AKO-5010 XaviP EDGE Communication Gateway Instructions

June 9, 2024
AKO

AKO-5010 XaviP EDGE Communication Gateway Instructions

**Warnings

**

  • If the device is used without adhering to the manufacturer’s instructions, the device safety requirements could be compromised. Only probes supplied by AKO should be used for the appliance to operate correctly.
  • The device should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • Avoid installing the device on metal walls or near devices that may produce radio emissions.
  • The AKO XaviP EDGE device should NEVERbe operated without installing the external antenna.
  • This device can be fitted with any antenna provided it has a gain of less than 9.2 dBi and there is a minimum distance between it and any person or animal of more than 20 cm.
  • This device must be installed in a location where a minimum distance of 20 cm to the human body can be guaranteed, in order to ensure compliance with standards on human exposure to electromagnetic fields.
  • Any type of antenna used with the device must comply with the limits established in the radio interface of the member states and the following documents: Commission Decision 2010/267/EU of 6 May 2010,ECC Decision (09)03 of 30 October 2009 and.

Description

AKO XaviP EDGE is a communication gateway with AKOnet. Cloud for up to 10 AKO devices in the AKO-5010 model, and up to 25 AKO devices in the AKO-5025model ,modbus-rtu,Ethernet and gprs ports, and local web panel via WiFi.
Product  Description Indicators (Wait between 3 and 4 minutes after start-up for indicators to show their real status)

lashing red: Indicates RS485 communication (MODBUS) (Tx).
Flashing green: Indicates RS485 communication (MODBUS) (Rx).
Flashing blue: Linux application activated.

Constant red: Communication error with the cloud.
Constant blue: Connected to the cloud with a registration error,check that registration has been completed correctly.
Flashing blue: Linux application in start-up process.
Constant green: Device connected and registered on the cloud.
Flashing green: Communication with the cloud (Tx).

Installation

Option A: Ethernet Connectivity through DHCP (Recommended)

  • Fix the device onto a DIN rail (Fig.2).
  • Connect the ethernet cable. By default, configuration is through DHCP, for configuration through static IP, consult the application note available on our web.
  • Make the connections according to the wiring diagram provided.
  • Connect the power supply,the device starts up automatically.
  • Register the AKO XaviP EDGE in https://akonet.cloud

Option B: GPRS Connectivity

  • Install the SIM card for GPRS connectivity (Not included) (Fig.1).
    Installation Instruction

  • Fix the device onto a DIN rail (Fig. 2).
    Installation Instruction

  • Make the connections according to the wiring diagram provided.

  • Connect the power supply.

  • Connect to the local console of the AKOXaviPEDGE with a computer or mobile device through a WIFI connection (the ethernet cable must be disconnected):

    • connection (the ethernet cable must be disconnected):
    • Search for WIFI network with name “EDGE-xxxx” (xxxx are the last 4 digits of the serial number of your AKO XaviP EDGE)
    • WIFI password:“edge1234″
    • Enter the following address in the web browser:“10.0.0.1″
    • Access with the following access data: Username: “Edge” and Password: (see product label).
    • Click “GPRS”and “Edit”.
    • Enter the data provided by your GPRS* operator and click “Submit”.
    • Click on “Parameters”,in “Tx type”change from Ethernet to GPRS and click on “Submit”.
    • Close the web browser and disconnect from the “EDGE-xxxx”WIFI.
  • Register the AKO XaviP EDGE in https://akonet.cloud
    Installation Instruction

  • Make sure you correctly configure GPRS data, your operator must provide you with the necessary information.

QR Code

QR Code
AKO
30-38 Roquetes, vda. A
Sant Pere de Ribes. • 08812
Spain. • Barcelona
We Reserve the right to supply material which may be slightly different from those describe in our data sheets. Updated information on our web site.

Start-up

  1. Access akonet.cloud (you must be registered).
    Start Up Instruction

  2. Access the “Edges”(A) section and click “+”(Activate new Edge) (B).
    Start Up Instruction

  3. Enter the data that appears on the label of the newAKO XaviP EDGE (Serial no. and validation code) or click QRC and scan the QR code provided on the label.
    Start Up Instruction

  4. Finish the activation by filling in the requested data.
    Start Up Instruction

  5. After registering start searching for devices connected to the AKO XaviP EDGE and activate them.
    Start Up Instruction

  6. From then on, the AKO XaviP EDGE starts to transmit data to akonet. cloud. For further information, please refer to the manuals available on our website

Display and analysis of the logged data

Both the display of the logged data and the device configuration must be done in the akonet. cloud portal. The portal also allows you to analyse the stored data using graphs, statistics and operating indicators. For more information visit akonet. cloud.

Wiring

Always disconnect the power supply to do the wiring.

For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near the device. The power supply cable shall be of the H05VV-F or NYM 1×16/3 type. The section to be used will depend on current local regulations but should never be less than 1.5 mm . The 120 / 230 V~ wiring area must be kept clear of any other 2 external element.
Wiring Instruction

Technical specifications

  • Power supply: 85 – 264 V ~ / 47 – 63 Hz
  • Maximum consumption: 10 VA
  • Communications: WIFI (802.11 b/g/n,2.4 GHz)
    • Ethernet Port 10/100 Mbps
    • RS 485 9600
    • Quad-band GSM/GPRS (850/900/1800/1900 MHz)
  • Antenna: External
  • Working ambient temperature: 0 to 40 ºC
  • Range o f moisture permbitted: 5 – 95 %
  • Maximum working height: 2000 m
  • Casin: Self-extinguishing UL94 V0 polycarbonate
  • Protection degree: IP20
  • Fixing: DIN rail 46277
  • Connections: .Plug-in terminals, maximum 1.5 mm
  • Electrical and safety features: Double insulation (fitted),protection class II
  • Dimensions (with terminals and antenna fitted) : 88 mm (W) x 145 mm (H) x 50 mm (D)

Simplified declaration of conformity

AKO Electromecánica S.A.L. hereby declares that the type of radioelectric device AKO-5010/AKO-5025 (communications gateway with AKOnet.Cloud for up to 10/25 devices respectively) is in accordance with Directive 2014/53/EU. The full text of the EU conformity declaration is available at the following internet address: http://help.ako.com/en/manuals/declaracion-ue-de- conformidad

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>