts

WIRING DIAGRAM

WIRING DIAGRAM

DO NOT INSERT TEST PROBES LARGER THAN 0.8MM WIDE AS IT WILL DAMAGE THE CONTACTS

Test plugs are supplied with the starter sockets. Additional test plugs are availble free of charge, by contacting our sales team.
Australia : 1300 159 159 New Zealand: 09 582 0776
www.cmselectra.co