MIX-M502MAPA Intelligent Monitor Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
MIX-M502MAPA Interface Module
Specifications
Normal Operating Voltage: | 15 to 32 VDC |
---|---|
Maximum Alarm Current: | 5.1mA (LED on) |
Average Operating Current: | 400µA, 1 communication and 1 LED flash every 5 |
seconds, 3.9k eol
EOL Resistance:| 3.9K Ohms
Maximum IDC wiring resistance:| 25 Ohms
IDC Supply Voltage (between Terminals T3 and Regulated DC Voltage:| 24 VDC
power limited
Ripple Voltage:| 0.1 Volts RMS maximum
Current:| 90mA per module
Temperature Range:| 32˚F to 120˚F (0˚C to 49˚C)
Humidity:| 10% to 93% Non-condensing
Dimensions:| 4 1 ⁄2˝ H x 4˝ W x 1 1 ⁄4˝ D (Mounts to a 4˝ square by 2 1 ⁄8˝
deep box.)
Accessories:| SMB500 Electrical Box
Before Installing
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of
service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The MIX-M502MAPA Interface Module is intended for use in intelligent, two-wire
systems, where the individual address of each module is selected using the
built-in rotary ecade switches. This module allows intelligent panels to
interface and monitor two-wire conventional smoke detectors. It transmits the
status (normal, open, or alarm) of one full zone of conventional detectors
back to the control panel. All two-wire detectors being monitored must be ULC
compatible with this module. The MIX-M502MAPA has a panel controlled LED
indicator. Compatibility Requirements To ensure proper operation, these
modules shall be connected to listed compatible system control panels only.
Mounting The MIX-M502MAPA mounts directly to 4˝ square electrical boxes (see
Figure 2A).
The box must have a minimum depth of 2 ⁄8˝. Surface mounted electrical boxes
(SMB500) are available from Mircom.
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
This module is intended for power-limited wiring only.
- Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
- Set the address on the module per job drawings.
- Secure module to electrical box (supplied by installer), as shown in Figure 2A.
Compatible Two-wire System Sensor Smoke Detectors for Use with MIX-M502MAPA
with Zone Identifier A:
Detector| Compatibility| Detector| Base| Base|
Max
---|---|---|---|---|---
Model| ID| Type| Model| Identifier| Detectors
1451A| A| Ionization| B401/BA| A| 20
2451A| A| Photoelectric| B401/BA| A| 20
2451THA| A| Photoelectric with Thermal| B401/BA| A| 20
1400A| A| Ionization| N/A| —| 20
2400A| A| Photoelectric| N/A| —| 20
2400THA| A| Photoelectric with Thermal| N/A| —| 20
1151A| A| Ionization| B110LPA/B401A| A| 20
2151A| A| Photoelectric| B110LPA/B401A| A| 20
Figure 3. Interface two-wire conventional detectors, NFPA Style B:
*NOTE: ANY FAULT IN THE POWER
SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE
ZONE.
Figure 4. Interface two-wire conventional detectors, NFPA Style D:
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT
RESULT IN A FAULT IN A SEPARATE ZONE.
Figure 5. Relay control module used to disconnect a power supply:
MC-460-012 2 I56-3326-000
© 2008 Mircom
firealarmresources.com
Documents / Resources
|
Mircom MIX-M502MAPA Intelligent Monitor
Module
[pdf] Instruction Manual
MIX-M502MAPA Intelligent Monitor Module, MIX-M502MAPA, Intelligent Monitor
Module, Monitor Module, Module
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>