POTTER VSR-S Series Waterflow Alarm Switch for Small Pipe Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
VSR-S
VSR-S Series Waterflow Alarm Switch for Small Pipe
Owner’s Manual
Features
- Assembled in USA
- 0-90 second field replaceable time delay retard
- Easy to read retard time delay adjustment knob
- Fits 1” to 2” CPVC, copper, brass, or iron pipe
- Comes with all necessary paddles
- Two SPDT (form C) contacts
- Weatherproof
- Easy to read wire terminal designations
- 5 year warranty
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall not be
used as the sole initiating device to discharge AFFF, deluge, or chemical
suppression systems. Waterflow switches used for this application may result
in unintended discharges caused by surges, trapped air, or short retard times.
Important: This document contains important information on the
installation and operation of the VSR-S waterflow switches. Please read all
instructions carefully before beginning installation. A copy of this document
is required by NFPA 72 to be maintained on site.
Description
The Model VSR-S is a vane type waterflow switch for use on wet sprinkler
systems that use 1” (25mm), 1¼” (32mm), 1½” (38mm) or 2” (50mm) pipe size. The
unit may also be used as a sectional waterflow detector on large systems.
The unit contains two single pole double throw snap action switches and an
adjustable, instantly recycling pneumatic retard. The switches are actuated
when a flow of 10 gallons per minute (38 LPM) or more occurs downstream of the
device. The flow condition must exist for a period of time necessary to
overcome the selected retard period.
Enclosure
The VSR-S switches and retard device are enclosed in a general purpose, die-
cast housing. The cover is held in place with two tamper resistant screws
which require a special key for removal. A field installable cover tamper
switch is available as an option which may be used to indicate unauthorized
removal of the cover. See bulletin number 5401103 for installation
instructions of this switch.
WARNING
-
Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances.
-
Shock hazard. Disconnect power source before servicing.
Serious injury or death could result. -
Risk of explosion. Not for use in hazardous locations. Serious injury or death could result.
Technical Specifications
Service Pressure | 300 PSI (20,68 BAR) – UL |
---|---|
How Requinx1 for Alarm | 10 GPM (38 LPM) |
To ensure minimum flow of 10 gpm, a minimum pressure is required at all
sprinklers with a k-factor of 3 or less.
K-3: 10 PSI K-2.8: 12 PSI
Maximum Surge| 18 FPS (5,5 m/s)
Enclosure| Die-cast, red powdercoat finish
Contact Ratings| Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at
30 VDC Resistive 10 mAmps min. at 24VDC
Conduit Entrances| Two 1/2″ conduit connections provided. Individual switch
compartments suitable for dissimilar voltages.
Usage| Listed plastic, copper, schedule 40 iron pipe and unlisted riser
assemblies approved by Potter .
Fits pipe sizes – 1″, 11/4″, 1’/i” and 2″
Note: 12 paddles are furnished with each unit, one for each pipe size of
threaded and sweat TEE, one for I” CPVC, one for I” CPVC (Central), one for I”
threaded Nibco CPVC, and one for 11/2″ threaded (Japan).
Environmental Specifications| • NEM A 4/IP65 Rated Enclosure suitable for
indoor or
outdoor use with factory installed gasket and die-cast housing when used with
appropriate conduit fitting.
• Temperature Range: 40°F -120°F, (4.5°C – 49°C) – UL
Service Use| Automatic Sprinkler NFPA-13 One or two family dwelling NFPA- I 3D
Residential occupancy up to four stories NFPA-I 3R National Fire Alarm Code
NFPA-72
*Specifications subject to change without notice.
Installation
These devices may be mounted in horizontal or vertical pipe. On horizontal
pipe they should be installed on the top side of the pipe where they will be
accessible. The units should not be installed within 6” (15cm) of a fitting
which changes the direction of the waterflow or within 24” of a valve or
drain. Select the proper paddle for the pipe size and type of TEE used see
Fig. 2 for instructions on changing paddle. The unit has a 1” NPT bushing for
threading into a TEE. See Fig. 1 for proper TEE size, type and installation.
Use no more than three wraps of teflon tape.
Screw the device into the TEE fitting as shown in Fig. 1. Care must be taken
to properly orient the device for the direction of waterflow.
The vane must not rub the inside of the TEE or bind in any way. The stem
should move freely when operated by hand.
The device can also be used in copper or plastic pipe installations with the
proper adapters so that the specified TEE fitting may be installed on the pipe
run.
Note: Do not leave cover off for an extended period of time.
WARNING
Do not trim the paddle. Failure to follow these instructions may prevent the
device from operating and will void the warranty. Do not obstruct or otherwise
prevent the trip stem of the flow switch from moving when water flows as this
could damage the flow switch and prevent an alarm. If an alarm is not desired,
a Flow switch Bypass Switch should be used (refer to Potter data sheet
5401554), or a qualified technician should disable the alarm system.
Retard Adjustment
The delay can be adjusted by rotating the retard adjustment knob from 0 to the
max setting (60-90 seconds). The time delay should be set at the minimum
required to prevent false alarms.
Paddle Selection
WARNING
There are 12 paddles furnished with each unit. One for each size of threaded,
sweat or plastic TEE as described in Fig. 3. These paddles have raised
lettering that shows the pipe size and type of TEE that they are to be used
with. The proper paddle must be used. The paddle must be properly attached
(see drawing) and the screw that holds the paddle must be securely tightened.
Do not trim the paddle.
Note: For National Fire Products risers, use paddle marked SWEAT for
corresponding size riser.
TEE Specifications
Screw the fitting into the TEE fitting as shown in Fig. 3.
The depth to the inside bottom of the TEE should have the following dimensions:
Approximate Depth Requirement
Tee Size| Threaded| Sweat| CPVC
1″ x 1″ x 1″| 2 1/16″| 1 3/4″| 2 7/16″
1 1/4″ x 1 1/4″ x 1″| 2 7/16″| 2 7/16″| N/A
1 1/2″ x 1 1/2″ x 1″| 2 11/16″| 2 1/4″| N/A
2″ x 2″ x 1″| 3 3/16″| 2 3/4″| N/A
NOTICE
Use only factory TEE’s with a 1” NPT bull. Threaded bushings, reducing
bushings, mechanical TEE’s and weld-o-lets are not allowed unless they comply
with the dimensions listed in the chart in Fig. 3 and have been factory
approved by Potter. Apply teflon tape to the 1” NPT fitting. Do not use more
than three wraps of teflon tape. Do not use any other type of sealant.
Cover Tamper Switch Wiring
Switch Terminal Connections Clamping Plate Terminal
WARNING
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
become dislodged from under the terminal. Failure to sever the wire may render
the device inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8” of length or expose an uninsulated conductor
beyond the edge of the terminal block. When using stranded wire, capture all
strands under the clamping plate.
Typical Electrical Connections
CAUTION
The VSR-S does not require power to operate. Do not connect AC power directly
to the terminals as this will damage the switch.
The terminals are for switching power to an indicating appliance such as a
bell or strobe. Similar to how a light switch is used to switch power to a
light. The terminals can also be used to connect to a fire/security panel.
Notes:
- The Model VSR-S has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator.
- For supervised circuits, see “Switch Terminal Connections Clamping Plate Terminal” drawing and warning note (Fig. 5).
Fig 7
Break out thin section of cover when wiring both switches from one conduit
entrance.
Testing
The frequency of inspection and testing for the Model VSR-S and its associated
protective monitoring system should be in accordance with applicable NFPA
Codes and Standards and/or the authority having jurisdiction (manufacturer
recommends quarterly or more frequently). If provided, the inspector’s test
valve shall always be used for test purposes. If there are no provisions for
testing the operation of the flow detection device on the system, application
of the VSR-S is not recommended or advisable.
A minimum flow of 10 GPM (38 LPM) is required to activate this device.
NOTICE
Please advise the person responsible for testing of the fire protection system
that this system must be tested in accordance with the testing instructions.
Do not obstruct or otherwise prevent the trip stem of the flow switch from
moving when water flows as this could damage the flow switch and prevent an
alarm. If an alarm is not desired, a Flow switch Bypass Switch should be used
(refer to Potter data sheet 5401554), or a qualified technician should disable
the alarm system.
Mounting Dimensions
Maintenance
Inspect detectors monthly for leaks. If leaks are found, replace the detector. The VSR-S waterflow switch should provide years of trouble-free service. The retard and switch assembly are easily field replaceable. In the unlikely event that either component does not perform properly, please order replacement retard switch assembly stock number 1029030. There is no maintenance required, only periodic testing and inspection. Vane type waterfowl switches have a normal service life of 10-15 years. However, the service life may be significantly reduced by local environmental conditions.
Vane-Type Waterflow Switch for Small Pipe Specification
UL, CUL Listed, LPCB Approved and CE Marked vane type waterflow switches shall
be furnished and installed at each sprinkler system connection to the wet pipe
main where indicated on the drawings and plans and as required by applicable
local and national codes and standards. The device shall consist of a 1” NPT
threaded brass bushing for installation into tees and approved manifolds,
gasket and non-corrosive vane and trip stem assembly as well as a field
replaceable adjustable time delay/switch mechanism to prevent false alarms
from water surges. All whetted parts of the waterflow switch shall be non-
corrosive to resist being affected by or contributing to corrosion. The
waterflow switch enclosures shall be NEMA 4 rated and the cover shall be held
captive by tamper resistant screws. It shall be possible to install an
optional cover tamper switch to detect removal of the enclosure. The field
replaceable instantly recycling adjustable pneumatic retard shall provide a
0-90 second time delay and visual indication of activation. Expiration of the
retard time shall result in the simultaneous operation of two sets of single
pole double throw (SPDT) switch contacts rated at 10A, 125VAC and 2A, 30 VDC.
Each switch contact shall have a separate wiring chamber and separate conduit
entrance to comply with the NEC requirements for separation of power limited
and non power limited conductors without the need for special wire or wire
methods. The device shall be listed for pressures up to 300 psi, maximum water
surges of 18 fps and alarm activation by a continuous flow of 10 gpm. The
device shall be Listed for installation on CPVC, brass, copper and iron tees
and manifolds from 1” – 2” size. The waterflow switch shall be a model VSR-S
manufactured by Potter Electric Signal Company LLC.
Retard/Switch Assembly Replacement
NOTICE
The Retard/Switch Assembly is field-replaceable without draining the system or
removing the waterflow switch from the pipe
- Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
- Disconnect the power source for local bell (if applicable).
- Identify and remove all wires from the waterflow switch.
- Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
- Remove the retard assembly by lifting it straight up over the trip stem.
- Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
- Re-install the (2) original mounting screws.
- Reconnect all wires. Perform a flow test and place the system back in service.
Removal of Waterflow Switch
- To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced.
- Turn off electrical power to the detector, then disconnect wiring.
- Use a wrench on the flats of the bushing. Turn the switch counterclockwise to disengage the pipe threads.
- Gently lift with your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector.
- Lift detector clear of pipe.
Ordering Information
Model | Description | Stock Number |
---|---|---|
VSR-S | VSR-S WATER FLOW INDICATOR | 1144440 |
Replaceable Components:
Retard/Switch Assembly, stock no. 1029030
Paddle Tree, stock no. 5559001
Paddle Retention Screw, stock no. 5490374
Optional Components:
Cover Tamper Switch, stock no. 0090148
FSBS – Flow switch Bypass Switch , stock no. 3001006
DG-B-R Surface Mount Double Gang Box – Red F/FSBS, stock no. 1000484
Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com
5401206 – REV H • 05/19
firealarmresources.com ****
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>