EXPLOSION-PROOF FIRE ALARM STATION
XAL-53
Operation
The Killark XAL-53 Explosion-Proof Fire Alarm Station is activated by lifting the front cover and pulling down the ring. This quick, easy-to-use two-step process prevents unintentional operation. The unit is reset by depressing the shaft and returning the plate to the original position.
Applications
- Hazardous areas due to the presence of flammable gases or vapors, combustible dusts or easily ignitable fibers or flyings
- Installation at petroleum refineries, chemical and petrochemical plants, storage areas, and other processing facilities where hazardous substances are handled and stored
- Areas where emergency control of fire alarm or signal circuits is required.
Features
- Enclosure is made of copper free aluminum alloy
- Conduit openings are 3/4” NPT feed through
- Red, textured powder epoxy paint finish is standard on box and cover and provides high visibility for alarm station
- Bilingual nameplates included per CSA requirement
- Internal ground screw is standard
Hazardous Area Classifications
- Class I, Divison 1 and 2, Group C and D.
- Class l, Zones 1 & 2, Groups llB, llA
- Class II, Division 1 and 2, Group E, F, and G.
- Class III
- NEMA 7 (C,D) 9 (E,F,G).
Dimensions
Contact Block Rating
AC | DC |
---|
Volts
| Make Amperes| ****
VA
| Break Amperes| ****
VA
| Continous Carrying Amperes| ****
Volts
| Make Break| Continuous Carrying Amperes
120| 60| 7200| 6| 720| 10| 125| 1.1| 2.5
240| 30| 7200| 3| 720| 10| 250| 0.55| 2.5
480| 15| 7200| 1.5| 720| 10| 600| 0.2| 2.5
600| 12| 7200| 1.2| 720| 10| —| —| —
Ordering Information
Model | Description |
---|---|
XAL-53 | Explosion-Proof Manual Fire Alarm Station |
NOT TO BE USED FOR INSTALLATION PURPOSES.
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone:
905-660-4655 Fax:
905-660-4113
Web page: http://www.mircom.com
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655 Fax Toll Free:
888-660-4113
Email: mail@mircom.com
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>