Mircom MS-400U SERIES Metal Fire Alarm Station Owner’s Manual
- June 9, 2024
- Mircom
Table of Contents
Mircom MS-400U SERIES Metal Fire Alarm Station
Description
Attractive and durable, Mircom’s MS-400U Series of manual stations provide manual fi re-reporting. The MS- 400U Series manual stations are non-coded, single or double-action devices which initiate an alarm when pulled. Resetting is accomplished by inserting a 1/8” screwdriver from the front. The handle once pulled will remain open and cannot be reset without utilizing the screwdriver. The MS-400U Series manual stations are constructed of durable aluminium and finished in red. An abrasion resistant label with large, raised letters provides clear legible instructions.
The model MS-402U (two stage) is similar to the MS- 401U (single stage) except it contains an additional General Alarm (G.A.) N.O. switch. For safety reasons, the G.A. switch is only accessible after the handle has been pulled. A special key is supplied with each unit. The model MS-405U is similar to the MS-401U except it has an additional N.O. switch. The model MS-406U is similar to the MS-402U except it has an additional N.O. switch. The model MS-407U is similar to the MS- 401U except it has an additional N.C. switch. The model MS- 408U is similar to the MS-402U except it has an additional N.C. switch. All manual stations can be easily converted from single action to double action station by the addition of the MS-DA double-action lever.
Operation
Pulling on the station’s handle will release the internal switch to trigger the alarm detection circuit. The MS-402U, MS-406U and MS-408U (two stage versions) also provide a key switch which is accessible after the handle has been pulled. Operation of the key switch, when connected to a separate general alarm circuit, will initiate the 2nd stage of a two stage alarm signalling system.
Specifications
The single-action manual station shall be Mircom’s MS- 400U Series. Operating instructions shall be in raised English lettering and the unit shall be constructed of extruded aluminum, finished in red enamel paint to provide quick identification. Pulling the handle shall initiate the immediate operation of the alarm detection circuit. In addition, those stations installed in a two stage system shall come equipped with an internal key switch designed to operate the 2nd stage alarm initiating circuit. All manual fire alarm stations shall be installed as per the specifi c requirements outlined in the UL codes, as well as all other applicable national or local codes.
Dimensions
Wiring Diagrams
NOTES
- WIRE AS SHOWN SO THAT SUPERVISION OF CONNECTIONS IS MAINTAINED.
- N.O. SWITCH FOR MODEL MS-406 N.C. SWITCH FOR MODEL MS-408
- MOUNT STATION TO 2” X 4” X 2 1/4” OUTLET BOX.
- SWITCH RATING: ALL MODELS 1A @ 30 VDC
NOTES
- WIRE AS SHOWN SO THAT SUPERVISION OF CONNECTION IS MAINTAINED.
- N.O. SWITCH FOR MODEL MS-405 N.C. SWITCH FOR MODEL MS-407
- MOUNT STATION TO 2” X 4” X 2 1/4” OUTLET BOX.
- SWITCH RATING: ALL MODELS 1A @ 30 VDC
Ordering Information
Model / Description
- MS-401U: Single Stage Manual Station
- MS-402U: Dual Stage Manual Station
- MS-405U: Single Stage Manual Station with additional N.O. Switch
- MS-406U: Dual Stage Manual Station with additional N.O. Switch
- MS-407U: Single Stage Manual Station with additional N.C. Switch
- MS-408U: Dual Stage Manual Station with additional N.C. Switch
- MS-DA: Double Action Lever Kit (converts any of the above to double action stations)
CONTACTS
Canada
- 25 Interchange Way Vaughan, Ontario L4K 5W3
- Telephone: 905-660-4655
- Fax: 905-660-4113
U.S.A.
- 4575 Witmer Industrial Estates Niagara Falls, NY 14305
- Toll-Free: 888-660-4655
- Fax Toll-Free: 888-660-4113
- Web page: http://www.mircom.com
- Email: mail@mircom.com
- firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>