Description
- Mircom’s INX-10A is an Intelligent NAC expander/ power supply that works with listed compatible Intelligent fire alarm control panels. Available in a 10 Amp configuration, the INX-10A can extend the power capabilities of existing notification appliance circuits as well as provide power for other ancillary devices. In addition, the INX-10A has the ability to operate with any UL/ULC Listed 24 VDC fire alarm control panel to provide Notification Appliance Circuit expansion.
- The INX-10A is equipped with five individual Class B (Style Y) or Class A (Style Z) output circuits that can be independently configured for NAC operation or auxiliary power. The INX-10A provides the option of configuring all five circuits as an output to provide general purpose power. In addition output circuits four and five can be configured to provide auxiliary power for four-wire detectors or door holders.
- Each output circuit is rated for 2.5 Amps. When configured for NAC operation the outputs can be set for Steady, Temporal Code, California Code or March Time. In addition the output circuits have field selectable built-in strobe and horn synchronization protocols to support Amseco, System Sensor, Wheelock and Gentex devices, eliminating the need for additional external synchronization modules.
Features
- 10 Amp output
- 120 / 240V operation
- Works with listed compatible Series Intelligent Fire Alarm Control Units
- Easily configured using DIP switches
- One isolated input from the host panel
- Five Class B (Style Y) or Class A (Style Z) synchronized output circuits
- DC regulated outputs
- Configurable AC Power fail delay
- Ground fault enable or disable
- Option available on configuration to enable or disable the battery charger on activation
- From 7 to 15 Address functions (Combination of inputs and outputs, depending on the application)
- Outputs individually controllable
- Separate Relay for Ground Fault and Common Trouble available on terminals
- Horn/Strobe synchronization protocols include Amseco, Gentex, System Sensor and Wheelock
- Two-wire horn/strobe Sync Mode allows audible notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate
- Audible signals may be configured for Steady, Temporal Code, California Code and March Time
- Output circuits four and five can be configured to provide auxiliary power for four-wire detectors or door holders.
- Canadian two stage operation
- Output fault notification to fire alarm control panel
- Ability to sync outputs for multiple INX-10A units
- 2.5 Amp max. current per output
- 1.7 Amp auxiliary power output
- Built-in charger for sealed lead acid or gel type batteries
- Unit includes power supply, charger, red door, black backbox, transformer and battery leads
- Compatible with any UL/ULC listed 24VDC conventional fire alarm control panel to provide Notification Appliance Circuit expansion
Modes of Operation
-
Intelligent NAC Expander (INX) Modes
The INX-10A features three modes of NAC Expander operation:- INX Mode with Internal Sync
- INX Mode with External Sync
- INX Mode with Redundant Input
-
Input Mode with Internal Sync
In this mode all signal and sync strobe rates are produced in the INX-10A. -
INX Mode with External Sync
When one of the Sync Inputs is activated, the INX-10A outputs follow the signal pattern of the Sync Input. The NX-10A must be configured as a slave to operate in this mode. -
INX Mode with Redundant Input
The system continuously monitors the SLC loop. If there is no activity for a notable time, an SLC trouble is generated. While the SLC trouble is active, if either of the Sync Inputs are activated then all NAC outputs follow. -
Power Supply Modes
In addition to the NAC expander modes, some or all of the NAC outputs on the INX-10A can be configured for the following power supply modes of operation:- NAC Outputs as Power Supply Outputs
- NAC Outputs for Door Release
- NAC Outputs for 4-Wire Smoke Supply
-
NAC Outputs as Power Supply Outputs
This mode allows any NAC output to be configured as a power supply. The SLC and Sync inputs are ignored for the power supply outputs. -
NAC Outputs for Door Release
This mode allows NAC circuits 4 and/or 5 to provide power for door holders. -
NAC Outputs for 4-Wire Smoke Supply
This mode allows NAC circuits 4 and/or 5 to provide auxiliary power for 4-wire smoke detectors.
Specifications
Dimensions
20”H x 14½”W x 4½”D
AC Line Voltage
120V 60Hz / 240V, 50Hz, 2 Amps / 1 Amp (primary)
NAC Circuits
24VDC regulated, Power Limited 10A Total, 2.5A maximum per circuit
Battery
24VDC, Gel-Cell/Sealed Lead-Acid
Charging Capability
Up to 40 AH batteries
Current Consumption from INX-10(A) Power Supply
Standby| 200 mA
Alarm| 350 mA
Current Consumption from Compatible FACP
4.5mA
Common Indicators
Power On
Addressable Line Activity/Alarm Common Trouble
Battery Charger/Trouble CPU Fail
Trouble LEDs
Auxiliary Output Trouble Synchronized Output Trouble Ground Fault Trouble
Other LEDs
Addressable (SLC) Loop Indicators (3 LEDs) Synchronized Input Indicators (2
LEDs) Synchronized Output Indicators (2 LEDs) Trouble LED Indicator Alarm
Relay Indicator
Controls
Acknowledge Button Configuration DIP Switches
Current Consumption from Compatible FACP
4.5mA
Ordering Information
Model | Description |
---|---|
INX-10A | Intelligent NAC Expander, 10 Amps c/w backbox and red door |
INX-10AC | Intelligent NAC Expander, 10 Amps Addressable Chassis Mounts into |
BB-5008 or BB-5014 enclosure
THIS INFORMATION IS FOR MARKETING PURPOSES ONLY AND NOT INTENDED TO
DESCRIBE THE PRODUCTS TECHNICALLY.
For complete and accurate technical information relating to performance,
installation, testing and certification, refer to technical literature. This
document contains intellectual property of Mircom. The information is subject
to change by Mircom without notice. Mircom does not represent or warrant
correctness or completeness.
Canada
25 Interchange Way Vaughan, Ontario L4K 5W3 Telephone:
905-660-4655 Fax:
905-660-4113
www.mircom.com
U.S.A.
4575 Witmer Industrial Estates Niagara Falls, NY 14305
Toll Free: 888-660-4655 Fax Toll Free:
888-660-4113
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>