MGC MIX-4040 Dual Input Module
ABOUT THIS MANUAL
This manual is included as a quick reference for installation. For fur-ther
information on the use of this device with a FACP, please refer to the panel’s
manual.
Note: This manual should be left with the owner/operator of this
equipment.
MODULE DESCRIPTION
The MIX-4040 Dual Input module is designed to operate with a listed compatible intelligent fire system control panel. The module can sup-port one Class A or 2 Class B inputs. When configured for Class A operation, the module provides an internal EOL resistor. When con-figured for Class B operation, the module can monitor two indepen-dent input circuits while using only one module address. The address of each module is set using the MIX-4090 programmer tool and up to 240 units may be installed on a single loop. The module has a panel controlled LED indicator.
FIGURE 1 MODULE FRONT
MOUNTING
Notice: You must disconnect power from the system before installing the module. If this unit is being installed in a system that is currently operational, it is necessary to inform the operator and the local authority that the system will be temporarily out of service. The MIX-4040 module is intended to be mounted in a standard 4” square back-box (see Figure 2). The box must have a minimium depth of 2 1/8 inches. Surface mounted electrical boxes (BB-400) are available from Mircom.
FIGURE 2 MODULE MOUNTING:
SPECIFICATIONS
- Normal Operating Voltage: 15 to 30VDC
- Alarm Current: 3.3mA
- Standby Current: 2mA with two 22k EOL
- EOL Resistance: 22k Ohms
- Maximum Input Wiring Resistance: 150 Ohms total
- Temperature Range: 32F to 120F (0c to 49C)
- Humidity: 10% to 93% Non-condensing
- Dimensions: 4 5/8”H x 4 1/4” W x 1 1/8” D
- Mounting: 4” square by 2 1/8” deep box
- Accessories: MIX-4090 Programmer. BB-400 Electrical Box MP-302 EOL on mounting plate
- Wiring range on all terminals: 22 to 12 AWG
WIRING
Note: This device should be installed as per applicable requirements of the authorities having jurisdiction. This device shall be connected to power limited circuits only.
- Install the module wiring as indicated by the job drawings and appropriate wiring diagrams (see Figure 3 for an example of wring for a Class A connected device and Figure 4 for an example of Class B)
- Use the programmer tool to set the address on the module as indicated on the job drawings.
- Mount the module in the electrical box as shown in figure 2.
FIGURE 3 SAMPLE CLASS A WIRING:
FIGURE 4 SAMPLE CLASS B WIRING: