Description

Mircom’s FleX-Net Mass Notification System (MNS) is designed to provide real- time information to all building occupants or personnel in the immediate vicinity of a  building during emergency situations. The system allows for real-time information regarding the type of emergency as well as safely instructing people on where to go and what to do.
Mircom’s FleX-Net MNS system offers building owners and facility managers with a simple solution to their safety requirements. The system is designed to automatically change as emergency situations change. In addition it is able to manage all mass notification functions, allow responding authorities the ability to override fire alarm notification, issue external voice announcements, and simultaneously distribute different emergency communications on any geographic scale required.
Designed with the industry’s most advanced hardware and software, Mircom’s FleX-Net MNS system provides reliable and clear audible and visual notification, live voice instruction and Internet based text messaging. In addition it can be easily integrated to other public safety systems for emergency communications to wide area networks. Mircom’s FleX-Net MNS is UL 2572 listed for Mass Notification and complies with NFPA 72-2019 and UFC/DOD standards for emergency communications systems. Based on the proven and reliable FleX-Net Intelligent Network Fire Alarm Control Panel and Audio System the FleX-Net MNS provides a rich feature set that delivers an extensive number of configurable options that allow for flexibility in any environment while reducing the installation and maintenance burden with an easy to install, modular setup.

Features

Mass Notification

  • Storage and activation of pre-programmed intelligible voice messages
  • Supervision of all Mass Notification (MNS) equipment
  • Auxiliary inputs for general paging, background music, or other non-emergency functions
  • Tamper resistant enclosures with password-protected features for enhanced access control
  • One-Way and Two-Way EVACS capability
  • Automatic response to MNS inputs
  • Local and remote controls and indicators
  • Synchronized evacuation zone signalling
  • Voice message priority according to risk analysis and emergency response plan
  • Visible notification and strobes support
  • Local Operating Console (FX-LOC) that provides on-site monitoring/ control of voice and notification appliances
  • Large LCD displays
  • Fire Alarm Control Panel Interface (FACI)
  • Building Management System Interface (BMSI)
  • Autonomous Control Unit providing real time status of all FX-LOC units
  • UL 2572 Listed for Mass Notification

Fire Alarm Control

  • Base system is expandable up to 20 SLCs.
  • Advanced Protocol (AP) supports up to 318 devices per SLC (159 sensors & 159 modules)
  • MGC Protocol supports up to 240 MIX-4000 devices (240 sensors and modules) per SLC
  • Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at 1.7 Amps each
  • Built-in Ethernet port
  • Remote diagnostics via a built-in web server

Audio Control

  • Multi-channel operation
  • Distributed audio
  • Compatible with 520Hz low frequency signal by Mircom
  • 5 hard wire fire fighter telephone channels that can be expanded with intelligent fire phone modules
  • 25 or 70 volt system
  • Multiple amplifier sizes
  • Max. of 180 watts per Integrated Fire & Audio panel
  • Expansion to three 360 watts expansion cabinets for a total of 1260 watts of audio power per node

Network Features

  • Up to 63 nodes
  • Peer-to-peer network communications
  • Fully integrated digital network audio and control over a single pair of copper wire or fiber optic cable
  • Supports over 5,000 points per node
  • Supports over 250,000 points on a single network
  • Remote diagnostics via built in web server and standard Ethernet port in every node
  • Style 4 (Class B) or Style 6 or 7 (Class A) wiring configuration
  • Proprietary Arcnet Network Communications protocol

FLEXNET-MNS Mass Notification Control Modules

FX-4000MNS Main Network Board
The FX-4000MNS main network board includes four Style Z/Y (Class A/B) NAC circuits. The FX-4000MNS has provisions to mount up to 9 internal adder modules and mounts in the BBX-FXMNS enclosure.
QMB-5000N Integrated Audio Network Chassis
The QMB-5000N includes the audio and telephone control which consists of an audio card cage designed for mounting the ANC-4000 Audio Network Controller Module, TNC-5000 Telephone Network Controller Module and up to four QAA style audio amplifiers. The QMB-5000N connects to the FX-4000MNS Network fire alarm main board and mounts in the BBX-FXMNS enclosure. BBX-FXMNS Enclosure
The BBX-FXMNS enclosure supports the FX-4000MNS Network main board, DSPL-XXXX Main LCD display, QMB-5000N audio card cage, QMP-5101NV Master Paging Microphone and QMT-5302NV Master Telephone Handset. In addition the enclosure provides space for additional external modules and internal lobby control modules. The BBX-FXMNS holds up to 40 AH batteries and is available with white (BBXFXMNS) or red (BBX-FXMNSR) doors.
BBX-FXMNS Dimensions: 61.5”H x 20”W x 9”D DSPL- 420DS Main Display Module
The DSPL-420DS Main Display Module provides theFLEXNET-MNS with a 4-line by 20-character backlit LCDdisplay, Common Controls buttons and Four Status Queues withselector switches and LEDs for Alarm, Supervisory, Trouble andMonitor. The DSPL-420DS occupies one display position in the BBX-FXMNS enclosure. DSPL-420-16TZDS Main Display Module
The DSPL-420-16TZDS Main Display Module provides a 4 line by 20 character backlit LCD display, Common Control buttons and Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitoring with an additional 16 LED points of annunciation. The DSPL-420-16TZDS occupies one display position in the BBX-FXMNS enclosure. DSPL-2440DS Graphical Main Display Module
The DSPL-2440DS Graphical Main Display Module provides the FLEXNET-MNS with a 24 line x 40 character backlit LCD display, common controls buttons and four status queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor. The DSPL-2440DS occupies one display position in the BBX-FXMNS enclosure. QMP-5101NV Network Master Paging Control Module
The QMP-5101N Network Master Paging Control Module includes the paging microphone and common control indicators. The QMP-5101N Network Master Paging Control Module connects via a ribbon cable to the first QAZT-5348DS or QAZT- 5302DS Zoned Selector Panel and to the previous display module. The QMP-5101NV is vertical mount unit that mounts in the BBX-FXMNS enclosure. QMT-5302NV Network Master Firefighters’ Telephone Control Module
The QMT-5302NV includes the Master Telephone Handset and common control indicators. The QMT-5302NV supports the QAZT5302DS Paging and Telephone selector modules. The QMT-5302NV is a vertical mount unit that mounts in the BBX-FXMNS enclosure.

Fire Network Controller Modules

FNC-2000 Fire Network Controller Module
The FNC-2000 provides network capability to the system. One Fire Network Controller Module is required per network node panel. In addition the FNC-2000 provides an interface for adding an optional FOM-2000-UM Fiber Optic Network Adder Module. The FNC-2000 mounts in the FLEXNET-MNS.Mircom FLEXNET-MNS
Intelligent Fire Alarm and Emergency Communications Network - FOM-2000-UM
Fiber Card Universal Mode FOM-2000-UM Fiber Card Universal Mode
Allows for single-mode or multi-mode fibre optic communication on a
Flex-Net network. Add FOM-CONN-SM and FOM-CONN-MM
FOM-CONN-MM Fiber Optic Connector Multi-Mode
Fibre Optic Module Connector Multi-mode (pack of 2). Must use a
FOM-2000-UM
FOM-CONN-SM Fiber Optic Connector Single-Mode
Fibre Optic Connector Single Mode (pack of 2). Must use a
FOM-2000-UM

Adder Auxiliary Modules

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - UDACT-300A Digital Alarm Communicator Module UDACT-300A Digital Alarm Communicator Module
The UDACT-300A Digital Communicator allows the system to transmit addressable point information to a central station. The UDACT-300A occupies one module slot.

Adder Hardwire Modules

DM-1008A Eight Initiating Circuit Module
The DM-1008A provides 8 Style B (Class B) or 4 Style D (Class A) Initiating Circuits configurable for Alarm, Supervisory or Trouble zones. The DM-1008A occupies one module slot.Mircom FLEXNET-MNS Intelligent Fire Alarm and
Emergency Communications Network - SGM-1004A Four Notification Appliance
Circuit Module SGM-1004A Four Notification Appliance Circuit Module
The SGM-1004A provides 4 Style Z/Y(Class A/B) Notification Appliance Circuits configurable as Silenceable or Non-Silenceable. Each NAC circuit is rated at 1.7 Amps and has individual signal silence inputs (jumper selectable). The SGM-1004A occupies one module slot.Mircom FLEXNET-MNS Intelligent Fire Alarm
and Emergency Communications Network - RM-1008A Eight Relay Circuit
Module RM-1008A Eight Relay Circuit Module
The RM-1008A provides the system with eight individual configurable relays per module. Each relay provides one Form C contact rated at 28 VDC @1 Amp (resistive load) as well as a Green LED to indicate that the relay is active. The RM-1008A occupies one module slot.Mircom FLEXNET-MNS Intelligent Fire
Alarm and Emergency Communications Network - PR-300 Polarity Reversal City Tie
Module PR-300 Polarity Reversal/City Tie Module
The PR-300 Polarity Reversal/City Tie Module provides the system with a supervised City Tie (24 VDC/200 mA max.) and Polarity Reversal connection (24 VDC (open circuit), 8 mA max. (shorted)). The PR-300 occupies one module slot.

Remote LCD Annunciators

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - RAXN-4000LCD Remote LCD Annunciator RAXN-4000LCD Remote LCD Annunciator
The RAXN-4000LCD Remote LCD Annunciator is equipped with a 4-line x 20-character back-lit alphanumeric LCD display that provides an exact replica of the main FleX-Net fire alarm control panel display. The RAXN-4000LCD occupies one display position in the BBXFXMNS, BB-1000 or BB-5000 Series enclosuresMircom FLEXNET-MNS Intelligent Fire Alarm and Emergency
Communications Network - RAM-1032TZDS-CC Conformal Coated Main Remote
LED RAM-1032TZDS-CC Conformal Coated Main Remote LED Annunciator
The RAM-1032TZDS-CC Conformal Coated Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. The RAM- 1032TZDS-CC has indicators for A.C. On, Common Trouble and Signal Silence and controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence and Signal Silence. The RAM1032TZDS-CC occupies one display position in the BB-1001WP(R)A or BB-1002WP(R)A enclosures.Mircom FLEXNET-MNS Intelligent Fire Alarm and
Emergency Communications Network - RAM-1032TZDS Main Remote LED
Annunciator RAM-1032TZDS Main Remote LED Annunciator
The RAM-1032TZDS Main Remote LED Annunciator provides common annunciator functions and 32 points of LED annunciation. The RAM1032TZDS has indicators for A.C. On, Common Trouble and Signal Silence and controls for System Reset, Lamp Test, Fire Drill, Buzzer Silence and Signal Silence. The RAM-1032TZDS occupies one display position in the BB-1000 or BB-5000 enclosures.Mircom
FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications Network -
RAXN-4000LCDG Remote Graphic LCD Annunciator RAXN-4000LCDG Remote Graphic LCD Annunciator
The RAXN-4000LCDG Remote Graphic LCD Annunciator is equipped with a 24-line x 40-character back-lit graphical LCD display that is used to display 9 events per page. Each event is displayed over 2 lines with 40 characters per line allowing emergency information to be displayed in easy to read format. The RAXN-4000LCDG occupies one display position in the BBX-FXMNS, BB-1000 or BB-5000 Series enclosures.Mircom FLEXNET-MNS Intelligent Fire Alarm and
Emergency Communications Network - RAX-1048TZDS-CC Conformal Coated
Programmable LED RAX-1048TZDS-CC Conformal Coated Programmable LED Annunciator Module
The RAX-1048TZDS-CC Conformal Coated Programmable LED Annunciator Module provides 48 programmable bi-colored LEDs. The RAX-1048TZDSCC connects to the main panel or either the RAXN-4000LCD or RAM-1032TZDS when mounted remotely. The RAX-1048TZDS-CC occupies one display position in the BB-1002WP(R)A Series enclosures.Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency
Communications Network - RAX-1048TZDS Programmable LED Annunciator
Module RAX-1048TZDS Programmable LED Annunciator Module
The RAX-1048TZDS Programmable LED Annunciator Module provides 48 programmable bi-colored LEDs. The RAX-1048TZDS connects to the main panel or either the
RAXN-4000LCD or RAM-1032TZDS when mounted remotely. The RAX-1048TZDS occupies one display position in the FX-4009-12N, BB-1000 or BB-5000 Series enclosures.

Programmable Modules

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - FDX-008W KI Fan Damper Module FDX- 008W/KI Fan Damper Module
The FDX-008W/FDX-008WKI Fan Damper Control Module provides individually programmed circuits which can be used for fan or damper control. The FDX-008W /FDX-008WKI connects to the main panel or the RAXN-4000LCD and occupies one display position in the BBX-FXMNS, BB-1000 or BB-5000 Series enclosures.Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency
Communications Network - IPS-2424DS Programmable Input Switches
Module IPS-2424DS Programmable Input Switches Module
The IPS-2424DS provides 24 programmable switches that can be configured for ancillary functions such as zone bypass or added common control functions. The IPS-2424DS connects to the main panel or the RAXN-4000LCD when mounted remotely. The IPS-2424DS occupies one display position in the BBX-FXMNS, BB-1000 or BB5000 Series enclosures.Mircom FLEXNET-MNS Intelligent Fire
Alarm and Emergency Communications Network - IPS-4848DS Programmable Input
Switches Module IPS-4848DS Programmable Input Switches Module
The IPS-4848 provides 48 programmable switches that can be configured for ancillary functions such as zone bypass or added common control functions. The IPS-4848DS connects to main control unit or the RAXN-4000LCD when mounted remotely. The IPS-4848DS occupies one display position in the BBX-FXMNS, BB-1000 or BB-5000 Series enclosures.

Adder Loop Controller Modules

ALCN-960MISO Isolated Quad Loop Adder Module
For MIX-4000 devices, the ALCN-960MISO Isolated Quad Loop Adder Module provides two Signaling Line Circuits (SLC) with ground fault detection to the system consisting of 240 MIX-4000 devices per loop. The ALCN-960MISO can be expanded with the use of the ALCN-960D Daughter Board Module. The ALCN-960MISO occupies one module slot. ALCN-960D Daughter board for ALCN-960MISO
For MIX-4000 devices, the ALCN-960D Daughter Board provides an additional two SLC loops when connected to the ALCN-960MISO Isolated Quad Loop Adder  Module. The daughter board mounts on top of the ALCN-960MISO.Mircom FLEXNET-MNS
Intelligent Fire Alarm and Emergency Communications Network - ALCN-4792MISO
Isolated Quad Loop adder Module ALCN-4792MISO Isolated Quad Loop adder Module
The ALCN-4792MISO Isolated Quad Loop Adder Module provides two Signaling Line Circuits (SLC) with ground fault detection to the system consisting of 159 Analog Sensors and 159 Addressable Modules per loop. The ALCN-4792MISO can be expanded with the use of the ALCN-792D Daughter Board Module. The ALCN- 4792MISO occupies one module slot. ALCN-792D Daughter board for ALC- 4792MISO
The ALCN-792D Daughter Board provides an additional two SLC loops when connected to the ALCN-4792MISO Isolatd Quad Loop Controller Module. The daughter board mounts on top of the ALCN-4792MISO.

FLEXNET-MNS Audio and Telephone Network Controller Modules

ANC-4000 Audio Network Controller Module
The ANC-4000 Audio Network Controller module is mounted on a metal plate (which is packaged with the FX-4000MNS) and then the plate is mounted into BBX-FXMNS backbox in position 1 of the QMB-5000N Card Cage.

Paging Control Modules for Remote Applications

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - QMP-5101N Network Master Paging Control Module QMP-5101N Network Master Paging Control Module
The QMP-5101N Network Master Paging Control Module includes the paging microphone and common control indicators. The QMP-5101N Network Master Paging Control Module connects via a ribbon cable to the first QAZT-5348DS or QAZT- 5302DS Zoned Selector Panel and to the previous display module. The QMP-5101N occupies one module space in the BB-5000 Series enclosures.

Firefighter Telephone Control Modules

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - QMT-5302N Network Master Firefighters’ Telephone
ControlQMT-5302N Network Master Firefighters’ Telephone Control Module
The QMT-5302N includes the Master Telephone Handset and common control indicators. The QMT-5302N supports the QAZT-5302DS Paging and Telephone selector modules. The QMT-5302N occupies one module space in the BB-5000 Series enclosures. TNC-5000 Telephone Network Controller Module
The TNC-5000 provides five hardwired telephone circuits for the local floor panel with the first circuit configurable for the master telephone handset. The TNC-5000 mounts in the QMB-5000N.Mircom FLEXNET-MNS Intelligent Fire
Alarm and Emergency Communications Network - QAZT-5302DS Zoned Paging and
Telephone Selector Module QAZT- 5302DS Zoned Paging and Telephone Selector Module
The QAZT-5302DS Zoned Paging and Telephone Selector Module includes 24 zone selector switches and LEDs. The QAZT-5302DS is used with the QMP-5101N Network Master Paging Control module or QMT5302N Network Master Firefighters’ Telephone module. Slide-in labels are provided to label the selector zones. The QAZT-5302DS occupies one module space in the BB-1000 or BB-5000 Series enclosures.Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency
Communications Network - QAZT-5348DS Zoned Paging and Telephone Selector
Module QAZT-5348DS Zoned Paging and Telephone Selector Module
The QAZT-5348DS Zoned Paging and Telephone Selector Module includes 48 zone selector switches and LEDs. The QAZT-5348DS is used with the QMP-5101N Network Master Paging Control module or QMT-5348N Network Master Firefighters’ Telephone module. Slide-in labels are provided to label the selector zones. The QAZT-5348DS occupies one module space in the BB-5000 Series enclosures.
Annunciator/Programmable Module Enclosures
BB-1001D: 9”H x 12.75”W x 1.85”D
BB-1002D: 18”H x 12.75”W x 1.85”D
BB-1003D: 26.4”H x 12.75”W x 1.85”D
BB-1008D: 33”H x 22.5”W x 1.85”D
BB-1012D: 45”H x 22.5”W x 1.85”D

Audio Amplifiers

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - QAA-5415-70 and QAA-5415-25 Quad 15 Watt
Amplifiers QAA-5415-70 and QAA-5415-25 Quad 15 Watt Amplifiers
The QAA-5415-70 and QAA-5415-25 consist of four 15 watt supervised paging/speaker circuits which can be wired in Class ‘B’ (Style ‘Y’) only. The QAA-5415-70 is a 70 Volt amplifier and the QAA-5415-25 is a 25 Volt amplifier. Both models mount in either the QMB-5000N or QMB-5000B card cage and occupy one amplifier slot.
QAA-5230S-70/25 Dual 30 Watt Amplifier
The QAA-5230S-70/25 consists of two 25 or 70 Volt 30 watt amplifiers. Each amplifier has two 15 watt supervised speaker outputs which are used for ‘A’ ‘B’ speakers per floor and are wired in Class ‘B’ (Style ‘Y’) only. The QAA- 5230S-70/25 mounts in either the QMB-5000N or QMB-5000B card cage and occupies one amplifier slot.
QAA-5230-70/25 Dual 30 Watt Amplifier
The QAA-5230-70/25 consists of two 25 or 70 Volt 30 watt supervised paging/speaker circuits which can be wired in Class ‘A’ (Style ‘Z’) or Class ‘B’ (Style ‘Y’). The QAA-5230-70/25 mounts in either the QMB5000N or QMB-5000B card cage and occupies one amplifier slot.
QAA-5160-70/25 60 Watt Amplifier
The QAA-5160-70/25 consists of one 25 or 70 Volt 60 watt supervised paging/speaker circuit which can be wired in Class ‘A’ (Style ‘Z’) or Class ‘B’ (Style ‘Y’). The QAA-5160-70/25 mounts in either the QMB-5000N or QMB- 5000B card cage and occupies one amplifier slot. QAA-4CLA Class ‘A’ (Style ‘Z’) Converter Module
The QAA-4CLA converts each of the four Class ‘B’ (Style ‘Y’) outputs on a QAA-5415-70 or QAA-5415-25 Amplifiers to Class ‘A’ (Style ‘Z’). The module attaches to the bottom of the amplifier. One QAA-4CLA is required for each amplifier.
QAA-4CLAS Class ‘A’ (Style ‘Z’) Converter Module
The QAA-4CLAS converts each of the four Class ‘B’ (Style ‘Y’) outputs on a QAA-5230S-70/25 or QAA-5230S-525-70/25 Amplifier to Class ‘A’ (Style ‘Z’). The module attaches to the bottom of the amplifier. One QAA-4CLAS is required for each amplifier.
QAA 5415-70 or QAA-5415-25 Wiring DiagramMircom FLEXNET-MNS Intelligent
Fire Alarm and Emergency Communications Network - Wiring Diagram
1 QAA-5230S-70/25 Wiring DiagramMircom FLEXNET-MNS
Intelligent Fire Alarm and Emergency Communications Network - Wiring Diagram
2 QAA-5230-70/25 Wiring DiagramMircom FLEXNET-MNS
Intelligent Fire Alarm and Emergency Communications Network - Wiring Diagram
3 QAA-5160-70/25 Wiring DiagramMircom FLEXNET-MNS
Intelligent Fire Alarm and Emergency Communications Network - Wiring Diagram
4 QAA-4CLA and QAA-4CLAS Connection Diagram

Network System Expansion Enclosures

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - FX-4009-12NDS Large Network Main Control Unit FX-4009-12NDS Large Network Main Control Unit
The FX-4009-12NDS Large Network Main Control Unit consists of a base fire alarm panel with one isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7, Four Style Z/Y (Class A/B) NAC circuits, a 4 line by 20 character LCD display and a 12 Amp power supply. The FX-4009-12NDS has space to mount the FNC2000 Fire Network Controller Module, ANC-4000  Audio Network Controller Module, TNC-5000 Telephone Network  Controller Module and provision to mount up to 4 adder modules. The FX-400912NDS mounts in a BB-5000 Series enclosure and supports Audio Lobby Control modules, Fire Fighter’s Lobby Control modules and FX-4000 Internal Annunciator / Programmable modules. ECX-0012 Expander Chassis
The ECX-0012 Expander Chassis for the FX-4009-12NDS supports up to 12 adder modules and has space for 2 internal annunciator modules.
The ECX-0012 mounts in the BB-5000 series enclosures. QBB-5001 Audio Backbox
The QBB-5001 holds one QMB-5000B Audio Motherboard and Card Cage, one QPS- 5000N Audio Power Supply, one QBC-5000N Audio Battery Charger and up to 40 Ah batteries.Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency
Communications Network - QMB-5000B Audio Motherboard and Card
Cage QMB-5000B Audio Mother board and Card Cage
The QMB-5000B supports 7 QAA style audio amplifiers. The QMB-5000B requires one QPS-5000N Audio Power Supply and one QBC-5000N Audio Battery Charger and mounts in the QBB-5001 Audio Backbox. to 12 adder modules and has space for 2 internal annunciator modules. The ECX-0012 mounts in the BB-5000 series enclosures.

QPS-5000N Audio Power Supply

The QPS-5000N supports up to 360 watts and mounts in the QBB-5001 Audio b QBC-5000N Audio Battery Charger
Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - DOX-5008MB DOX-5014MB Doors
The QBC- 5000N will charge up to 65 Ah batteries and mounts in QBB-5001 Audio Backbox.
Note: The QBB-5001 Audio Backbox will hold up to 40 Ah batteries. Larger batteries will require a BC-160 Battery Cabinet. DOX-5008MB / DOX-5014MB Doors
The DOX-5008MB and DOX-5014MB mounts on the BB-5008 and BB-5014 backbox. The door features the universal CAT-30 lock.
BB-1001WP(R)A – Outdoor Weather Protected EnclosureMircom FLEXNET-MNS
Intelligent Fire Alarm and Emergency Communications Network - BB-1001WP\(R\)A
– Outdoor Weather Protected Enclosure The BB-1001WP(R)A is a complete enclosure that comes with either a RED or WHITE door, a black back-box, two keys and a durable lock at the top of the door. The door comes hinged to the  bottom side of the box for added weather protection. The box is capable of handling one RAM-1032TZDS-CC Main Annunciator Chassis which provides up to
32 points of annunciation. RAM-1032TZDS-CC is ordered separately conform with the UL, ULC installation requirements.
Note: there is no need for thermostat or heater.
RAM-1032TZDS-CC must be ordered separately to match UL, ULC installation requirements.

Dimensions 11-5/32″ H x 12-15/16″ W x 3-1/2″ D (283mm x 329mm x 89mm)
Rated for Outdoor Enviroment +50ºC to -40ºC (-122ºF to -40ºF)
Wet Location 95% R.H. @60ºC

BB-1002WP(R)A – Outdoor Weather Protected Enclosure Mircom FLEXNET-
MNS Intelligent Fire Alarm and Emergency Communications Network - BB-
1002WP\(R\)A – Outdoor Weather Protected EnclosureThe BB-1002WP(R)A is a complete enclosure that comes with either a RED or WHITE door, a black back-box, two keys and a durable lock at the top of the door. The door comes hinged to the bottom side of the box for added weather protection. The box is capable of handling one RAM-1032TZDS-CC Main Annunciator Chassis which provides up to 32 points of annunciation and one RAX1048TZDS-CC Adder Annunciator, which provides up to 48 points of annunciation. RAM1032TZDS-CC and RAX1048TZDS-CC are ordered separately to match the UL, ULC installation requirements.
Note: there is no need for thermostat or heater.
RAM-1032TZDS-CC and RAX-1048TZDS-CC must be ordered separately to match UL, ULC installation requirements.

Dimensions 17-15/16″ H x 12-15/16″ W x 3-1/2″ D (456mm x 329mm x 89mm)
Rated for Outdoor Enviroment +50ºC to -40ºC (-122ºF to -40ºF)
Wet Location 95% R.H. @60ºC

Graphics Software

Open Graphic Navigator (OpenGN)
Open Graphic Navigator (OpenGN) is a centralized fire alarm management system that provides building or campus monitoring. As a powerful integration tool, OpenGN allows operators to monitor remote sites from multiple workstations located anywhere in the world. OpenGN displays monitored buildings and campuses in both 2D and 3D representations, and is highly customizable.

Model Description
OGN-FLSLIC-ONE Single Fire Alarm Control Panel License Requires: OGN-KEY

(sold seperately)
OGN-FLSLIC-EXP| Fire Alarm Control Panel License for 2-9 Connections
Requires: OGN-KEY(sold seperately)
OGN-FLSLIC-STD| Fire Alarm Control Panel License for 10-99 Connections
Requires: OGN-KEY (sold seperately)
OGN-FLSLIC-ENT| Fire Alarm Control Panel License for 100+ Connections
Requires: OGN-KEY (sold seperately)
OGN-KEY| OGN License Key Stick

Power Supply Expansion

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - INX-10AC Internal Booster Power Supply Module INX-10AC Internal Booster Power Supply Module
Mircom’s INX-10AC is an Intelligent Booster Power Supply that extends the power capabilities of existing notification appliance circuits as well as provide power for other ancillary devices. The INX-10AC has 10 amps of power and mounts inside the BB-5014 enclosure.

Graphic Annunciator Driver Modules

MGD-32 Master Graphic Driver Module
The MGD-32 Master Graphic Driver Module provides common control inputs for the common control switches such as System Reset, Signal Silence, Auxiliary Disconnect, Fire Drill, Lamp Test, Acknowledge and General Alarm. The MGD-32 can also drive up to 32 supervised outputs. These output points are capable of driving LEDs or incandescent lamps. The MGD-32 mounts in a graphic annunciator wallbox or in the BB-5000 enclosures. An external power supply is required for incandescent lamps and lamp test. AGD-048 Adder Graphic Driver Module
The AGD-048 Adder Graphic Driver Module can be used with the MGD-32 to support an additional 48 supervised outputs. The AGD-048 mounts in a graphic annunciator wallbox or in the BB-5000 enclosures.

Mounting Brackets

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - M500-BK9 Module Mounting Bracket M500-BK9 Module Mounting Bracket
The M500-BK9 Module Mounting Bracket mounts inside the BB-5000 Series enclosures and provides space to mount up to nine M500 style intelligent modules. M500-BK2 Module Mounting Bracket
The M500-BK2 Module Mounting Bracket mounts inside the BBX-FXMNS enclosure and provides space to mount up to two M500 style intelligent modules.

Local Operating Console Components

Mircom FLEXNET-MNS Intelligent Fire Alarm and Emergency Communications
Network - FX-LOC Lobby Operating Console FX-LOC Lobby Operating Console
The FX-LOC Local Operating Console provides on-site monitoring/ control of voice and notification appliances for Mass Notification applications. The FX- LOC enclosure supports one RAXN-4000LCD remote LCD annunciator, a QMP-5101N master paging microphone and one QAZT-5302DS Paging Selector Switch. RAXN- 4000LCD, QAZT-5302DS, QAZT-5348DS and QMP-5101N are ordered separately.
Add suffix “R” for red door.
Dimensions: 25”H x 15”W x 5.5”D RAXN-4000LCD Remote LCD Annunciator
The RAXN-4000LCD Remote LCD Annunciator is equipped with a 4 line x 20 character back-lit alphanumeric LCD display that provides the exact functions as the FLEXNET-MNS main display. The RAXN4000LCD occupies one display position in the FX-LOC enclosure.Mircom FLEXNET MNS Intelligent Fire Alarm and
Emergency Communications Network - QAZT-5302DS Zoned Paging and Telephone
Selector Module QAZT-5302DS Zoned Paging and Telephone Selector Module
The QAZT-5302DS Zoned Paging and Telephone Selector Module includes 24 zone selector switches and LEDs. The QAZT-5302DS is used with the QMP-5101N Network Master Paging Control module or QMT-5302N Network Master Firefighters’ Telephone module. Slide-in labels are provided to label the selector zones. The QAZT-5302DS occupies one module space in the BB-1000 or BB-5000 Series enclosures. QMP-5101N Network Master Paging Control Module
The QMP-5101N Network Master Paging Control Module includes the paging microphone and common control indicators. The QMP-5101N interconnects between other QMP microphone modules at the FLEXNET-MNS and within the associated FX- LOC units. The QMP-5101N occupies one module space in the FX-LOC enclosure.

Mircom Mass Notification System

Mircom’s FleX-Net Intelligent Fire Alarm & Emergency Communications Network is comprised of an Autonomous Control Unit (FLEXNET-MNS) and the FX-LOC Local Operating Console that complies with the UL 2572 requirements for Mass Notification Systems (MNS).
The FX-LOC Local Operating Console along with the FleX-Net Network Fire Alarm provides compliance with the UL 2572 requirements for Mass Notification Systems (MNS) .
The FLEXNET-MNS Autonomous Control Unit is comprised of a BBX-FXMNS enclosure that includes a RAXN-4000LCD Annunciator and a Master Microphone to provide emergency audio. In addition the FLEXNET-MNS is equipped with another RAXN- 4000LCD which annunciates the fire alarm system events, a Master Telephone for emergency use and a DSPL-420DS or DSPL-2440DS LCD display which annunciates all system messages (Fire Alarm and Mass Notification). A maximum of seven FX- LOC units can be connected to a FleX-Net MNS node.
Sample In-Building Mass Notification System ConfigurationMircom FLEXNET
MNS Intelligent Fire Alarm and Emergency Communications Network - Sample In-
Building Mass Notification System Configuration

Current Consumption

Model Number Description Standby (Amps) Alarm (Amps)

Fire Alarm Components
FX-4000MNS| Main Network Board| 0.310| 0.733
ALCN-960MISO| Quad Analog Loops| 0.200| 0.230
ALCN-960D| Quad Analog Loops| 0.200| 0.230
ALCN-4792MISO| Dual Analog Loops| 0.130| 0.145
ALCN-792D| Quad Analog Loops| 0.130| 0.145
FNC-2000| Fire Network Controller Module| 0.190| 0.190
FOM-2000-UM| Fiber Optics Module| 0.015| 0.015
DM-1008A| 8 Initiating Circuit Module| 0.080| 1 zone active: 0.125
2 zone active: 0.170 4 zone active: 0.275 6 zone active: 0.370 8 zone active: 0.465
SGM-1004A| 4 Notification Appliance Circuit Module| 0.060| 0.258
RM-1008A| 8 Relay Circuit Module| 0.025| 0.150
FDX-008W/KI| Fan Damper Control Module| 0.015| 0.035
DSPL-420DS| Narrow Display| 0.025| 0.025
DSPL-420-16TZDS| Narrow Display w/ 16 additional LED Zones| 0.010| 0.046
DSPL-2440DS| Graphic Display| 0.025| 0.025
UDACT-300A| Dialer Module| 0.045| 0.120
PR-300| City Tie Module| 0.035| 0.300
FDS-008| Selection Control Panel for MNS| 0.024| 0.112
RAX-1048TZDS| Adder Annunciator Chassis| 0.022| 1 zone active: 0.026
2 zone active: 0.030
3 zone active: 0.035
4 zone active: 0.039
48 zone active: 0.262
RAM-1032TZDS| Adder Annunciator Chassis| 0.050| 32 zone active: 0.300
MGD-32| Main Graphic Driver Module| 0.035| 2.
AGD-048| Adder Graphic Driver Module| 0.035| # of LEDs x 4mA
IPS-2424DS| Programmable Input Switches Module| 0.005| 0.022
IPS- 4848DS| Programmable Input Switches Module| 0.010| 0.022
Audio Components
ANC-4000| Audio Network Controller Module| 0.255| 0.265
TNC-5000| Telephone Network Controller Module| 0.195| 0.215
OAA-5160-70125| 1 Zone 60W Amplifier| 0.055| 0.350
OAA-5230-70125| 2 Zone 30W Amplifier| 0.055| 0.350
OM-52305-70/25| 2 Zone 30W Amplifier (split)| 0.055| 0.350
OAA-5415-70| 4 Zone 15W Amplifier. 70V| 0.055| 0.350
OAA-5415-25| 4 Zone 15W Amplifier. 25V| 0.055| 0.350
OMP-5101N| Master Paging Module| 0.004| 0.012
OMP-5101NV| Vertical Master Paging Module| 0.004| 0.012
QMT-5302N| Master Telephone Module| 0.003| 0.013
OMT-5302NV| Vertical Master Telephone Module| 0.003| 0.013
CIAZT-5302DS| Paging/Telephone Zone Module| 0.005| 0.022
OAZT-5348DS| Paging/Telephone Zone Module| 0.010| 0.022

Electrical Specifications

Fire Alarm Primary Input Power| 120V 60Hz / 240V, 50Hz 4 Amps / 2 Amp (primary)
---|---
Power Supply Ratings| 12 Amps. max. (secondary)
For NAC Circuits| 24VDC unfiltered, 10 Amps. max.
Battery Type| 24VDC, Gel-CeIVSealed Lead-Add
Battery Charging Capability| 17-65 AH batteries
Audio Primary Input Power (QPS-5000N)| 120 VAC, 60Hz / 240 VAC, 50Hz 12 Amps

Dimensions for Annunciator Module Enclosures

Model Dimensions
BB-1001D 9″H x 12.75″W x 1.85″D
BB-1002D 18″H x 12.75″W x 1.85″D
BB-1003D 26.4″1-1 x 12.75″W x 1.85″D
BB-1008D 33″H x 22.5″W x 1.85″D
BB-1012D 45″H x 22.5″W x 1.85″D

Environmental

Operating Temperature 32°F to 120°F (0°C to 49C)
Humididty 10% – 93% non-condensing

Ordering Information

Model Description

Mass Notification Control Panels
FX-4000MNS| FLEXNET-MNS Main Network Board with 12 Amp power supply and 120/240V transformer.  Mounts in the BBX-FXMNS enclosure.
QMB-5000N| Integrated Audio Network Control Chassis.  Mounts in the BBX-FXMNS enclosure
PS-2040| FLEXNET-MNS Network Fire Alarm and Audio Power Supply (120/240V)
BBX-FXMNS| Black backbox enclosure  with white doors for FX-4000MNS. Add suffix ‘R’ for red doors. Add suffix ‘B’ for black doors.
DSPL-420DS| 4 x 20 Main LCD Display for FX-4000MNS
DSPL-420-16TZDS| 4 x 20 Main LCD Display for FX-4000MNS w/ Additional 16 LED Zones
DSPL-2440DS| Graphical Main Display for FX-4000MNS
FX-LOC| Local Operating Console enclosure for FLEXNET-MNS. Add suffix “R” for red door. Add suffix ‘B’ for black doors.
Paging/Telephone Modules
QMP-5101NV| Master Network Paging Control Module for FLEXNET-MNS, Vertical Mount. For use in BBX-FXMNS.
QMT-5302NV| Master Network Telephone Module for FLEXNET-MNS, Vertical Mount. For use in BBX-FXMNS.
QMP-5101N| Master Network Paging Control Module
QMT-5302N| Master Network Telephone Control Module
QAZT-5302DS| Paging and Telephone Selector Panel
QAZT-5348DS| Paging and Telephone Selector Panel
Network Controller Modules
FNC-2000| Fire Network Controller Module
FOM-2000-UM| Allows for single-mode or multi-mode fibre optic communication on a FLEXNET-MNS network. Add FOM-CONN-SM and FOM-CONN-MM
FOM-CONN-MM| Fibre Optic Module Connector Multi-mode (pack of 2). Must use a FOM-2000-UM
FOM-CONN-SM| Fibre Optic Connector Single Mode (pack of 2). Must use a FOM-2000-UM
ANC-4000| Audio Network Controller Module
TNC-5000| Telephone Network Controller Module
Adder Loop Controller Modules
ALCN-960MISO| Isolated Quad Loop Controller (for MIX-4000 Devices)
ALCN-960D| Daughter Board for ALCN-960MISO
ALCN-4792MISO| Network quad loop Module with isolator
ALCN-792D| Daughter board for ALC-4792MISO Quad Loop Controller Module with Isolator
Adder Hardwire Modules
DM-1008A| Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module
SGM-1004A| Four Class A/B (Style Z/Y) Notification Appliance Circuit Module (Rated at 1.7 Amps per circuit)
RM-1008A| Eight Relay Circuit Module c/w eight form C relays (Rated for 28 VDC @ 1 Amp max. per relay)
Adder Auxiliary Modules
UDACT-300A| Digital Alarm Communicator Transmitter/Dialer Module
PR-300| Polarity Reversal and City Tie Module
Remote Annunciators
RAXN-4000LCD| Remote Network LCD Annunciator c/w 4 x 20 LCD display
RAXN-4000LCDG| Remote Graphic  LCD Annunciator
RAM-1032TZDS| Main Remote LED Annunciator c/w 32 Bi-Colored LEDs
RAX-1048TZDS| Programmable LED Annunciator Module c/w 48 Bi-Coloured LEDs and 48 Trouble LEDs
Programmable Modules
IPS-2424DS| Programmable Input Switches Module c/w 24 selector switches and 24 bi-coloured LEDs
IPS-4848DS| Programmable Input Switches Module c/w 48 selector switches and 48 bi-coloured LEDs
FDX-008W| Fan Damper Control Module provides switch operation of 8 fan damper zones
FDX-008WKI| Fan Damper Control Module provides switch operation of 7 fan damper zones and one keyswitch operation of the 8th fan damper zone
Graphic Annunciator Driver Modules
MGD-32| Main Graphic Driver Module c/w 32 Supervised Outputs
AGD-048| Adder Graphic Driver Module c/w 48 Supervised Outputs
Audio Amplifiers
QAA-5415-70| 70 Volt Quad 15 Watt Amplifier
QAA-5415-25| 25 Volt Quad 15 Watt Amplifier
QAA-4CLA| Class ‘A’ (Style ‘Z’) Converter Module for QAA-5415-25 and QAA-5415-70 Amplifiers
QAA-5230S-70/25| 25 or 70 Volt Dual 30 Watt Amplifier split ‘A’ ‘B’ circuits per floor
QAA-4CLAS| Class ‘A’ (Style ‘Z’) Converter Module for QAA-5230S-70/25 and QAA- 5230S-525-70/25 Amplifiers
QAA-5230-70/25| 25 or 70 Volt Dual 30 Watt Amplifier
QAA-5160-70/25| 25 or 70 Volt 60 Watt Amplifier
Graphics Software

OGN-FLSLIC-ONE| Single Fire Alarm Control Panel License (Price per connection)
Requires: OGN-KEY (sold seperately) Contact us for non-Mircom panel connections
OGN-FLSLIC-EXP| Fire Alarm Control Panel License for 2-9 Connections (Price per connection)
Requires: OGN-KEY(sold seperately) Contact us for non-Mircom panel connections
OGN-FLSLIC-STD| Fire Alarm Control Panel License for 10-99 Connections (Price per connection)
Requires: OGN-KEY (sold seperately) Contact us for non-Mircom panel connections
OGN-FLSLIC-ENT| Fire Alarm Control Panel License for 100+ Connections (Price per connection)
Requires: OGN-KEY (sold seperately) Contact us for non-Mircom panel connections
OGN-KEY| OGN License Key Stick
Graphics Hardware
OGN-UL-STD| Industrial Rack Appliance /w UL/ULC Certification
OGN-TWR-STD| Industrial Tower/Rack Appliance /w Long Life & Stability
51-15063-001| 22″ Class Wide Desktop Monitor UL864 / ULC-S527-11 / UL 2572 Recognized LED Backlit (Monitor for OGN-UL-STD)
ARW-VESP211-KIT| 1-port Ethernet Serial Server Kit
ARW-2525-KIT| Industrial 5-PORT Unmanaged POE Switch Kit. Kit includes: 1 X 5-PORT Unmanaged POE Switch and 1 X 75W 48 VDC power supply
Power Supply Module
INX-10AC| Internal Booster Power Supply Module
Fire & Audio Expansion Components and Enclosures
FX-4009-12NDS| Large Network Main Chassis.  Mounts in the BB-5000 series enclosures.
ECX-0012| Expander Chassis for the FX-200912NDS.  Mounts in the BB-5000 series enclosures.
BB-5008| Lobby Control Wallbox Enclosure.  Supports 8 Module Footprints.
DOX-5008MB/R| Door for BB-5008 – “B” for Black and “R” for Red
CCH-5008-PANELKIT| Panel Mounting Kit for BB-5008- CCH-5008-ANNUNKIT
CCH-5008-ANNUNKIT| Annunciator Mounting Kit for BB-5008
BB-5014| Lobby Control Wallbox Enclosure.  Supports 14  Module Footprints.
DOX-5014MB/R| Door for BB-5014 – “B” for Black and “R” for Red
CCH-5014-PANELKIT| Panel Mounting Kit for BB-5014
CCH-5014-ANNUNKIT| Annunciator Mounting Kit for BB-5014
QBB-5001| Audio Backbox
QMB-5000B| Audio Motherboard and Card Cage
QPS-5000N| Audio Power Supply (120/240V)
QBC-5000N| Audio Battery Charger
BB-1001D/DR/DS/DB| Remote Annunciator Enclosure Houses one module. “D” White, “DR” Red, “DS” Stainless Steel, or “DB” for Black Door.
BB-1002D/DR/DS/DB| Remote Annunciator Enclosure Houses two module. “D” White, “DR” Red, “DS” Stainless Steel, or “DB” for Black Door.
BB-1003D/DR/DS/DB| Remote Annunciator Enclosure Houses three module. “D” White, “DR” Red, “DS” Stainless Steel, or “DB” for Black Door.
BB-1008D/DR/DB| Remote Annunciator Enclosure Houses eight modules. “D” White, “DR” Red or “DB” for Black Door.
BB-1012D/DR/DB| Remote Annunciator Enclosure Houses twelve modules. “D” White, “DR” Red or “DB” for Black Door.
BB-1001WP(R)A| Weather Protected Enclosure Enclosure Houses one module. White. BB-1001WPRA for red.
BB-1002WP(R)A| Weather Protected Enclosure Enclosure Houses two module. White. BB-1002WPRA for red.
Mounting Brackets
M500-BK-9| M500 Series Mounting Bracket.  Holds up to 9 modules in a BB-5000 Series enclosure.
M500-BK-2| M500 Series Mounting Bracket.  Holds up to 2 modules in a BBX-FXMNS enclosure.

Canada
25 Interchange Way Vaughan, ON L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
www.mircom.com THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO DESCRIBE THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance, installation, testing and certification, refer to technical literature. This document contains intellectual property of Mircom. The information is subject to change by Mircom without notice. Mircom does not represent or warrant correctness or completeness. All rights reserved. All other trademarks and registered trademarks are properties of their respective owners.

Mircom logo 1 NOT TO BE USED FOR INSTALLATION PURPOSES.
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND
NOT INTENDED TO DESCRIBE THE PRODUCTS TECHNICALLY.
firealarmresources.com
CAT. 5985

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals