Mircom XAL-53 Explosion Proof Fire Alarm Station Owner’s Manual

June 9, 2024
Mircom

Mircom-LOGO

Mircom XAL-53 Explosion Proof Fire Alarm Station

EXPLOSION-PROOF FIRE ALARM STATION
XAL-53

Operation

The Killark XAL-53 Explosion-Proof Fire Alarm Station is activated by lifting the front cover and pulling down the ring. This quick, easy-to-use two-step process prevents unintentional operation. The unit is reset by depressing the shaft and returning the plate to the original position.

Applications

  • Hazardous areas due to the presence of flammable gases or vapors, combustible dusts or easily ignitable fibers or flyings
  • Installation at petroleum refineries, chemical and petrochemical plants, storage areas, and other processing facilities where hazardous substances are handled and stored
  • Areas where emergency control of fire alarm or signal circuits is required.

Features

  • Enclosure is made of copper free aluminum alloy
  • Conduit openings are 3/4” NPT feed through
  • Red, textured powder epoxy paint finish is standard on box and cover and provides high visibility for alarm station
  • Bilingual nameplates included per CSA requirement
  • Internal ground screw is standard

Hazardous Area Classifications

  • Class I, Divison 1 and 2, Group C and D.
  • Class l, Zones 1 & 2, Groups llB, llA
  • Class II, Division 1 and 2, Group E, F, and G.
  • Class III
  • NEMA 7 (C,D) 9 (E,F,G).

Dimensions

Contact Block Rating

AC DC

Volts

| Make Amperes| ****

VA

| Break Amperes| ****

VA

| Continous Carrying Amperes| ****

Volts

| Make Break| Continuous Carrying Amperes
120| 60| 7200| 6| 720| 10| 125| 1.1| 2.5
240| 30| 7200| 3| 720| 10| 250| 0.55| 2.5
480| 15| 7200| 1.5| 720| 10| 600| 0.2| 2.5
600| 12| 7200| 1.2| 720| 10| —| —| —

Ordering Information

Model Description
XAL-53 Explosion-Proof Manual Fire Alarm Station

NOT TO BE USED FOR INSTALLATION PURPOSES.

Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone: 905-660-4655 Fax: 905-660-4113
Web page: http://www.mircom.com
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655 Fax Toll Free: 888-660-4113
Email: mail@mircom.com
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>