POTTER IPA-4000 Fire Alarm Control Panel Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
IPA-4000 Fire Alarm Control
Panel
City of Chicago, Class 1 Addressable Approved City of Chicago
Class 1 Addressable Approved
Features
- 4,064 addresses available on this analog addressable system
- Additional system capacity achieved via multi-point SLC modules
- 1500 software zones
- NFPA 72 Compliant Smoke Sensitivity Test Built-In
- System Operates as Class A or Class B for SLC, P-Link and NACs
- 10 Amp Power Supply
- 6 NACS, Regulated, Rated at 3 Amps each
- 4 Input/Output (I/O) Circuits for system flexibility rated at 1 Amp each
- Strobe Synchronization and System Wide Sync for Potter/AMSECO®, Gentex®, Cooper Wheelock® and System Sensor® strobes
- Dedicated Alarm, Supervisory and Trouble Relays
- 4,000 Event History Buffer
- Cabinet will house up to 18 AH batteries
- Optional two line DACT with UD-2000 that can report General, Zone or Point Information
- Built in IP communicator
- Ethernet Port for Programming and Network Connectivity
- E-Mail System Status, Reports and Event Information
- Product includes 5 year warranty
Description
The IPA-4000 is an expandable analog/addressable releasing fire alarm system
with a total system capacity of 4,064 addresses. Additional capacity on the
system is achieved using multi-point SLC modules The control panel utilizes
the exclusive Potter protocol that includes a complete line of sensors and
modules. The system is expandable with a
total of thirty-one additional addressable Signaling Line Circuits (SLC) each
with a maximum of 127 devices. Each SLC may be comprised of any combination of
smoke sensor, heat detectors or modules and allows for a total of 50 ohms of
impedance and may use any wire compliant with the National Electrical Code
(NEC).
The IPA-4000 has a 10 Amp power supply with six Notification Appliance
Circuits (NACs) and four Input/Output (I/O) circuits. The NACs are rated at 3
Amps each and the I/Os are rated at 1 Amp each. Each output is regulated and
power limited. In addition, each output is uniquely programmable and may be
configured for steady signal, strobe synchronization, constant power, door
holder power, or releasing. The strobe synchronization includes Potter/AMSECO,
Gentex, System Sensor and Cooper/Wheelock and with the exclusive Quadrasync
each output may have a unique brand and all strobes will flash together. The
I/Os are designed for inputs such as manual release stations and abort
switches that will not require polling and react nearly instantaneously.
The IPA-4000 is listed for releasing of fire suppression systems. The software
allows cross zones, counting zones, and timers for suppression.
The system is capable of multiple release outputs across multiple hazards.
In addition, the PSN-1000 may be used to extend releasing capability.
The NACs may be expanded using the PSN-1000 series intelligent power supplies.
Each PSN-1000 adds another 10 Amps of power, 2 additional input circuits and
the IPA-4000 will support up to 31 power supplies. The system will synchronize
the strobes system wide. In addition, the PSN1000E has space to allow the
installation of up to six
PAD100-SLCE SLC loop expansion cards. The cards mount on a stacker bracket
that allows access to all SLC circuit connections.
Technical Specifications
Dimensions | 18 ishew x 27 5/16″H x 4 meD |
---|---|
AC Mains | 5.0 Amps @ 120 VAC 50/60 HZ 3.0 Amps @ 240 VAC 50/60 HZ |
Enclosure | 16 gauge cold rolled steel with removable locked door with Lexan |
viewing window
Batted| Standby Current-130 mA Alarm Current-220 mA
10 Amps power for NACs, I/O, and P-Link 3 Amps per NAC, regulated 1 Amp per
I/O circuit, regulated
Battery Charger range 8-55 Ah Battery Charger voltage 27.3 VDC P-Link maximum
current of 1 Amp
Temperature and Humidity Range| 32° to 120° (0°C to 49°C) with a maximum
humidity of 93% non-condensing.
Standards| ANSI/UL 864 – Local (L), Remote Station (RS), Central Station (CS),
Propriety (PPU), Auxiliary (AUX).Type of Service: Automatic (A), Manual (M),
Water flow (WF) Sprinkler Supervisory (SS) Type of Signaling: Digital Alarm
Communicator (DAC), March Time (March), Non Coded (NC), Reverse Polarity (Rev
Pol), Other Technologies (OT)
Note: We recommend using a non-synchronized NAC circuit for audible
signals when using the Potter EH24, HS-24 or CHS series signaling devices to
produce a steady / non-temporal pattern. For synchronized visual signaling,
strobes should be controlled separately by a NAC circuit that provides Gentex
synchronization protocol.
SLC Loop Accessories
The control panel may be connected with up to 4,064 addressable devices or
modules in any combination. The SLC is not restricted by any special wire
requirements and may be wired with any wire that complies with the NEC.
SLC Features
The Potter protocol is a digital protocol with a proven design for reliability
and noise immunity. The system does not require special cable or conductors
for connection of the Signaling Line Circuit as long as the cable is compliant
with NFPA 70 and NFPA 72.
The system allows for Class A or Class B installations as well as
“T-Taps.”Each loop is capable of 127 points, with a max wiring distance of
10,000 ft.
Sensor Features
The sensors through the fire alarm control panel provide a real time status as
to the condition of the system. The smoke detector sensitivity, heat detector
temperature level and drift compensation are all programmable options. The
system also allows for a day/night mode where the panel automatically adjusts
the sensitivity depending on the time of day. To assist in the reduction of
false alarms, the smoke detectors also have a maintenance warning that sends a
trouble signal when a detector is dirty to the point that it can no longer
maintain the programmed sensitivity.
User Interface
The fire alarm control panel has a 4 x 40 LCD display to provide information
to the system status. The keypad has navigation keys to allow manipulation of
the Menu on board the panel. The panel is shipped standard with the following
LEDs:
- AC Power – Green
- Alarm – Red
- Earth Fault – Amber
- Supervisory – Amber
- Silenced – Amber
- Trouble – Amber
- Pre-Release – Amber
- Release – Red
The common buttons include a Silence, Reset, Acknowledge, and
Drill. All of the buttons are accessible once the locked door is opened.
P-Link
The IPA-4000 has a proprietary communication protocol that communicates
through a RS-485 connection to field devices. Up to 64 devices may be
connected to a single P-Link connection. The P-Link includes the communication
terminals and regulated 24 VDC connection for the field devices. The field
devices may be any of the following:
PAD100-SLCE-Analog/Addressable loop expansion module (maximum of 31 per
IPA-4000)
RA-6075R – 2 x 16 LCD annunciator with a key pad in a locked metal
enclosure.
RA-6500R(F) – 4 x 40 LCD annunciator with a key pad in a locked metal
enclosure. Flush mount version available.
LED-16(F) – 16 LED annunciator with common indicators in a locked metal
enclosure. Flush mount version available.
PSN-1000(E) – 10 amp, remote intelligent power supply with 6 NACs, 2
Inputs and a P-Link repeater. This panel is listed in conjunction with the
IPA-4000 as releasing circuits.
CA-6500 – Class A converter that converts the SLC, NACs and P-Link
connection.
UD-2000 – UL listed, Dual line telephone alarm communicator.
DRV-50 – LED driver expander, used to connect up to 50 LEDs in a graphic
display.
FCB-1000 – Fire communication bridge, provides remote mounting of the
Ethernet connection.
FIB-1000 – Fiber interface module, used to extend P-Link to multimode
fiber (2 required).
RLY-5 – Relay module, provides 5 form C relay contacts rated at 3.0 amps
24VDC/125AC.
SPG-1000 – Serial parallel gateway, allows for the connection to a serial
or parallel printer.
The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker
bracket or ordered with the optional rack mount enclosure. MC-1000 Multi-
Connect allows up to sixty-three IPA series panels to share a single reporting
technology.
AE-2 – Two card expansion cabinet AE-8 – Eight card expansion cabinet,
AE-14 – Fourteen card expansion cabinet
Ethernet/I.P. Connection
The IPA-4000 is shipped standard with an Ethernet connection.
This connection is the programming port and may be connected to a building
Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the
Internet, the panel may be selectively programmed to e-mail alarm conditions,
trouble conditions, supervisory conditions, test, Event History and detector
status. An e-mail may be sent to the panel and the panel will e-mail the event
history, detector status, configuration file or server status to an authorized
E-mail account. In addition, reminders may be set to send an e-mail for
service, testing or other conditions. In addition, the Ethernet connection is
UL listed as an IP communicator. The IP communicator is listed to report to
the UL listed Sur-Gard III IP receiver. The IP communicator replaces the
traditional less reliable alarm communicator transmitter that utilized
telephone lines. The IP communicator is an active method of connection and
communication to the monitoring station.
Chicago Building Code Requirements
The models CBC-DC-KIT-2, CTD2G, CITY, and FIRE are designed to comply with
conventional and addressable Class I type building requirements of the City of
Chicago, Illinois. They provide the ability to perform silencing of the system
trouble bell and the city tie disconnect bell. They also allow disconnecting
of the municipal tie fire alarm box. For City of Chicago fire alarm projects,
a fire alarm plan review and permit are required.
CTD2G
The City Disconnect Switch is used to disconnect the fire alarm panel from
reporting any alarm or trouble condition to the city in order to test and
maintain the fire alarm system. When the key switch is turned to the
Disconnect position a white pilot light illuminates to inform the user that
the panel has been disconnected.
FIRE
The Fire Alarm Trouble Bell module is used to silence and test the fire alarm
trouble bell. When the fire alarm system is in trouble the bell will ring.
Moving the toggle switch to Bell Silence will silence the bell and activate
the Bell Silenced LED.
When the trouble clears the Bell Silenced LED will turn off and a ring back
will sound until the toggle switch is returned to the Bell Normal position.
When the panel is normal, moving the toggle switch to the Bell Silence
position will ring the bell. Pressing the Bell Test button will ring the bell.
CITY
The City Tie Trouble module is used to silence and test city tie disconnect
troubles. When the CTD2G keyswitch is in the Disconnected position, the City
Tie Trouble bell will ring. Moving the toggle switch to Bell Silence will
silence the bell and activate the Bell Silenced LED. When the trouble clears
the Bell Silenced LED will turn off and a ring back will sound until toggle
switch is returned to the Bell Normal position. When the CTD2G keyswitch is in
the Normal position and the toggle switch on the CITY module is in the Bell
Silence position, the City Tie Trouble bell will ring. Pressing the Bell Test
button will ring the bell.
These modules can be each be mounted to a two-gang deep bell box or a two gang
deep wiremold box and operates on 24VDC. The modules can be flush mounted with
a two-gang plaster ring on a deep 4” square 1900 box.
For more information on and to order the above modules or the City Tie
Disconnect Panel, please contact the following vendor:
Gemcom, Inc., 8828 S. Archer Ave.
Chicago, IL 60480800-871-6840
www.gemcom.com
CBC-DC-KIT-2
The City Tie DISCONNECT PANEL combines 3 separate switch assemblies in one
complete panel to simplify installation and wiring near the Fire Alarm Panel
The City Tie Disconnect Switch is used to disconnect the Fire Alarm Panel from
reporting any Alarm or Trouble Condition to the City in order to test and
maintain the Fire Alarm System. When the switch is turned to the Disconnected
position, a White Pilot light illuminates to inform the user that the Panel
has been disconnected. The City Tie Trouble Bell will ring and can be silenced
using the City Tie Trouble Station on the bottom right of the Disconnect
Switch.
Both the Fire Alarm Trouble and the City Tie Trouble Stations work the same
way. In the “BELL NORMAL” position, the “BELL TEST” will sound the bell. When
there is a trouble condition, the bell will sound. Switching the toggle to the
“BELL SILENCE” position will silence the bell and the Bell Silenced LED will
illuminate. When the trouble clears, the LED will turn off and a ring back
will sound until the “BELL SILENCE” switch is returned to the normal position.
The back box contains 8 combination 1/2” / 3/4” knockouts. The door mounts
with 2 locknuts and the back plate with 4 locknuts. The enclosure includes a
key lock.
Additional Equipment Required
An incandescent backlit annunciator is required to comply with Class I type requirements. Contact the vendor listed below for the custom model XL8 Tabular Annunciator (see figure at right). Space Age Electronics, Inc., 58 Chocksett Road Sterling, MA 01564 800-486-1723 www.1sae.com
Dimensions
Ordering Information
Model | Description | Stock No. |
---|---|---|
Ipa-4000 | Fire Alarm Releasing Control Panel | 3992717 |
Potter Electric Signal Company, LLC • St. Louis, MO •
Phone: 800-325-3936
www.pottersignal.com
firealarmresources.com
Documents / Resources
|
POTTER IPA-4000 Fire Alarm Control
Panel
[pdf] Owner's Manual
IPA-4000 Fire Alarm Control Panel, IPA-4000, Fire Alarm Control Panel, Alarm
Control Panel, Control Panel
---|---
|
POTTER IPA-4000 Fire Alarm Control
Panel
[pdf] Owner's Manual
IPA-4000 Fire Alarm Control Panel, IPA-4000, Fire Alarm Control Panel, Alarm
Control Panel, Control Panel
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>