Description

The PAM Series Relays are encapsulated multivoltine devices with “flying” leads that offer versatile, reliable performance in a convenient package. Several of the versions  contain a red LED which indicates when the relay coil is energized. The PAM Series Relays are packaged with a self-tapping screw and a piece of double sided tape for easy  installation almost anywhere. The relays are also packaged with wisents to aid installation.
PAM Relays are ideal for applications where remote relays are required for control or status feedback. They are suitable for use with HVAC, Temperature Control, Fire Alarm,  Security, Energy Management, Lighting Control Systems and Building Automation Systems.
PAM-1
The PAM-1 Relay provides 10.0 A form “C” contacts. The relay may be energized by one of three input voltages: 24VDC, 24VAC, or 120VAC. The input voltages are polarity-sensitive and diode-protected. PAM-1 Relays contain a red LED which indicates when the relay coil is energized. This relay may not be suitable for continuous duty use at 120VAC for extended periods of time. For these applications, please refer to our RIC-Series products.

Features

  • Multi-voltage operation
  • Activation LEDS to indicate when the relay coil  is energized
  • Easy installation
  • Ideal for applications where remote relays are required for control or status feedback
  • Suitable for use with HVAC, Temperature Control, Fire Alarm, Security, Energy Management, Lighting Control Systems and Building Automation Systems

PAM-2
The PAM-2 Relay provides 7.0 A form “C” contacts. The relay may be energized by one of two input voltages: 12VDC or 24VDC. The input voltages are polarity- sensitive and diode-protected. PAM-2 Relays contain a red LED which indicates when the relay coil is energized.

PAM-3
The PAM-3 Relay provides a 3.0 A form “A” contact. The relay may be energized across a wide voltage range from 9VDC to 40VDC, making it ideal for 12VDC and 24VDC EOL circuits. The 19.3 mA operating current is constant across the operating range. The input voltage is polarity-sensitive and diode-protected.

PAM-4
The PAM-4 Relay provides 10.0 A form “C” contacts. The relay may be energized across a wide voltage range from 9VDC to 40VDC, making it ideal for 12VDC and 24VDC EOL circuits. The 15mA operating current is constant across the operating

Wiring Diagrams

Mircom PAM Series Multi Voltage Control Relays -
Diagrams

Specifications

Model Number PAM-1 PAM-2 PAM-3 PAM-4
Coil Voltage 24VAC/24VDC/120VAC 12VDC/24VDC 9 to 40VDC 9 to 40VDC
Polarized Yes Yes Yes Yes
Energized Led Indicator Yes Yes No No

Current Requirement
@12VDC| –| 15mA| 19.3mA| 15mA
@24VDC| 15mA| 15mA| 19.3mA| 15mA
@24VAC| 31mA| –| –| –
@120VAC| 19mA| –| –| –
Contact Configuration| (1) SPDT dry form “C”| (1) SPDT dry form “C”| (1) SPST dry form “A”| (1) SPDT dry form “C”
Contact Ratings (contact rating / power factor)
@5VDC| 250μA / .35 PF| 250μA / .35 PF| –| 250μA
@24VDC| 7A / .35 PF| 7A / .35 PF| 3A / .35 PF| 7A
@120VAC| 10A| 7A / .35 PF| 3A / .35 PF| 10A
Wire Leads| 6 “flying” leads 12” / 18 AWG
Wire-nuts provided| 6 “flying” leads 12” / 18 AWG
Wire-nuts provided| 4 “flying” leads 12” / 18 AWG
Wire-nuts provided| 5 “flying” leads 12” / 18 AWG
Wire-nuts provided
Ambient Temperature (@ 100% RH, condensing)| 32°F to 120°F (0°C to 49°C)| 32°F to 120°F (0°C to 49°C)| 32°F to 120°F (0°C to 49°C)| 32°F to 120°F (0°C to 49°C)
Construction| 100% potted (sealed) with “flying” leads
Mounting| Pre-drilled mounting screw hole and self tapping screw provided. Double sided tape provided.
Dimensions| 1.50” (38mm) H x 1.00” (25mm) W x 0.80” (20mm)| 1.50” (38mm) H x 1.00” (25mm)Wx0.90”(23mm)D| 1.50” (38mm) H x 1.00” (25mm)Wx0.90”(23mm)D| 1.50” (38mm) H x 1.00” (25mm)Wx0.90”(23mm)D

Ordering Information

Model Number Description
PAM-1 Encapsulated relay, Single SPDT, 10.0 A form “C” contact
PAM-2 Encapsulated relay, Single SPDT, 7.0 A form “C” contact
PAM-3 End-Of-Line Relay, 3.0 A form “A” contact
PAM-4 Encapsulated relay, Single SPDT, 10.0 A form “C” contact

CATALOG NUMBER 5317
NOT TO BE USED FOR INSTALLATION PURPOSES.

Morcom reserves the right to make changes at any time without notice in prices, colors, materials, components, equipment, specifi cations and models and also to discontinue models.
NOT TO BE USED FOR INSTALLATION PURPOSES.

Distributed by:
ISO 9001:2008
REGISTERED
mircom loogCanada

25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
Web page: http://www.mircom.com

U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
Email: mail@mircom.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals