Mircom MIX-M502MAPA Intelligent Monitor Module Instruction Manual

June 9, 2024
Mircom

Mircom Logo 25 Interchange Way, Vaughan Ontario, L4K 5W3
Phone: 905.660.4655; Fax: 905.660.4113

MIX-M502MAPA Intelligent Monitor Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS
MIX-M502MAPA Interface Module

Specifications

Normal Operating Voltage: 15 to 32 VDC
Maximum Alarm Current: 5.1mA (LED on)
Average Operating Current: 400µA, 1 communication and 1 LED flash every 5

seconds, 3.9k eol
EOL Resistance:| 3.9K Ohms
Maximum IDC wiring resistance:| 25 Ohms
IDC Supply Voltage (between Terminals T3 and  Regulated DC Voltage:| 24 VDC power limited
Ripple Voltage:| 0.1 Volts RMS maximum
Current:| 90mA per module
Temperature Range:| 32˚F to 120˚F (0˚C to 49˚C)
Humidity:| 10% to 93% Non-condensing
Dimensions:| 4 1 ⁄2˝ H x 4˝ W x 1 1 ⁄4˝ D (Mounts to a 4˝ square by 2 1 ⁄8˝ deep box.)
Accessories:| SMB500 Electrical Box

Before Installing
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Disconnect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
General Description
The MIX-M502MAPA Interface Module is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary  ecade switches. This module allows intelligent panels to interface and monitor two-wire conventional smoke detectors. It transmits the status (normal, open, or alarm) of one full zone of conventional detectors back to the control panel. All two-wire detectors being monitored must be ULC compatible with this module. The MIX-M502MAPA has a panel controlled LED indicator. Compatibility Requirements To ensure proper operation, these modules shall be connected to listed compatible system control panels only.
Mounting The MIX-M502MAPA mounts directly to 4˝ square electrical boxes (see Figure 2A).
The box must have a minimum depth of 2 ⁄8˝. Surface mounted electrical boxes (SMB500) are available from Mircom.
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and regulations.
This module is intended for power-limited wiring only.

  1. Install module wiring in accordance with the job drawings and appropriate wiring diagrams.
  2. Set the address on the module per job drawings.
  3. Secure module to electrical box (supplied by installer), as shown in Figure 2A.

Mircom MIX M502MAPA Intelligent Monitor Module - Figure
1
Compatible Two-wire System Sensor Smoke Detectors for Use with MIX-M502MAPA with Zone Identifier A:

Detector| Compatibility| Detector| Base| Base| Max
---|---|---|---|---|---
Model| ID| Type| Model| Identifier| Detectors
1451A| A| Ionization| B401/BA| A| 20
2451A| A| Photoelectric| B401/BA| A| 20
2451THA| A| Photoelectric with Thermal| B401/BA| A| 20
1400A| A| Ionization| N/A| —| 20
2400A| A| Photoelectric| N/A| —| 20
2400THA| A| Photoelectric with Thermal| N/A| —| 20
1151A| A| Ionization| B110LPA/B401A|  A| 20
2151A| A| Photoelectric| B110LPA/B401A|  A| 20

Figure 3. Interface two-wire conventional detectors, NFPA Style B:
Mircom MIX M502MAPA Intelligent Monitor Module - Figure
2 *NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
Figure 4. Interface two-wire conventional detectors, NFPA Style D:

Mircom MIX M502MAPA Intelligent Monitor Module - Figure
3

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
Figure 5. Relay control module used to disconnect a power supply:

Mircom MIX M502MAPA Intelligent Monitor Module - Figure
4

MC-460-012 2 I56-3326-000
© 2008 Mircom
firealarmresources.com

Documents / Resources

| Mircom MIX-M502MAPA Intelligent Monitor Module [pdf] Instruction Manual
MIX-M502MAPA Intelligent Monitor Module, MIX-M502MAPA, Intelligent Monitor Module, Monitor Module, Module
---|---

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mircom User Manuals

Related Manuals