POTTER VSR-SG Waterflow Alarm Switch with Glue-in Union Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
FOR CPVC PIPE
VSR-SG VANE TYPE WATERFLOW ALARM SWITCH WITH RETARD AND GLUE-IN UNION
VSR-SG Waterflow Alarm Switch with Glue-in Union **
**
Specifications subject to change without notice.
stock number: 1144460
optional: Cover Tamper Switch Kit, stock no. 0090148 replaceable
Components: Retard/Switch Assembly, stock no. 1029030
CAUTION
Waterflow switches that are monitoring wet pipe sprinkler systems shall not
be used as the sole initiating switch to discharge AFFF, deluge, or chemical
suppression systems. Waterflow switches used for this application may result
in unintended discharges caused by surges, trapped air, or short retard times.
General Information
The Model VSR-SG is a vane type waterflow switch for use on wet sprinkler
systems using CPVC plastic fittings (manufactured by Tyco, Nibco, Victaulic,
Ipex, and Spears Manufacturing Company) that use 1”, 1 ¼”, 1 ½”, or 2” pipe
sizes. It is equipped with a union to accommodate installation in confined
spaces.
The VSR-SG contains two single pole, double throw, snap action switches and an
adjustable, instantly recycling pneumatic retard. The switches are actuated
when a flow of 10 GPM (38 LPM) or more occurs downstream of the switch. The
flow condition must exist for a period of time necessary to overcome the
selected retard perio d.
Enclosure
The VSR-SG switches and retard switch are enclosed in a general purpose,
die-cast housing. The cover is held in place with two tamper resistant screws
which require a special key for removal. A field installable cover tamper
switch is available as an option which may be used to indicate unauthorized
removal of the cover. See bulletin number 5401103 for installation
instructions of this switch.
Installation (see Fig. 1, 3, and 5)
These switches may be mounted on horizontal or vertical pipe. On horizontal
pipe they shall be installed on the top side of the pipe where they will be
accessible. The switch should not be installed within 6″ (15 cm) of a fitting
which changes the direction of the waterflow or
CAUTION
Do not trim the paddle. Failure to follow these instructions may prevent the switch from operating and will void the warranty.
UL, CUL and CSFM listed, CE Marked
Service Pressure: Up to 175 PSI (12,07 BAR)
Flow Sensitivity Range for Signal: 4-10 GPM (15-38 LPM) – UL
Maximum Surge: 18 FPS (5.5 m/s)
Contact Ratings: Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at
30VDC Resistive 10 mAmps min. at 24VDC
Conduit Entrances: Two openings provided for 1/2″ conduit. Individual switch
compartments suitable for dissimilar voltages.
Environmental Specifications:
- NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket and die-cast housing when used with appropriate conduit fitting.
- Temperature Range: 40°F – 120°F, (4.5°C – 49°C) – UL
service use:
British Standard | B59251 |
---|---|
Automatic Sprinkler | NFPA-13 |
One or two family dwelling | NFPA-13D |
Residential occupancy up to four stories | NFPA-13R |
National Fire Alarm Code | NFPA-72 |
WARNING
- Installation must be performed by qualified personnel and in accordance with all national and local codes and ordinances.
- Shock hazard. Disconnect power source before servicing. Serious injury or death could result.
- Risk of explosion. Not for use in hazardous locations. Serious injury or death could result.
within 24″ (60 cm) of a valve or drain. The unit has a 1″ male fitting for gluing into a CPVC plastic tee.
Note: Do not leave cover off for an extended period of time.
Loosen the union nut and separate the 1″ male fitting from the VSR-SG.
Glue the 1″ male fitting into the TEE following the TEE manufacturer’s
instructions for preparation and gluing of CPVC piping systems. (Note: The 1″
male fitting must bottom out on the stop of the TEE for proper operation of
the VSR-SG. See Fig. 1.) Wait 2 to 4 hours to allow the glue to dry before
attaching the VSR-SG to the 1″ male fitting. Select the proper paddle for the
pipe size and type of TEE used. See Fig. 3 for instructions on how to change
paddle. verify that the o-ring is properly positioned in its groove. Hand
tighten the nut on the union after orienting the switch in the appropriate
direction to detect waterflow as shown in Fig. 5 & Fig. 7.
The vane must not rub the inside of the TEE or bind in any way. The stem
should move freely when operated by hand.
CAUTION
Do not over-tighten the union nut, hand tighten only. Use of a wrench may damage the union nut.
Testing
The frequency of inspection and testing for the Model VSR-SG and its
associated protective monitoring system shall be in accordance with applicable
NFPA Codes and Standards and/or the authority having jurisdiction
(manufacturer recommends quarterly or more frequently).
A method of testing the VSR-SG must be provided. The valve used for testing
shall be easily reached and shall produce a minimum flow of 10 GPM to activate
the switch. The discharge orifice shall be equal to the smallest sprinkler
used in the system.
NOTICE
Advise the person responsible for testing of the fire protection system
that this system must be tested in accordance with the testing instructions.
Glue the 1″ male fitting into the TEE following the TEE manufacturer’s
instructions for preparation and gluing of CPVC piping systems. Wait 2 to 4
hours to allow the glue
to dry before attaching the VSR-SG to the 1″ male fitting.
Break out thin section of cover when wiring both switches from one conduit entrance.
Important:
11 paddles are furnished with each unit to accommodate the various sizes and
manufacturers of TEES. The paddles have raised lettering that show the pipe
size and the TEE manufacturer they are to be used with. The proper paddle must
be used. The paddle must be properly attached (see Fig. 3) and the screw that
holds the paddle must be securely tightened.
Notes:
- The Model VSR-SG has two switches, one can be used to operate a central station, proprietary or remote signaling unit, while the other contact is used to operate a local audible or visual annunciator.
- For supervised circuits, see “Switch Terminal Connections” drawing and warning note (Fig. 6).
Retard adjustment
The delay can be adjusted by rotating the retard adjustment knob from 0 to the
max setting (6090 seconds). The time delay should be setat the minimum
required to prevent false alarms.
Fig. 6 Switch Terminal Connections Clamping Plate Terminal
WARNING
An uninsulated section of a single conductor should not be looped around the
terminal and serve as two separate connections. The wire must be severed,
thereby providing supervision of the connection in the event that the wire
become dislodged from under the terminal. Failure to sever the wire may render
the device inoperable risking severe property damage and loss of life.
Do not strip wire beyond 3/8″ of length or expose an uninsulated conductor
beyond the edge of the terminal block. When using stranded wire, capture all
strands under the clamping plate.
Fig. 7 Mounting Dimensions-orientation
CAUTION
Flow switch must be properly orientated. Side of cover must be perpendicular with the pipe. Improper orientation could delay or prevent notification of waterflow.
Maintenance
Inspect the waterflow switch monthly. If leaks are found, replace the
waterflow switch. The VSR-SG waterflow switch should provide years of trouble-
free service. The retard and switch assembly are easily field replaceable. In
the unlikely event that either component does not perform properly, please
order replacement retard switch assembly stock #1029030 (see Fig. 9). There is
no maintenance required, only periodic testing and inspection.
Retard/switch assembly replacement (See Fig. 9)
NOTICE The Retard/Switch Assembly is field-replaceable without draining
the system or removing the waterflow switch from the pipe
- Make sure the fire alarm zone or circuit connected to the waterflow switch is bypassed or otherwise taken out of service.
- Disconnect the power source for local bell (if applicable).
- Identify and remove all wires from the waterflow switch.
- Remove the (2) mounting screws holding retard/switch assembly to the base. Do not remove the (2) retard housing screws.
- Remove the retard assembly by lifting it straight up over the tripstem.
- Install the new retard assembly. Make sure the locating pins on the retard/switch assembly fit into the locating pin bosses on the base.
- Re-install the (2) original mounting screws.
- Reconnect all wires. Perform a flow test and place the system back in service.
Removal of Waterflow Switch
- To prevent accidental water damage, all control valves should be shut tight and the system completely drained before waterflow detectors are removed or replaced.
- Turn off electrical power to the detector, then disconnect wiring.
- Loosen nuts and seperate unit from the glued-in fittings
- Gently lift the unit far enough to get your fingers under it. With your fingers, roll the vane so it will fit through the hole while continuing to lift the waterflow detector.
- Lift detector clear of pipe.
PRINTED IN USA
MFg. #5401205 – REV H
01/12
firealarmresources.com
Documents / Resources
|
POTTER VSR-SG Waterflow Alarm Switch with Glue-in
Union
[pdf] Owner's Manual
VSR-SG Waterflow Alarm Switch with Glue-in Union, VSR-SG, Waterflow Alarm
Switch with Glue-in Union, Glue-in Union, Waterflow Alarm Switch, Alarm
Switch, Switch
---|---
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>