Mircom QX-MINI Emergency Communication System Owner’s Manual
- June 9, 2024
- Mircom
Table of Contents
Mircom QX-MINI Emergency Communication System Owner’s Manual
Description
The QX-mini is an emergency and fire alarm audio system designed to provide notification for small to medium applications. The QX-mini supplies 30W for audio output and 5A for Notification Appliance Circuits (NAC). The optional 30 Watt Amplifier Module increases audio output to 60W.
Notifications can be sent using stored digital message recordings, the master microphone, or remote microphones. The QX-mini comes with standard notifications and can store up to
14 messages for a total of 12 minutes of digital message recordings. Up to six remote microphones and/or LOCs can be connected to the QX-mini.
The QX-mini operates either as a stand-alone audio system or as part of a fire alarm system. Conventional fire alarm systems control the
QX-mini with relays. Mircom compatible Fire Alarm Control Panels can control the QX-mini using Signalling Line Circuit (SLC).
Optional Booster Panels provide support for a distributed system. These Booster Panels act as true slaves to the master with respect to Outputs. All Inputs, Microphones and User interfaces are disabled on Booster Panels and they cannot be programmed through the configuration software. Up to five Booster Panels can be connected to a QX-mini.
Features
- Up to 60 watts per enclosure (2 X 30W amplifiers) and up to 360 watts per system
- 2 X 2.5A regulated 24V output for horns and strobes
- (NAC). System expandable to 12 X 2.5A
- Class A or Class B Speaker and NAC wiring
- Field selectable 25V or 70.7V audio output
- Comes with standard digital messages for fire, emergency, evacuation, weather, and all clear
- Select from up to 14 digital messages at the panel
- Custom message upload using the software configurator
- Stores up to 12 minutes of audio messages
- Master microphone input with push-to-talk (PTT)
- Supports up to 6 remote microphones and/or LOCs
- Use as a separate audio system or as part of a fire alarm system
- Two inputs for activation by conventional fire alarm systems using relays
- Two strobe inputs for synchronization and activation
- Signalling Line Circuit (SLC) input for activation and communication with Mircom compatible Fire Alarm Control Panels
- Battery backup (up to 75AH charge capacity)
- Dedicated Trouble, AC Fail, and Alarm relay outputs
- Audio system supports up to 6 panels in total (one Master Panel with 5 Booster Panels)
- 12 expandable up to 36 Programmable Switches
- Auxiliary 24V supply (up to 0.2A)
- ULC, UL, CSFM
Accessories
- Amplifier Module
- Audio amplifier Splitter
- 24 Zone Selector
Expansion Modules
- Booster Panel
- Remote Microphone
- LOC
Backup Amplifier with QAS-2X8 Audio Amplifier Splitter
When there are 2 amplifiers installed, one of them can be configured as a backup. If the main amplifier fails, the backup amplifier takes over.
Instructions
Up to 8 Audio Outputs with 2 different audio messages per Panel with QAS- 2X8 Audio Amplifier Splitter
When connecting 2 amplifiers to the audio zone splitter in an application
where each amplifier plays a different audio message. For example, one
amplifier can provide an alarm signal to a zone, and the other amplifier can
provide an alert signal to the other zones. This configuration provides 8
outputs. The 8 outputs can select from amplifier 1, amplifier 2, or they can
be off
NOT TO BE USED FOR INSTALLATION PURPOSES. THIS INFORMATION IS FOR
MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE THE PRODUCTS TECHNICALLY
Specifications
-
Dimensions
-
26”H x 14.5”W x 4.2”D
-
AC Line Voltage
-
120V @ 60Hz / 240V @ 50Hz (3.1 Amps / 1.57 Amp)
-
Output
-
30W audio (60W max.) and 2 X 2.5A NAC (5A max.)
Battery -
24VDC, Gel-Cell/Sealed Lead-Acid
-
Charging Capability
-
Up to 75AH charge capacity
-
Current Consumption
-
Standby : 215mA Alarm: 220mA
Indicators
AC Power Ground Fault CPU Fault Message Active| Alarm Active Pretone Active
Page Ready
Controls
Zone Select (4) Message Select (8) All Call| Selection Reset Lamp Test Trouble
Silence
Compatibility
UL/ULC listed Fire Alarm Control Panels
Ordering Information
Model | Description |
---|---|
QX-MINI | Master Panel: Microphone, Main Display, Main Board, 1 x 30W |
Amplifier, Deadfront, Red Door, Backbox, Back Plate, Transformer
QX-MINI-BP| Booster Panel: Outer Red Door, Main Board (acting in slave mode),
1 x 30W Amplifier, Backbox, Back Plate, Transformer
QX-MINI-RM| Remote Microphone: Backbox, Red Door, Microphone, RMIC PCB
QX-MINI-LOC| Local Operating Console: Main Display, Microphone, RMIC PCB,
Deadfront, Backbox, Red Door
QAD-30| 30 Watt Amplifier Module
QAZT-5302DS| 24 Zone Controller
QAS-2X8| Audio amplifier Splitter
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
www.mircom.com
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance, installation, testing and certification, refer to technical literature. This document contains intellectual property of Mircom. The information is subject to change by Mircom without notice. Mircom does not represent or warrant correctness or completeness.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>