Mircom SIS-204 Speaker Isolator Module Owner’s Manual
- June 9, 2024
- Mircom
Table of Contents
Mircom SIS-204 Speaker Isolator Module
SPEAKER ISOLATOR MODULE SIS-204
Description
Mircom’s SIS-204 Speaker Isolator Module is designed for installations where disconnection of, or damage to an in-suite speaker will not interfere with the ability of speakers in other dwelling units, public corridors or suites to sound on an alarm. The SIS-204 works in conjunction with the QX-5000 Zoned Audio System and comes equipped with trouble LEDs. The LEDs are only operable when the isolator is used in a supervised connection. The SIS-204 Speaker Isolator Module can be connected in a supervised or non-supervised confi guration. In a supervised confi guration, the SIS-204 provides two supervised outputs. Under this scenario, if the in-suite speaker has a open circuit, the fi re or audio control panel will indicate a zone trouble and the isolator LED will fl ash to indicate which isolator has the fault. The trouble LEDs fl ash to indicate a positive or negative fault on the isolator. When the left amber trouble LED fl ashes, it indicates an open on the positive side and consequently, when the right amber LED fl ashes, it indicates an open on the negative side. In a non-supervised confi guration, the SIS-204 provides four non-supervised outputs. Under this scenario, if a short or open circuit occurs, the isolator disconnects the speaker from the circuit but it does not indicate a trouble on the fi re or audio control panel. In this confi guration, an open circuit in the suite does not indicate a trouble on the control panel
Features
- Designed for installations where disconnection of, or damage to an in-suite speaker will not interfere with the ability of speakers in other dwelling units, public corridors or suites to sound on an alarm
- Operates in conjunction with the QX-5000 Emergency Zoned Audio System to provide 2 supervised isolator outputs or 4 non-supervised outputs
- Include two isolator trouble LEDs (operable when the isolator is used in a supervised confi guration)
- Mount in a 4” square electrical box
Installation Instructions
Mounting of the SIS-204 Speaker Isolator Module
Electrical Specifications
- Rating: For 70V speaker lines
- In-Suite Speaker Load: 6 watts max.
- Max. Number of Isolators on a speaker line: 15 with specified Littelfuse type 312 fuse
- Fuse: Littelfuse 0.1A, 250V Slow Blow #312.100
- Standby: 0.0 A
- Open circuit on (+) or (-) side: 200uA
- Open circuit on both sides: 100uA
Note: The SIS-204 is used with Mircom’s 4” 70 Volt Speakers (Standard or Smart Silenceable Speakers).
Typical Wiring Diagrams
Typical Wiring of the SIS-204 Speaker Isolator Module in a Supervised Configuration
THE (+) LED WILL BLINK FOR AN OPEN ON THE POSITIVE SIDE OF THE IN-SUITE SPEAKER, SIMILARLY, THE (-) LED BLINKS FOR AN OPEN CIRCUIT ON THE NEGATIVE SIDE OF THE IN-SUITE SPEAKER.
Typical Wiring of the SIS-204 Speaker Isolator Module in a Non-Supervised
Confi guration Note: Mircom does not recommend the
installation of unsupervised signal circuits. Mircom recommends that occupants
follow proper measures for fi re procedures for their premises.
Mircom recommends that all suite isolators should be mounted outside of the
suite they are protecting.
Ordering Information
Model
SIS-204
Description
Speaker Isolator Module
NOT TO BE USED FOR INSTALLATION PURPOSES.
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
Web page: http://www.mircom.com
Email: mail@mircom.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>