American Standard 4A7A3 Split System Air Conditioner User Manual

June 9, 2024
American Standard

American Standard 4A7A3 Split System Air Conditioner
logo

American Standard 4A7A3 Split System Air Conditioner

IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.

Safety

WARNING
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connection with its use.
WARNING
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only 410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE oil reference Retrofit Bulletins SS-APG006-EN and APP-APG011-EN or APP-APG012-EN.
WARNING
UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22. Proper service equipment is required. Failure to use proper service tools may result in equipment damage or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND AP-PROVED POE COMPRESSOR OIL.
WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and trouble-shooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
CAUTION
Scroll compressor dome temperatures may be hot. Do not touch the top of compressor; it may cause minor to severe burning.
WARNING
This product can expose you to chemicals including lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

Unit Location Considerations

Unit Dimensions and Weight

When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure.

Unit Dimensions and Weight

Models| H x D x W (in)| Weight* (lb.)
4A7A3018N| 29 x 26 x 29| 133
4A7A3024N| 29 x 26 x 29| 133
4A7A3030N| 29 x 30 x 33| 156
4A7A3036N| 29 x 30 x 33| 161
4A7A3042N| 29 x 34 x 37| 184
4A7A3048N| 29 x 34 x 37| 189
4A7A3060N| 37 x 34 x 37| 211
4A7A3018H| 29 x 26 x 29| 127
---|---|---
4A7A3024H| 29 x 26 x 29| 130
4A7A3030H| 29 x 26 x 29| 137
4A7A3036H| 29 x 30 x 33| 147
4A7A3042E| 29 x 30 x 33| 172
4A7A3043A| 29 x 34 x 37| 184
4A7A3048E| 37 x 30 x 33| 184
4A7A3049A| 29 x 34 x 37| 189
4A7A3060E| 37 x 34 x 37| 211

  • Weight values are estimated.
Refrigerant Piping Limits
  1. The maximum TOTAL length of refrigerant lines from outdoor to indoor unit should NOT exceed 150 feet* (including lift).
  2. The maximum vertical change should not exceed 50 feet*.
  3. Standard and alternate line sizes and service valve connection sizes.

Note: For other line lengths, Refer to Refrigerant Piping Application Guide, SS-APG006-EN or Refrigerant Piping Software Program, 32-3312-xx (latest revision).

Suggested Locations for Best Reliability
  • Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
  • Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
  • It is not recommended to install in a location where noise may distract the building occu-pants. Some examples of these types of loca-tions are sleeping quarters and by windows of a living area. Please discuss location with the building owner prior to installation.
  • Avoid locations such as near windows where condensation and freezing defrost vapor can annoy a customer.
  • Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow.
  • Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit.
Cold Climate Considerations

NOTE: It is recommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.

  • Units should be elevated 3-12 inches above the pad or roof top, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not
    obstructed preventing draining of defrost water.

  • If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.American Standard 4A7A3 Split System Air Conditioner 5

Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory sup-plied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.

Unit Preparation

Prepare The Unit For Installation
  • STEP 1
    Check for damage and report promptly to the carrier any damage found to the unit.

  • STEP 2
    To remove the unit from the pallet, remove tabs by cutting with a sharp tool.

Setting the Unit

Pad Installation

When installing the unit on a support pad, such as a concrete slab, consider the following:

  • The pad should be at least 1” larger than the unit on all sides.
  • The pad must be separate from any structure.
  • The pad must be level.
  • The pad should be high enough above grade to allow for drainage.
  • The pad location must comply with National, State, and Local codes.American Standard 4A7A3 Split System Air Conditioner 8

For other applications refer to application guide.

Refrigerant Line Considerations

Refrigerant Line and Service Valve Connection Sizes

 RATED LINE SIZES

| Line Sizes| Service Valve Connection Sizes| Max Line & Lift Lengths
---|---|---|---
Vapor Line| Liquid Line| Vapor Line Connection| Liquid Line Connection| TOTAL Max
Line Length (ft.)|

**** Max Lift (ft.)

4A7A3018N| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3024N| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3030N| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3036N| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3042N| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3048N| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3060N| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3018H| 3/4| 3/8| 3/4| 3/8| 150| 50
---|---|---|---|---|---|---
4A7A3024H| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3030H| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3036H| 3/4| 3/8| 3/4| 3/8| 150| 50
4A7A3042E| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3043A| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3048E| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3049A| 7/8| 3/8| 7/8| 3/8| 150| 50
4A7A3060E| 7/8| 3/8| 7/8| 3/8| 150| 50

Note: For other line lengths, Refer to Refrigerant Piping Application Guide, SS-APG006-EN or Refrigerant Piping Software Program, 32-3312-xx (latest revision).

Factory Charge

The outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, ten (10) feet of tested connecting line, and the smallest rated indoor evaporative coil match. Always verify proper system charge via subcooling (TXV/EEV) or superheat (fixed orifice) per the unit nameplate.

Required Refrigerant Line Length

Determine required line length and lift. You will need this later in STEP 2 of Section 14.

  • Total Line Length = __ Ft.
  • Total Vertical Change (lift) = __ Ft.
Refrigerant Line Insulation

Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and Vapor Line to come in direct (metal to metal) contact.

Reuse Existing Refrigerant Lines\

CAUTION
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken:

  • Ensure that the indoor evaporator coil and refrigerant lines are the correct size.
  • Ensure that the refrigerant lines are free of leaks, acid, and oil.

Refrigerant Line Routing

Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
For Example:

  •  When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type hangers.
  •  Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
  •  Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
  •  Isolate the lines from all ductwork.
  •  Minimize the number of 90º turns.
    American Standard 4A7A3 Split System Air Conditioner
12

Secure Vapor line from joists using isolators every 8 ft. Secure Liquid Line directly to Vapor line using tape, wire, or other appropriate method every 8 ft.
American Standard 4A7A3 Split System Air Conditioner
13Secure Vapor Line using isolators every 8 ft. Secure Liquid Line directly to Vapor Line using tape, wire, or other appropriate method every 8 ft.
Isolation In Wall Spaces
American Standard 4A7A3 Split System Air Conditioner
14

Refrigerant Line Brazing

Braze The Refrigerant Lines
  • STEP 1 :
    Remove caps or plugs. Use a deburring tool to deburr the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.

  • STEP 2 :
    Remove the pressure tap cap and valve cores from both service valves.

  • STEP 3 :
    Purge the refrigerant lines and indoor coil with dry nitrogen.

  • STEP 4:
    Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitro-gen purge.
    Braze the refrigerant lines to the service valves. For units shipped with a field-installed external drier, check liquid line filter drier’s directional flow arrow to confirm correct direction of refrigeration flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to the Liquid Line. Continue the dry nitrogen purge. Do not remove the wet rag until all brazing is completed.
    Important: Remove the wet rag before stopping the dry nitrogen purge.
    Note: Install drier in Liquid Line.
    Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the base pan.American
Standard 4A7A3 Split System Air Conditioner 18

  • STEP 5: Replace the pressure tap valve cores after the service valves have cooled.

Refrigerant Line Leak Check

Check For Leaks
  • STEP 1:
    Pressurize the refrigerant lines and evaporator coil to 150 PSIG using dry nitrogen.

  • STEP 2:
    Check for leaks by using a soapy solution or bubbles at each brazed location.

Remove nitrogren pressure and repair any leaks before continuing.

Evacuation

Evacuate the Refrigerant Lines and Indoor Coil

Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.

  • STEP 1:
    Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.

  • STEP 2:
    Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
    Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.

Service Valves

Open the Gas Service Valve

Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere.

  • STEP 1 : Remove valve stem cap.
  • STEP 2 :  Using an adjustable wrench, turn valve stem 1/4 turn counterclockwise to the fully open position.
  • STEP 3 : Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
Open the Liquid Service Valve

WARNING
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
Important: Leak check and evacuation must be completed before opening the service valves.

  • STEP 1: Remove service valve cap.
  • STEP 2: Fully insert 3/16” hex wrench into the stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)
  • STEP 3: Replace the valve cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.

Electrical – Low Voltage

Low Voltage Maximum Wire Length

defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.

24 VOLTS

WIRE SIZE| MAX. WIRE LENGTH
18 AWG| 150 Ft.
16 AWG| 225 Ft.
14 AWG| 300 Ft.

 Low Voltage Hook-up Diagrams
  • Units with pigtails require wirenuts for connections. Cap all unused wires.
  • In AC systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
  • TEM3/4 – Bypass air handler and connect Y from comfort control directly to OD unit
  • TEM6 Only
  • TEM6 only – When using a BK enabled comfort control, cut BK jumper and bypass Y1 and Y2 at the air handler. Connect BK from comfort control to BK of the air handler
  • TAM4 only – Wire as shown, no BK is available
  • TAM7 only – When using a BK enabled comfort control, cut BK jumper on the AFC and connect BK from comfort control to BK of the air handlerAmerican Standard 4A7A3 Split System Air Conditioner 26
  • Units with pigtails require wire nuts for connections. Cap all unused wires.
  •  In AC systems for multiple stages of heat, jumper W1 and W2 together if comfort control has only one stage of heat.
  •  If equipped with second stage heat
  •  When using a BK enabled comfort control, cut BK jumper and bypass Y and YLo at the furnace. Connect BK from comfort control to BK of the furnaceAmerican Standard 4A7A3 Split System Air Conditioner 27

Electrical – High Voltage

High Voltage Power Supply
WARNING
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate. Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit.
High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem within the structure.
High Voltage Ground
Ground the outdoor unit per national, state, and local code requirements.

Start Up

System Start Up
  • STEP 1 – Ensure Sections 7 through 12 have been completed.

  • STEP 2 – Set System Thermostat to OFF.

  • STEP 3 – Turn on disconnect(s) to apply power to the indoor and outdoor units.

  • STEP 4 – Wait one (1) hour before starting the unit if compressor crankcase heater accessory is used and the Outdoor Ambient is below 70ºF.

  • STEP 5 – Set system thermostat to ON.

System Charge Adjustment

Temperature Measurements (Systems can be rated with TXV, EEV or Piston. Ensure charging method is correct.)-

  • STEP 1 – Check the outdoor temperatures.
    Sub cooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature.

Note: For Superheat (In Cooling Mode), refer to the Superheat Charging Table
For best results the indoor temperature should be kept between 70º F to 80º F.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient temperature is above 55º F.

Sub cooling Charging in Cooling (Above 55º F Outdoor Temp.)

  • STEP 1 – Use the refrigerant line total length and lift measurements.
    Total Line Length = __ Ft.
    Vertical Change (Lift) = __ Ft.

  • STEP 2 – Determine the final sub cooling value using total Line Length and Lift measured in STEP 1 and the charts below.
    American Standard 4A7A3 Split System Air Conditioner
39

  • STEP 3 – Stabilize the system by operating for a minimum of 20 minutes.
    At startup, or whenever charge is removed or added, the system must be operated for a mini-mum of 20 minutes to stabilize before accurate measurements can be made.

  • STEP 4 – Measure the liquid line temperature and pressure at the outdoor unit’s service valve.
    Measured Liquid Line Temp = __ º F
    Liquid Gage Pressure = __ PSI
    Final Sub cooling Value = __ º F
    American Standard 4A7A3 Split System Air Conditioner
41

  • STEP 5 – Use the final sub cooling value, refrigerant temperature and pressure from STEP 4, to determine the proper liquid gage pressure using
    Example: Assume a 12º F Final Sub cooling value and liquid temp of 90º F.

    • Locate 12º F Final Sub cooling in Table 14.2.
    • Locate the Liquid Temperature (90º F) in the left column.
    • The Liquid Gage Pressure should be approximately 327 PSI. (This is the shown as the intersection of the Final Sub cooling column and the Liquid Temperature row.
  • STEP 6 – Adjust refrigerant level to attain proper gage pressure.
    Add refrigerant if the Liquid Gage Pressure is lower than the chart value.

    • Connect gages to refrigerant bottle and unit as illustrated.
    • Purge all hoses.
    • Open bottle.
    • Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure matches the charging chart Final Sub cooling value.
      American Standard 4A7A3 Split System Air Conditioner 43American Standard
4A7A3 Split System Air Conditioner 43Recover refrigerant if the Liquid Gage Pres-sure is higher than the chart value.
  • STEP 7 – Stabilize the system.

    • Wait 20 minutes for the system condition to stabilize between adjustments.
      Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged.

    • Remove gages.

    • Replace service port caps to prevent leaks. Tighten finger tight plus an additional 1/6 turn.

  • STEP 8 – Verify typical performance. Refer to System Pressure Curves at the end of the document to verify typical performance.
    Fixed Orifice Superheat Charging Table
    | Indoor Wet Bulb Temp (F)
    ---|---
    Outdoor Dry Bulb Temp. (F)| | 50| 51| 52| 53| 54| 55| 56| 57| 58| 59| 60| 61| 62| 63| 64| 65| 66| 67| 68| 69| 70| 71| 72| 73| 74| 75| 76| 77| 78
    55| 7| 9| 10| 11| 12| 14| 15| 17| 18| 20| 21| 23| 24| 26| 27| 29| 30| | | | | | | | | | | |
    60| 5| 7| 8| 9| 10| 12| 13| 15| 16| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| | | | | | | | | |
    65| | | 4| 6| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 27| 31| | | | | | | |
    70| | | | | 5| 7| 8| 10| 11| 13| 14| 16| 17| 18| 19| 21| 22| 24| 25| 27| 28| 30| 31| | | | | |
    75| | | | | | | 5| 6| 7| 9| 10| 12| 14| 16| 18| 19| 21| 22| 24| 26| 28| 29| 31| 32| | | | |
    80| | | | | | | | | 4| 6| 7| 9| 10| 11| 12| 14| 16| 18| 19| 21| 23| 25| 26| 28| 29| 31| 33| |
    85| | | | | | | | | | | 4| 6| 7| 9| 10| 13| 14| 16| 18| 20| 21| 23| 24| 26| 28| 29| 30| 31| 32
    90| | | | | | | | | | | | | 4| 6| 8| 10| 11| 13| 14| 16| 18| 20| 22| 24| 25| 27| 28| 30| 31
    95| | | | | | | | | | | | | | | 4| 6| 8| 10| 13| 14| 16| 18| 20| 22| 23| 25| 26| 28| 29
    100| | | | | | | | | | | | | | | | | 6| 8| 10| 12| 13| 16| 18| 20| 21| 23| 25| 27| 29
    105| | | | | | | | | | | | | | | | | 4| 6| 7| 9| 11| 13| 15| 18| 20| 22| 24| 26| 28
    110| | | | | | | | | | | | | | | | | | | 4| 7| 9| 11| 13| 16| 18| 21| 23| 26| 28


115

| | | | | | | | | | | | | | | | | | | | | ****

6

| ****

9

| ****

12

| ****

14

| ****

16

| ****

19

| ****

21

| ****

24

| ****

26

Using a digital psychrometer, measure the return air wet-bulb temperature at the unit just before the coil. Also measure the outdoor dry-bulb temperature. Use these temperatures to locate the target superheat on the charging table. Do not attempt to charge the system if these conditions fall outside of this charging table.
ADD refrigerant to DECREASE total superheat. REMOVE refrigerant to INCREASE total superheat. Always allow 10 to 15 minutes of operature after any refrigerant or air flow change prior to determining the final superheat.

  • STEP 9 – Record System Information for refer-ence.
    Record system pressures and temperatures after charging is complete.
    Outdoor model number = _____
    Measured Outdoor Ambient = __ º F
    Measured Indoor Ambient = __ º F
    Measured Liquid Line Temp = __ º F
    Measured Suction Line Temp = __ º F
    Liquid Gage Pressure = __ PSIG
    Suction Gage Pressure = __ PSIG

Sub cooling Charging Below 55º F Outdoor Temp.
The Sub cooling Charging method in cooling is not recommended below 55º F outdoor temperature.
The recommended method of charging at outdoor temperatures below 55º F is weighing in the charge. Return when weather conditions permit charge verification through sub cooling.

  • STEP 1 – Determine additional charge.
    Note: The nameplate charge value represents the amount of refrigerant shipped in the outdoor unit and is compatible with 10 feet of AHRI rated refrigerant lines and the smallest AHRI rated coil.
    Using the method below, find the charge associated with the additional length of tubing above 10 ft. and record it below.
    Weigh-In Method can be used for the initial installation, or anytime a system charge is being replaced. Weigh-In Method can also be used when power is not available to the equipment site or operating conditions (indoor/outdoor temperatures) are not in range to verify with the subcooling charging method.
    Calculating Charge Using the Weigh-In Method

    • Measure in feet the distance between the outdoor unit and the indoor unit. (Include the entire length of the line from the service valve to the IDU.) Subtract 10 ft from this entire length and record on line 1.
    • Enter the charge multiplier (0.6 oz/ft). Each linear foot of interconnecting tubing requires the addition of 0.6 oz of refrigerant.
    • Multiply the total length of refrigerant tubing (Line 1) times the value on Step 2. Record the result on Line 3 of the Worksheet.
    • This is the amount of refrigerant to weigh-in prior to opening the service valves.
    • Total Line length (ft.) – 10 ft. __
    • Charge multiplier  x _0.6 oz. ___
    • Step 1 x Step 2  = _____
    • Refrigerant (oz.)  = _____
  • STEP 2 – Stabilize the system by operating for a minimum of 20 minutes.
    At startup, or whenever charge is removed or added, the system must be operated for a mini-mum of 20 minutes to stabilize before accurate measurements can be made.

  • STEP 3 – Check the liquid line temperature and liquid gage pressure to obtain a minimum of 10º subcooling in heating mode.
    Measured Liquid Line Temp = __ º F
    Liquid Gage Pressure = __ PSIG

  • STEP 4 – Add charge if a minimum of 10º sub-cooling is not obtained with the namplate charge plus additional charge previously added.

  • STEP 5 – Return to site for adjustment.
    Important: Return in the spring or summer to accurately charge the system in the cooling mode with outdoor ambient above 55º F.

Checkout Procedures

Operational And Checkout Procedures

Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if nec-essary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:

  1. Leak check refrigerant lines. …………… …………… ………… [ ]
  2. Properly insulate suction lines and fittings. ………… [ ]
  3. Properly secure and isolate all refrigerant lines. …. [ ]
  4. Seal passages through masonry. If mortar is used, prevent mortar from coming into direct contact with copper tubing. … [ ]
  5. Verify that all electrical connections are tight. …………… [ ]
  6. Observe outdoor fan during on cycle for clearance and smooth operation …. [ ]
  7. Be sure that indoor coil drain line drains freely. Pour water into drain pan. ………………………………………… [ ]
  8. Be sure that supply registers and return grilles are open and unobstructed. ………………………………………… [ ]
  9. Be sure that a return air filter is installed. ………………… [ ]
  10. Be sure that the correct airflow setting is used. (Indoor blower motor)………………………………………… [ ]
  11. Operate complete system in each mode to ensure safe operation. …. [ ]

Refrigerant Circuits

  • 1.5 & 2 Ton Units

  • American Standard 4A7A3 Split System Air Conditioner 46 2.5 & 3.5 Ton UnitsAmerican Standard 4A7A3 Split System Air Conditioner 47

  • 3 & 4 Ton Units
    American Standard 4A7A3 Split System Air Conditioner
48

  • 5 Ton Units
    American Standard 4A7A3 Split System Air Conditioner
49

Wiring Diagrams

018N, 030N, 036N, 042N & 048N Models 018H, 024H, 043A & 049A Models
American Standard 4A7A3 Split System Air Conditioner
50
024N Models
American Standard 4A7A3 Split System Air Conditioner
52
030H, 036H & 042E ModelsAmerican Standard 4A7A3 Split System Air
Conditioner 54
060N Models
048E & 060E ModelsAmerican Standard 4A7A3 Split System Air Conditioner
56

Pressure Curves

PRESSURE CURVES (Refer below table for models)
American Standard 4A7A3 Split System Air Conditioner
58 COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES.
ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE:

  1. OUTDOOR TEMP. 82 F.
  2. INDOOR WET BULB 67 F.
  3. AT INTERSECTION
  4. LIQUID PRESSURE @ 600 CFM IS 304 PSIG
  5. SUCTION PRESSURE @ 600 CFM IS 145 PSIG

ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
American Standard 4A7A3 Split System Air Conditioner
59

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES.
ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE:

  1. OUTDOOR TEMP. 82 F.
  2. INDOOR WET BULB 67 F.
  3. AT INTERSECTION
  4. LIQUID PRESSURE @ 600 CFM IS 307 PSIG
  5. SUCTION PRESSURE @ 600 CFM IS 142 PSIG

ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES.
ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE:

  1. OUTDOOR TEMP. 82 F.
  2. INDOOR WET BULB 67 F.
  3. AT INTERSECTION
  4. LIQUID PRESSURE @ 600 CFM IS 308 PSIG
  5. SUCTION PRESSURE @ 600 CFM IS 144 PSIG

ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART

American Standard 4A7A3 Split System Air Conditioner
61

COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES.
ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1); LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE:

  1. OUTDOOR TEMP. 82 F.
  2. INDOOR WET BULB 67 F.
  3. AT INTERSECTION
  4. LIQUID PRESSURE @ 600 CFM IS 327 PSIG
  5. SUCTION PRESSURE @ 600 CFM IS 139 PSIG

ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
About American Standard Heating and Air Conditioning
American Standard has been creating comfortable and affordable living environments for more than a century. For more information, please visit www.americanstandardair.com.
The AHRI Certified mark indicates company participation in the AHRI Certification program. For verification of individual certified products, go to ahridirectory.org.
The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

American Standard User Manuals

Related Manuals