Mircom FX-2000 SERIES Intelligent Fire Alarm Control Panel Owner’s Manual
- June 9, 2024
- Mircom
Table of Contents
- Description
- Features
- Operation
- Input Correlations
- FX-2000 Standard Series
- Adder Auxiliary Modules
- Adder Hardwire Modules
- Programmable Modules
- Electrical Ratings
- Remote Annunciators
- Graphic Annunciator Driver Modules
- Enclosures
- Typical FX-2000 Panel Wiring Class B (Style 4)
- Ordering Information
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
FX-2000 SERIES Intelligent Fire Alarm Control Panel
Owner’s Manual INTELLIGENT FIRE ALARM CONTROL
PANEL
FX-2000 SERIES
Description
Mircom’s FX-2000 Series Microprocessor Based Intelligent Fire Alarm Control
Panel is designed to provide maximum flexibility of analog system requirements
while also providing easy installation and operation at a cost-effective
price. The FX-2000 base panel consists of one intelligent analog loop
controller capable of supporting 99 Analog Sensors and 99 Addressable Modules
which can be wired in Class A (Style 6 or 7) or Class B (Style 4). The system
can be expanded by adding additional Analog Loop Controller Modules. In
addition the base panel supports 16 conventional hardwire adder modules such
as the DM-1008A Initiating Circuit Module, SGM1004A Indicating Circuit Module
and the RM-1008A Relay Circuit Module. Additional conventional hardwire adder
modules can be added with the ALC-H16 Adder Hardwire Loop Controller Module,
which allows the system to support an additional 16 conventional adder
modules. The base panel also consists of 4 Class A/B (Style Z/Y) Indicating
Circuits rated at 1.7 Amps each and either a 6 or 12 Amp Power Supply.
Equipped with a large 4 x 20 Back-lit Alphanumeric LCD display, the FX-2000
utilizes a simple Menu system complete with a directional keypad, common
control switches and LEDs, Alarm Queue switches and LEDs and two configurable
input switches.
Features
- Listed to UL 864, 9th edition
- Large system capacity
- Modular design
- Each Analog Loop is capable of supporting 99 Analog Sensors and 99 Addressable Modules which can be wired in Class A (Style 6 or 7) or Class B (Style 4)
- Base system supports 16 conventional hardwired modules with the provision to add more using the ALC-H16 Hardwire Loop Controller Module
- 6 or 12 Amp power supply
- Four Class A/B (Style Z/Y) Indicating Circuits rated at 1.7 Amps each
- Configurable for Two Stage operation
- Three level password protection with field programmable definition which enables the installer to determine what functions are accessible for each password level
- Panel Security to protect site configurations
- Manual Control Enable which allows password protection for all front panel function switches
- Correlatable Switch Inputs which allows for multifunctional outputs
- Four Alarm Queues with selector switches and LEDs for Alarm, Supervisory, Monitor and Trouble
- Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble
- RS-232 output for remote system printer or CRT
- Two Event History Logs comprised of a 1000 Alarm History Log for alarm related events and a 2000 Event Log for all events
- Front Panel Auto-Configure and/or Computer laptop Programmable
- Large 4 by 20 character Back-lit LCD Display with user friendly menu
- Common Control switches and/or indicating LEDs for System Reset, Signal Silence, Fire Drill, Acknowledge, General Alarm, Lamp Test, A.C. On, Pre-Alarm and Ground Fault
- Built-in One Man Walk Test operation
- Configurable for Coded Operation
- Supports an RS-485 interface to the QX-5000 Voice Evacuation System
- Panel selection for Canadian (ULC) or U.S.A. (UL) requirements for smoke sensors (sensitivity) via computer laptop
- Capability to adjust Intelligent Smoke Detector sensitivity level
NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in
prices, colours, materials, components, equipment, specifications and models
and also to discontinue models.
firealarmresources.com
Operation
The FX-2000 is field programmable via the front panel auto configuration or a
laptop computer. In addition, it allows for a three level password protection
that can be field defined via a laptop computer. This unique feature allows
the installer to determine what functions are accessible for each password
level.
The system is also equipped with two Event History Logs; one for Alarm and the
other for full panel sequence events. The Alarm History Log (1000 events)
contains all alarm related functions while the Event Log (2000 events)
provides a full sequence log of all operations, as well as alarms and
troubles.
Both Event History Logs can be used during the One Man Walk Test operation.
This allows the event logs to be downloaded to a laptop or printer for a
permanent record.
The FX-2000 is a very flexible system which supports both internal and
external annunciation modules. The internal annunciation modules consist of
the RAX-1048TZDS Programmable Zone LED Annunciator, the IPS-2424DS
Programmable Input Switches Module, the FDX-008 Fan Damper Module and the
AGD-048 Adder Graphic Driver Module.
Input Correlations
All input circuits (addressable or hardwired) can be configured for non-
verified alarm, verified alarm, waterflow, latching/non-latching supervisory,
monitor, trouble only or remote switch inputs. All of the input configuration
types listed above, with the exception of remote switch can be programmed to
operate relays, signal and strobe circuits for hardwired or addressable
devices. Please refer to the chart below for correlations. The input circuits
configured as nonlatching will cause the output circuits configured to them to
follow the state of the input device. This feature allows for the connection
of multiple panels together for signal operation.
All of these modules mount within the panel and are driven from the main LCD
display. The external annunciator modules include the RAM-1032TZDS and RAX-
1048TZDS LED Remote Annunciators, the MGD-32 Master Graphic Driver Module, and
the RAX-LCD Remote LCD Shared Display. The RAX-LCD Remote LCD Shared Display
provides the same features as the main display on the FX-2000.
In addition the RAX-LCD also acts as a driver module that allows for the RAX-
1048TZDS, IPS-2424DS, FDX-008 and AGD-048 to be connected to it. The RAX-LCD
is required as a driver module any time any of the above mentioned external
annunciator modules are programmed differently from those on the main panel or
are mounted remote from the main panel.
In addition to these adder modules, the FX-2000 also supports the UDACT-300A
Digital Communicator Module and the PR-300 Polarity Reversal/City Tie Module.
The FX-2000 also supports an RS-485 interface to the QX-5000 Emergency Zoned
Audio System.
The Remote Switch input, which must be momentary, allows any input type device
(addressable or hardwired) to be configured as a common control functions such
as fire drill, system reset, signal silence etc. The remote switches operate
in a momentary mode like the control switches on the FX2000 main panel. For
functions such as fire drill, the remote switch functions in a toggle mode,
with one press for “on” and one press for “off”. The remote switch is
supervised for “stuck in on” positions, where the switch input is activated
(stuck) for more than 30 seconds. If this occurs, a trouble is generated and
clears when the input goes away.
Intelligent or Conventional Input Types | Output | Control Switches |
---|---|---|
Relay | Signal | Strobe |
Non-Verified Alarm | Yes | Yes |
Verified | Yes | Yes |
Waterflow | Yes | Yes |
Non-Latching Supervisory | Yes | Yes |
Latching Supervisory | Yes | Yes |
Monitor | Yes | Yes |
Trouble Only | Yes | Yes |
Remote Switch Input | No | No |
FX-2000 Standard Series
FX-2003-6DS/FX-2003-12DS Compact Main Control Units
The FX-2003-6DS and FX-2003-12DS Compact Main Control Units come complete with
one Intelligent Signaling Line Circuit, Four Style Z/Y (Class A/B)
Notification Appliance Circuits rated at 1.7 Amps each and a 4 line by 20
character back-lit LCD display. The FX-2003-6DS is equipped with a 6 Amp Power
Supply which charges 10-24 AH batteries while the FX-2003-12DS includes a 12
Amp Power Supply which charges 17-55 AH batteries. The
FX-2003-6DS/FX-2003-12DS provides space for 3 adder modules and 2 internal
annunciator adder modules. The FX-2003-6DS/FX-2003-12DS mount in a UB-1024DS
backbox. FX-2003-6DS-16LED Compact
Main Control Unit
The FX-2003-6DS-16LED Compact Main Control Unit come complete with one
Intelligent Signaling Line Circuit, Four Style Z/Y (Class A/B) Notification
Appliance Circuits rated at 1.7 Amps each and a 4 line by 20 character back-
lit LCD display with 16 LEDS for annunciation (DSPL-420-16TZDS). This display
is functionally equivalent to the classic FX-2000 main display, but more
compact adding in the 16 LEDs for annunciation in addition to all the standard
functions.The FX-2003-6DS-16LED is equipped with a 6 Amp Power Supply which
charges 10-24 AH batteries. The FX-2003-6DS-16LED provides space for 3 adder
modules and 2 internal annunciator adder modules. The FX-2003-6DS-16LED mounts
in a separate ordered UB-1024DS Backbox. FX-2017-12ADS Mid-Size Main Control
Unit
The FX-2017-12ADS Mid-Size Main Control Unit comes complete with one
intelligent Signaling Line Circuit (SLC) Four Style Z/Y (Class A/B) NAC
Circuits (1.7 Amps each), a 4 line by 20 character back-lit LCD display and a
12 Amp Power Supply which charges 17-55 AH batteries. The FX-2017-12ADS has
space for up to 17 adder modules and 3 internal annunciator adder modules. The
FX-2017-12ADS mounts in the BBX-1072ADS enclosure. FX-2009-12DS Large Size Main Control Unit
The FX-2009-12DS Large Size Main Control Unit comes complete with one Analog
Loop Controller (99 Analog Sensors and 99 Addressable Modules), 4 Class A/B
(Style Z/Y) Indicating Circuits (1.7 Amps each), a 4 line by 20 character
back-lit LCD display and a 12 Amp Power Supply which charges 17-55 AH
batteries. The FX-2009-12DS supports 16 conventional adder modules and
provides space for up to 9 adder modules and 3 internal annunciator adder
modules. The FX-2009-12DS mounts in the BB-5000 Series enclosures. ECX-0012 Expander Chassis
The ECX-0012 Expander Chassis for the FX-2009-12DS/FX-2009S-12 supports up to
12 adder modules and has space for 2 internal annunciator modules. The
ECX-0012 mounts in the BB-5000 series enclosures.
FX-2000 Standard Series System Maximums
- 495 Input Circuits
- 150 Output Circuits
- 5 Intelligent Addressable Loops
- 4 Remote LCD Annunciators
- 4 Main LED Annunciators
- 100 Manual Control Switches
Adder Loop Controller Modules ALC-
198S Single Analog Loop Controller Module
The ALC-198S Single Analog Loop Controller Module provides an additional
analog loop to the FX-2000 consisting of 99 Analog Sensors and 99 Addressable
Modules. The ALC-198S occupies one module slot in the FX-2000 main or expander
chassis. ALC-396S Dual Analog Loop
Controller Module
The ALC-396S Dual Analog Loop Controller Module provides two additional analog
loops to the FX-2000 consisting of 99 Analog Sensors and 99 Addressable
Modules per loop. The ALC-396S occupies one module slot in the FX-2000 main or
expander chassis.![Mircom FX-2000 SERIES Intelligent Fire Alarm Control Panel
- fig 8](https://manuals.plus/wp-content/uploads/2023/03/Mircom-FX-2000 -SERIES-Intelligent-Fire-Alarm-Control-Panel-fig-8.png)
ALC-H16 Hardwire Loop Controller Module
The ALC-H16 Hardwire Loop Controller Module allows the FX-2000 to support an
additional sixteen (16) conventional hardwire adder modules. The hardwire
modules consist of the DM-1008 Eight Initiating Circuit Module, SGM1004 Four
Indicating Circuit Module and the RM-1008 Eight Relay Circuit Module. The
ALC-H16 occupies
one module slot in the FX-2000 main or expander chassis.
Adder Auxiliary Modules
UDACT-300A Digital Alarm Communicator Module
The UDACT-300A Digital Alarm Communicator Module allows the FX-2000 to
transmit addressable point information to a central station. The UDACT-300A
can be configured locally via the on-board keypad and the CFG-300
Configuration Tool or with a UIMA programming tool and a computer with an
available serial or USB port. The UDACT300A occupies one module slot in the
FX-2000 main or expander chassis.
Adder Hardwire Modules
DM-1008A Eight Initiating Circuit Module
The DM-1008A provides 8 Class B (Style B) or 4 Class A (Style D) Initiating
Circuits configurable for Alarm, Supervisory or Trouble zones. The DM-1008A
occupies one module slot in the FX-2000 main or expander chassis. SGM-1004A
Four Indicating Circuit Module
The SGM-1004A provides 4 Class A/B (Style Z/Y) Indicating Circuits
configurable as Silenceable or Non-Silenceable. Each Indicating Circuits is
rated at 1.7 Amps. Each of the indicating circuits have individual signal
silence inputs which are jumper selectable. The SGM-1004A occupies one module
slot in the FX-2000 main or expander chassis. RM-1008A Eight Relay Circuit Module
The RM-1008A provides the FX-2000 with 8 individual configurable relays per
module. Each relay provides one Form C contact rated at 28 VDC @1 Amp
(resistive load). The RM-1008A occupies one module slot in the FX-2000 main or
expander chassis. ![Mircom FX-2000 SERIES Intelligent Fire Alarm Control Panel
- fig 13](https://manuals.plus/wp-content/uploads/2023/03/Mircom-FX-2000
-SERIES-Intelligent-Fire-Alarm-Control-Panel-fig-13.png) PR-300 Polarity
Reversal/City Tie Module
The PR-300 Polarity Reversal/City Tie Module provides the system with a supervised City Tie (24 VDC/200 mA max.) and Polarity Reversal connection (24 VDC (open
circuit), 8 mA max. (shorted)). The PR-300 mounts in the FX-2000 main chassis.
Programmable Modules
RAX-1048TZDS Programmable Zone LED Annunciator Module
The RAX-1048TZDS Programmable Zone LED Annunciator Module provides 48
programmable bicoloured LEDs. The RAX-1048TZDS connects to the main panel or
the RAX-LCD Shared Display when mounted remotely. The RAX-1048TZDS occupies
one display position in the BB-1000 or BB-5000 enclosures.
FDX-008 Fan Damper Module
The FDX-008 Fan Damper Module provides individually programmed circuits which
can be used for fan or damper control. Each circuit has a slide-in label, a
three position selector switch, green “run or open” LED and an amber “off or
closed” LED. The three-position selector switch has a centre “auto” position,
a left “off or close” position and a right “on or open” position. The FDX008
connects to the main panel or the RAX-LCD when mounted remotely. It uses MIX-
M500CH for control of fans or dampers
and two MIX-M501A for status. The FDX-008 occupies one display position in the
BB-1000 or BB-5000 enclosures. IPS-
2424DS Programmable Input Switches Module
The IPS-2424DS Programmable Input Switches Module provides 24 programmable
switches that can be configured for ancillary functions such as zone bypass or
added common control functions. The switches operate in a toggle operation
with one press for “on” and one press for “off”. The IPS-2424DS connects to
main panel or the RAX-LCD when mounted remotely. The IPS-2424DS occupies one
display position in the BB-1000 or BB-5000 enclosures.
Electrical Ratings
Current Consumption
Model | Standby | Alarm |
---|---|---|
FX-2003-6DS-16LED | 230 mA | 380 mA |
FX-2003-6DS
FX-2003-12DS| 230 mA| 380 mA
FX-2017-12ADS| 230 mA| 380 mA
FX-2009-12DS| 230 mA| 380 mA
ALC-198S/ALC-396S| 50 mA| 60 mA
ALC-H16| 35 mA| 50 mA
DM-1008A – 8 zone active| 80 mA| 465 mA
SGM-1004A| 60 mA| 258 mA
RM-1008A| 25 mA| 150 mA
PR-300| 35 mA| 300 mA
UDACT-300A| 45 mA| 120 mA
RAX-LCD| 100 mA| 150 mA
IPS-2424DS| 5 mA| 22 mA
FDX-008| 15 mA| 35 mA
MGD-32| 35 mA| 1.6 Amps
AGD-048| 35 mA| 2.4 Amps
RAM-1032TZDS| 50 mA| 300 mA
RAX-1048TZDS| 22 mA| 262 mA
Remote Annunciators
RAX-LCD Remote Shared Display
The RAX-LCD Remote Shared Display is a remote annunciator that provides the
same functions as the main display on the fire alarm control panel, less the
16 zone LEDs. In addition to operating as a remote annunciator, it can also be
used as a driver module for standard LED annunciation or reduced zone
annunciation (different from the main panel annunciation), graphic drivers
programmed different from the main annunciators, programmable switch modules
with a unique configuration and fan damper control also with a unique
configuration. Each time a different type of annunciation configuration is
needed an additional RAX-LCD is required. The RAX-LCD occupies one display
position in the BB-1000 or BB-5000 enclosures.
RAM-1032TZDS Main Remote LED Annunciator
The RAM-1032TZDS Main Remote LED Annunciator provides common annunciator
functions and 32 points of LED annunciation. Each display point can be
identified by the slide-in label that slides in beside the LED. The RAM-
1032TZDS is equipped with sealed membranelike buttons for Common Control
functions. The RAM1032TZDS fallows for the control switches to be disabled on
a per function basis for areas that do not require certain common control
functions to be remotely located from the fire alarm control panel. The RAM-
1032TZDS can be programmed differently than the main panel annunciator or a
remote RAX-LCD. All RAM-1032TZDS remote annunciators on the system must be
programmed the same. The RAM-1032TZDS occupies one display position in the
BB-1000 or BB-5000 enclosures. RAX-
1048TZDS Adder Remote LED Annunciator
The RAX-1048TZDS Adder Remote LED Annunciator provides an additional 48 points
of LED annunciation. The RAX-1048TZDS is an expandible module that connects to
the RAM-1032TZDS. The RAX-1048TZDS occupies one display position in the
BB-1000 or BB-5000 enclosures.
Graphic Annunciator Driver Modules
MGD-32 Master Graphic
Driver Module
The MGD-32 Master Graphic Driver Module provides common control inputs for the
common control switches such as System Reset, Signal Silence, Auxiliary
Disconnect, Fire Drill, Lamp Test, Acknowledge and General Alarm. Any or all
of these switch inputs can be used. There are supervised outputs for all of
the support LEDs and the common control switches. The MGD-32 can also drive up
to 32 supervised outputs. These output points are capable of driving LEDs or
incandescent lamps. Mounts in a graphic annunciator wallbox or in the BB-5000
enclosures. External power supply required for incandescent lamps and lamp
test. AGD-048 Adder Graphic
Driver Module
The AGD-048 Adder Graphic Driver Module can be used with the MGD-32 Master
Graphic Driver modules, or if located remotely it must be connected and
mounted with the RAX-LCD Shared Display. The AGD-048 will support an
additional 48 supervised outputs. As with the master modules, the AGD-048 will
support both LEDs and incandescent lamps. Mounts in a graphic annunciator
wallbox or in the BB-5000 enclosures.
NOTE:
The combined total of RAM-1032TZDS and MGD-32 per system is eight. All RA-1000
Series annunciators or Graphic driver modules must have the zoned LED or
graphic LED correlated to the same combination of addressable devices or
hardwired zones . However, the zoned LED annunciator on the FX-2000 main panel
can be programmed differently from the annunciators mounted remotely.
Enclosures
UB-1024DS Universal Backbox
The UB-1024DS Universal Backbox houses the FX-20036DS or FX-2003-12DS main
control unit and provides space to mount up to 17 AH batteries. A DOX-
1024DS(R)
door is ordered separately.
Dimensions (minus built-in trim ring): 26”H x 14.5”W x 4.2”D DOX-1024DS(R)
Door
The DOX-1024DS mounts on the UB-1024DS backbox.
The door features the universal CAT-30 lock and is available in a white (DOX-
1024DS) or red exterior (DOX-1024DSR). BB-5008
The BB-5008 is a lobby control centre enclosure which is capable of handling
one FX-2009-12DS Large Main Control Unit which supports 2 internal annuciator
modules
such as the IPS-2424DS, FDX-008, RAX-1048TZDS, etc.In addition the BB-5008
allows for 4 footprints for mounting Audio Lobby Control modules, Fire
Fighter’s Lobby Controlmodules and FX-2000 Internal Annunciator modules. The
cabinet hold up to 24 AH batteries. Door and Chassis hardware are ordered
seperately.
Dimensions: 36”H x 30”W x 7”D
Other Enclosures
BB-1001: 9”H x 12.75”W x 1.2”D
BB-1002: 18”H x 12.75”W x 1.2”D
BB-1003: 26.4”H x 12.75”W x 1.2”D
BB-1008: 33”H x 22.5”W x 1.25”D
BB-1012: 45”H x 22.5”W x 1.25”D BBX-
1072ADS
The BBX-1072ADS enclosure is capable of handling one FX-2017-12ADS Mid-Size
Main Control Unit as well as up to 24 AH Batteries. The cabinet features the
universal
CAT-30 lock and a removable door for easy installation and servicing. The
cabinet is available in a white or red exterior (BBX-1072ARDS).
Dimensions (minus built-in trim ring): 32.5”H x 25”W x 6 .5”D
BB-5014
The BB-5014 is a lobby control centre enclosure which is capable of handling
one FX-2009-12DS Large Main Control Unit which supports 2 internal annuciator
modules
such as the IPS-2424DS, FDX-008, RAX-1048TZDS, etc. In addition the BB-5014
allows for 10 footprints for mounting Audio Lobby Control modules, Fire
Fighter’s Lobby Control modules and FX-2000 Internal Annunciator modules. The
BB-5014 can also support a graphic annunciator in place of these modules. The
cabinet holds up to 24 AH batteries. Door and Chassis hardware are ordered
seperately.
Dimensions: 60”H x 30”W x 7”D
Typical FX-2000 Panel Wiring Class B (Style 4)
FX-2009-12DS Large Main Chassis in a BB-5014 enclosure c/w ECX-0012 Expander Chassis. RAX-1048TZDS, IPS-2424DS, FDX-008 and AGD-048. Includes DM-1008A Conventional Indicating Circuit Modules. External power supply is required for incandescent lamps and lamp test.
Ordering Information
Model | Description |
---|
FX-2000 Standard Series
FX-2003-6DS-16LED
FX-2003-6DS| Compact Main Control Unit c/w one Intelligent Signaling Line
Circuit, Four Style Z/Y (Class A/B) Notification Appliance Circuits rated at
1.7 Amps each and a 4 line by 20 character back-lit LCD display with 16 LEDS
for annunciation (DSPL-420-16TZDS). This display is functionally equivalent to
the classic FX-2000 main display, but more compact adding in the 16 LEDs for
annunciation in addition to all the standard functions.TheFX-2003-6DS-16LED is
equipped with a 6 Amp Power Supply which charges 10-24 AH batteries. The
FX-2003-6DS-16LED provides space for 3 adder modules and 2 internal
annunciator adder modules. Order UB-1024DS and DOX-1024DS(R) separately.
Compact Main Control Unit c/w one Intelligent Analog Loop Controller (99
Analog Sensors and 99 Addressable Modules), 4 x 20 Back-lit LCD display, 4
Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each), a 6 Amp power
supply and a backbox. Supports up to 16 Conventional Adder Modules. Provides
space for 3 Adder Modules and 2 internal annunciation modules. Order UB-1024DS
and DOX-1024DS(R) separately.
FX-2003-12DS| Compact Main Control Unit c/w one Intelligent Analog Loop
Controller (99 Analog Sensors and 99 Addressable Modules), 4 x 20 Back-lit LCD
display, 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps each), a 12 Amp
power supply and a backbox. Supports up to 16 Conventional Adder Modules.
Provides space for 3 Adder Modules and 2 internal annunciation modules. Order
UB-1024DS and DOX-1024DS(R) separately.
FX-2017-12ADS| Mid-Size Main Control Unit c/w one Intelligent Analog Loop
Controller (99 Analog Sensors and
99 Addressable Modules), 4 x 20 Back-lit LCD display, 4 Class A/B (Style Z/Y)
Indicating Circuits
(1.7 Amps each) and a 12 Amp power supply. Supports up to 16 Conventional
Adder Modules.
Provides space for 17 Adder Modules and 3 Internal Annunciation modules.
Mounts in the BBX1072ADS
enclosure.
FX-2009-12DS|
Large Main Control Unit c/w one Intelligent Analog Loop Controller (99 Analog
Sensors and 99
Addressable Modules), 4 x 20 Back-lit LCD display, 4 Class A/B (Style Z/Y)
Indicating Circuits (1.7 Amps each) and a 12 Amp power supply. Supports up to
16 Conventional Adder Modules. Provides space for 9 Adder Modules and 3
Internal Annunciation modules. Mounts in the
BB-5000 series enclosures.
ECX-0012| Expander Chassis for the FX-2009-12DS c/w space to add up to 12
adder modules and 2 Internal Annunciation modules. Mounts in the BB-5000
series enclosures
Adder Loop Controller Modules
ALC-198S| Single Loop Intelligent Analog Loop Controller Module (99 Analog
Sensors and 99 Addressable Modules)
ALC-396S| Dual Loop Intelligent Analog Loop Controller Module (198 Analog
Sensors and 198 Addressable Modules)
ALC-H16| Hardwire Loop Controller Module. Supports 16 Conventional Hardwired
Modules
Adder Hardwire Modules
DM-1008A| Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit
Module
SGM-1004A| Four Class A/B (Style Z/Y) Indicating Circuit Module (Rated at 1.7
Amps per circuit)
RM-1008A| Eight Relay Circuit Module c/w eight form C relays (Rated for 28 VDC
@ 1 Amp max. per relay)
Adder Auxiliary Modules
UDACT-300A| Digital Alarm Communicator Transmitter/Dialer Module
PR-300| Polarity Reversal and City Tie Module
Programmable Modules
RAX-1048TZDS| Programmable Zone LED Annunciator Module c/w 48 bi-coloured
LEDs.
IPS-2424DS| Programmable Input Switches Module c/w 24 selector switches and 24
bi-coloured LEDs
FDX-008| Fan Damper Control Module c/w 8 programmable switches
Remote Annunciators
RAM-1032TZDS| Main Annunciator Chassis c/w Common Control Features, Indicators
and 32 Bi-Coloured LEDs
RAX-1048TZDS| Adder Annunciator Chassis c/w 48 Bi-Coloured LEDs
RTI-1| Remote Trouble Indicator
Remote Shared Display Annunciators
RAX-LCD| Remote Shared Display LCD Annunciator c/w Display Queues and Common
Controls
Graphic Annunciator Driver Modules
MGD-32| Master Graphic Driver Module c/w Fire Alarm Common Control Switch
Inputs and 32 Supervised Outputs
AGD-048| Adder Graphic Driver Module c/w 48 Supervised Outputs
Ordering Information
Enclosures
UB-1024DS| Universal backbox for FX-2003-6DS/FX-2003-12DS. Order DOX-1024DS
separately
DOX-1024DS| White door for UB-1024DS backbox
DOX-1024DSR| Red door for UB-1024DS backbox
BBX-1072ADS| Black backbox enclosure for FX-2000 c/w removable door and CAT-30
lock and key. Houses one FX2017-12ADS Mid-Size Main Control Unit and up to 24
AH batteries. Includes White door
BBX-1072ARDS| Black backbox enclosure for FX-2000 c/w removable door and
CAT-30 lock and key. Houses one
FX-2017-12ADS Mid-Size Main Control Unit and up to 24 AH batteries. Includes
Red door
BB-5008| Lobby Control Centre Wallbox Enclosure. Supports 8 Module Footprints
DOX-5008M| White Metal Door for BB-5008
DOX-5008MR| Red Metal Door for BB-5008
CCH-5008| Custom Mounting Kit for BB-5008. One required per BB-5008
BB-5014| Lobby Control Centre Wallbox Enclosure. Supports 14 Module
Footprints
DOX-5014M| White Metal Door for BB-5014
DOX-5014MR| Red Metal Door for BB-5014
CCH-5014| Custom Mounting Kit for BB-5014. One required per BB-5014
NOT TO BE USED FOR INSTALLATION PURPOSES.
Canada
25 Interchange Way
Vaughan, Ontario L4K 5W3
Telephone: 905-660-4655
Fax: 905-660-4113
U.S.A.
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Toll Free: 888-660-4655
Fax Toll Free: 888-660-4113
Distributed by:
ISO 9001:2008 REGISTERED
CAT.5910
Rev.11
Web page: http://www.mircom.com
Email: mail@mircom.com
firealarmresources.com
References
Read User Manual Online (PDF format)