APC BN1050M Back UPS Pro User Manual

June 9, 2024
APC

APC-logo

APC BN1050M Back UPS Pro

APC-BN1050M-Back-UPS-Pro-product

Important Safety Instructions

SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation and maintenance of the UPS and batteries.

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. The following special messages may appear throughout this bulletin or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

  • The addition of this symbol either to a “Danger” or “Warning” safety label indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.

  • This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

  • DANGER
    DANGER indicates a hazardous situation that, if not avoided, will result in death or serious injury.

  • WARNING
    WARNING indicates a hazardous situation that, if not avoided, could result in death or serious injury.

  • CAUTION
    CAUTION indicates a hazardous situation that, if not avoided, could result in minor or moderate injury.

  • NOTICE
    NOTICE is used to address practices not related to physical injury.

Product Handling Guidelines

APC-BN1050M-Back-UPS-Pro-fig- \(1\)

Safety and General Information
Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

  • This UPS is for indoor use only.

  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or high humidity.

  • Do not operate the UPS near open windows or doors.

  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
    NOTE: Allow a minimum of 20 cm clearance on both front and rear sides of the UPS.

  • Environmental factors impact battery life. Elevated ambient temperatures, poor quality utility power leading to frequent discharges will shorten battery life. Follow the battery manufacturer’s recommendations.

  • Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.

  • The UPS cord shall be connected to an earthed mains socket outlet for safety reasons.

Battery Safety

CAUTION
RISK OF HYDROGEN SULPHIDE GAS AND EXCESSIVE SMOKE

  • Replace the battery at least every 5 years or at the end of its service life, whichever is earlier.
  • Replace the battery immediately when the UPS indicates battery replacement is necessary.
  • Replace batteries with the same number and type of batteries as originally installed in the equipment.
  • Replace the battery immediately when the UPS indicates a battery over-temperature condition, or when there is evidence of electrolyte leakage. Power off the UPS, unplug it from the AC input, and disconnect the batteries. Do not operate the UPS until the batteries have been replaced.

Failure to follow these instructions can result in minor or moderate injury and equipment damage.

  • Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions. Keep unauthorized personnel away from batteries.
  • APC by Schneider Electric uses Sealed Maintenance-Free Lead Acid batteries. Under normal use and handling, there is no contact with the internal components of the batteries. Overcharging, overheating or another misuse of batteries can result in leakage of battery electrolytes. Released electrolyte is toxic and may be harmful to the skin and eyes.
  • CAUTION: Do not dispose of batteries in a fire. The batteries may explode.
  • CAUTION: Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
  • CAUTION: Before installing or replacing the batteries, remove conductive jewelry such as chains, wristwatches, and rings. High energy through conductive materials could cause severe burns.
  • CAUTION: Failed batteries can reach temperatures that exceed the burn thresholds for touchable surfaces.
  • CAUTION: A battery can present a risk of electrical shock and high short-circuit current. The following precautions should be observed when working on batteries:
    • Disconnect the charging source prior to connecting or disconnecting battery terminals.
    • Do not wear any metal objects including watches and rings.
    • Do not lay tools or metal parts on top of batteries.
    • Use tools with insulated handles.
    • Wear rubber gloves and boots.
    • Determine if the battery is either intentionally or inadvertently grounded. Contact with any part of a grounded battery can result in electric shock and burns by high short-circuit current. The risk of such hazards can be reduced if grounds are removed during installation and maintenance by a skilled person.

Inventory

Connect the Battery

The UPS is shipped with the battery disconnected.APC-BN1050M-Back-UPS-Pro-
fig- \(3\)

PowerChute Personal Edition Software

Use PowerChute Personal Edition software to configure the UPS settings. During a power outage, PowerChute will save any open files on your computer and shut it down. When power is restored, it will restart the computer.

Note:
PowerChute is only compatible with a Windows operating system. If you are using Mac OSX, use the native shutdown feature to protect your system. See the documentation provided with your computer.

Installation
  1. Use the cable supplied with the Back-UPS to connect the data port on the Back-UPS to the USB port on your computer.
  2. On the computer, go to www.apc.com.
  3. Search for “PowerChute Personal Edition” then click on “View Details” to download the latest version of PCPE software.
  4. Click the download link and select Software product.
  5. Select the appropriate operating system.
  6. Follow the directions to download the software.

Connect the Equipment

Battery Backup and Surge Protected outlets
When the Back-UPS is receiving mains power, the Battery Backup with Surge Protection outlets will supply mains power to connected equipment. During a power outage or brown out or sags or surges, the Battery Backup outlets will supply battery power to the connected equipment for a limited time.

Connect equipment such as printers, fax machines, scanners, or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full-time protection from surges even if the Back-UPS is switched OFF.

1| USB and Serial Data port| To use PowerChute Personal Edition, connect the supplied USB cable or an optional serial cable (not supplied).
---|---|---
2| Building Wiring Fault indicator| If this indicator is illuminated, there is a problem with the wiring in the building. Contact an electrician immediately and do not use the Back-UPS.
3| Surge Protected outlets| These outlets provide full-time protection from surges, even if the Back-UPS is off. Connect equipment such as printers and scanners that do not require battery backup protection.
4| Battery Backup outlets with Surge Protection| During a power outage or brown out or sags or surges, the Battery Backup outlets receive power for a limited time from the Back-UPS. Connect essential equipment such as desktop computer, computer monitor, modem or other data sensitive devices into these outlets.
5| Circuit Breaker| Use to reset the system after an overload condition has occurred causing the circuit breaker to trip.

Operation

Power Saving Display
The display interface can be configured to be continuously illuminated or to save energy, it can be configured to darken after a period of inactivity.

  1. Full-Time Mode: Press and hold the DISPLAY button for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full-Time mode.
  2. Power Saving Mode: Press and hold the DISPLAY button for two seconds. The display illumination will turn off and the Back-UPS will beep to confirm the Power Saving mode. While in Power Saving Mode, the display will illuminate if a button is pressed and turns off after 60 seconds of inactivity.

Unit sensitivity
Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.

  1. Be sure that the Back-UPS is connected to mains power, but is turned OFF.
  2. Press and hold the POWER ON/OFF button for six seconds. The Load Capacity bar will flash on and off, indicating that the Back-UPS is in programming mode.
  3. Press the POWER ON/OFF button again to navigate through the menu options. Select the appropriate sensitivity. The Back-UPS will beep to confirm the selection.APC-BN1050M-Back-UPS-Pro-fig- \(5\)

Front Panel Buttons and Display Interface
Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.APC-BN1050M-Back-UPS-Pro-fig-
\(6\)

Alarms and System Errors

APC-BN1050M-Back-UPS-Pro-fig- \(7\) APC-BN1050M-
Back-UPS-Pro-fig- \(8\)

Audible Indicators
  • Four Beeps Every 30 Seconds Back-UPS is running on battery. You should consider saving any work in progress.
  • Continuous Beeping Low battery condition and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system.
  • Continuous tone Battery Backup outputs are overloaded.
  • It Chirps every 2 Seconds with the Load Capacity Bar flashing Battery is disconnected.
  • Continuous chirping with the Load Capacity Bar and Replace Battery icon alternately flashing Battery did not pass the automatic diagnostic test and should be replaced as early as possible. Pressing the MUTE button pauses the chirping.
Status Icons

APC-BN1050M-Back-UPS-Pro-fig- \(9\)

System Errors

The Back-UPS will display these error messages. Except for errors F01 and F02, contact SEIT Technical Support.APC-BN1050M-Back-UPS-Pro-fig-
\(10\)

Function Button Quick Reference

APC-BN1050M-Back-UPS-Pro-fig- \(11\)APC-BN1050M-
Back-UPS-Pro-fig- \(12\)

Troubleshooting

Problem and Possible Cause Corrective Action

Back-UPS will not switch on.
The Back-UPS is not connected to mains power.| Ensure that the Back-UPS is securely connected to an AC outlet.
The circuit breaker has been tripped.| Disconnect non-essential equipment from the Back-UPS. Reset the circuit breaker.

Re-connect equipment one item at a time. If the circuit breaker is tripped again, disconnect the device that caused the trip.

The internal battery is not connected.| Connect the battery.
The AC input voltage is out of range.| Adjust the transfer voltage and sensitivity range.
Back-UPS does not provide power during a power outages.
Ensure that essential equipment is not plugged into a Surge Only outlet.| Disconnect equipment from the Surge Only outlet and re-connect to a Battery Backup outlet.
Back-UPS is operating on battery power, while connected to mains power.
The plug has partially pulled out of the wall outlet, the wall outlet is no longer receiving mains power, or the circuit breaker has been tripped.| Be sure that the plug is fully inserted into the wall outlet. Be sure that the wall outlet is receiving main power by checking it with another device.
The Back-UPS is performing an automatic self-test.| No action is necessary.
The AC input voltage is out of range, the frequency is out of range, or the waveform is distorted.| Adjust the transfer voltage and sensitivity range.
Back-UPS does not provide the expected amount of backup time.
Battery Backup outlets may be fully or improperly loaded.| Disconnect non- essential equipment from the Battery Backup outlets and connect the equipment to surge outlets.
The battery was recently discharged due to a power outage and has not fully recharged.| Charge the battery cartridge for 16 hours.
The battery has reached the end of its useful life.| Replace the battery.
The Replace Battery indicator is illuminated.

The battery has reached the end of its useful life.| Replace the battery as early as possible.
The Overload indicator is illuminated.
The equipment connected to the Back-UPS is drawing more power than the Back- UPS can provide.| Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to surge outlets.
The System Error indicator is illuminated, and all the front panel indicators are flashing.
There is an internal error.| Determine which internal error message is displayed by matching the number displayed on the LCD with the corresponding Error Message (see “System Errors”) and contact SEIT Technical Support.

Specifications

Model BN1050M
VA 1050 VA
Maximum Load 600 W
Nominal Input Voltage 120 Vac
Online Input Voltage Range 88 – 139 Vac
Automatic Voltage Regulation (88-107) +11.2% (to compensate for low

input voltage)
Frequency Range Battery Type

On-battery Waveshape

| 60 Hz ± 1 Hz

Lead acid, 12V with 1 battery Step-approximated sine-wave

Typical Recharge Time Transfer Time

On Battery Runtime

| 12 hours

8 ms (typical), 10 ms (maximum) Go to: www.apc.com

Interface

Operating Temperature Storage Temperature

| USB

0 to 40 °C (32 to 104 °F)

-5 to 45 °C (23 to 113 °F)

Unit Dimensions

Unit Weight

| 19 x 9.1 x 31 cm (7.5 x 3.6 x 12.2 in)

7.2 kg (15.9 lbs)

Replacement Battery
The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement parts for Back-UPS is APCRBC158. Delaying the replacement of parts may corrode the batteries in the cartridge. Recycle spent battery cartridges.

Warranty

The standard warranty is three (3) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory-reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with a SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department or cross-ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

EMC Compliance

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and the receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

Select models are ENERGY STAR® qualified. For more information on your specific model visit APC by Schneider Electric’s website, www.apc.com. Select models are compliant with California (CEC) Battery Charger regulations. For more information on your specific model visit APC by Schneider Electric’s website, www.apc.com.

APC by Schneider Electric IT Customer Support Worldwide
For country-specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.

© 2022 APC by Schneider Electric. APC, the APC logo, Back-UPS, and PowerChute are owned by Schneider Electric Industries S.A.S. or their affiliated companies. All other trademarks are the property of their respective owners.

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

APC User Manuals

Related Manuals