DELIXI CDC19s Series Switching Capacitor Contactors User Manual

June 9, 2024
DELIXI

CDC19s Series Switching Capacitor Contactors

Series
User Manual

Please carefully read this User Manual before installing and operating the product, and keep this manual properly for future reference

CDC19s Series Switching Capacitor Contactor

Safety Notice Please carefully read this instruction before the installation, operation, run, maintenance, and inspection, and follow the contents of the instruction to properly install and operate this product.

Danger:

  • Do not operate the contactor with your wet hands;
  • Do not touch the energized parts during operation;
  • Mark sure that the product is deenergized during the maintenance and service;

Caution:

  • The installation, maintenance and service shall be performed by the qualified professional;
  • Please confirm that the product voltage, current, frequency and usage category meet the requirements before use;
  • Please turn on teh control loop for no-load operation test, and then power on the load after no any abnormality is found during test;
  • Please tighten the terminal blocks regularly and remove the deposited dust;
  • Do not allow foreign objects fall into the product:
  • Not used for jogging;
  • To purchase accessories, please select the matching accessories provided by our company;
  • If found any damage or abnormal sound when unpacking, please refuse to use it and contact the supplier;
  • When scrapping the product, please dispose the product waste properly. Thanks for your cooperation.

About CDC19s Series Product

  • Panel Introduction

panel

Fig. 1 Product Diagram

Legends:

1 – Main circuit outlet terminal 2/T1, 4/T2, 6/T32

2 – Product model

3 – Main circuit inlet terminal 1/L1, 3/L2, 5/L3

4 – Coil inlet terminal A1

5 ­ Coil outlet terminal A2

6 ­ Normally-closed auxiliary inlet terminal 21NC

7 ­ Normally-open auxiliary inlet terminal 13NO

8 ­ Normally-closed auxiliary inlet terminal 31NC

9 ­ Pre-charged contact set

10 – Normally-open auxiliary outlet terminal 32NC

11 – Normally-open auxiliary outlet terminal 14NO

12 ­ Normally-closed auxiliary outlet terminal NC 22 13 ­ Coil outlet terminal A2

14 – Current limiting reactor

15 ­ Company logo

16 – Product model

17 ­ Certification mark

18 ­ Standards: GB/T 14048.4, IEC 60947-4-1

19 – Insulation voltage Ui

20 ­ Ith: Resistive free air current

21 – Ue, Ie, and controllable capacitor capacity under the usage category

22- Company name

  • Technical Parameters

Main circuit

Table 1 Technical parameters of main circuit

Product model

|

Rated

insulation

voltage Ui V

|

Rated

operating

current Ie A

|

Rated operating voltage Ue A

|

Resistive free  air current Ith A

|

Controllable capacity

|

Inrush current  suppression

capacity

---|---|---|---|---|---|---

|

220/230V 380/400V

|

660/690V

Rated capacity Qn kVar

CDC19s-25

|

690

|

17

|

220/230V

380/400V

660/690V

|

25

|

6

|

12

|

18

|

35Ie

CDC19s-32

|

24

|

32

|

9

|

18

|

26

CDC19s-43

|

29

|

43

|

10

|

20

|

36

CDC19s-63

|

43

|

63

|

15

|

30

|

48

|

50Ie

CDC19s-95

|

63

|

95

|

22.5

|

45

|

63

CDC19s-115

|

87

|

125

|

35

|

60

|

92

CDC19s-150

|

115

|

200

|

46

|

80

|

/

|

60Ie

CDC19s-170

|

130

|

200

|

52

|

90

|

/

Aux. circuit

Table 2 Basic parameters of the auxiliary circuit

Usage category

|

Rated

insulation

voltage Ui

|

Resistive free air current Ith

|

Control capacity

|

Rated operating current Ie

---|---|---|---|---

Making

|

Breaking

|

220V

|

380V

AC-15

|

690V

|

10A

|

3600VA

|

360VA

|

1.6A

|

0.95A

DC-13

|

33W

|

0.15A

|

Normal Operation, Installation, and Transport Conditions

Normal Operation and Installation Conditions

(1) The ambient air temperature is not higher than +40℃, and is not below -5℃; the average value within 24  hours does not exceed +35℃;

(2) The altitude of the installation site does not exceed 2000m;

(3) The relative humidity of the atmosphere does not exceed 50% at the maximum ambient temperature of +40℃,  and a higher relative humidity is allowed lower temperatures, such as 90% at +20℃. Protective measures shall be  taken for condensation occasionally occurred due to temperature changes;

(4) The installation position should be vertical, and the inclination angle in each direction should not exceed ±5°;

(5) Installed in a place where there is no shock vibration for rain and snow intrusion;

(6) Pollution level: Level 3;

(7) Installation category: Class III;

(8) Rated impulse withstand voltage Uimp: CDC19s-25~43; CDC19s-63~170: 6kV;

(9) Rated frequency: 50Hz;

(10) Protection grade: CDC19s-25~115 IP20, CDC19s-150, 170 IP00;

(11) Suitable for 8h working system, intermittent working system, uninterrupted working system, and short-time  working system.

Normal Storage and Transport Conditions

(1) Temperature: -25℃ ~ +55℃, up to +70℃ in a short time (24h);

(2) Relative humidity: ≤95%;

(3) Please handle the product gently, do not upside it down, and prevent harsh collision during transport. The  product shall not be affected by the rain or snow intrusion during transportation and storage.

Install product

● All contactors are installed with screws, and CDC19s-25, 32, and 43 are also be mounted on a 35mm  mounting rail and CDC19s-63, 95, and 115 can be mounted on a 35mm or 75mm rail.

● The outline and installation dimensions of contactor are shown in Fig. 2, Fig. 3, Fig. 4 and Table 3.

Table 3 Outline and installation dimensions Unit: mm

Model

|

Outline dimensions

|

Installation dimensions

---|---|---

Amax

|

Bmax

|

Cmax

|

Dmax

|

Emax

|

Fmax

Debugging and Operation

● Check whether the technical parameters of product comply with the operation requirements;

● Please separate the resistance wires between the phases after installation;

● The inlet line and outlet line of contractor must be connected firmly to prevent burns to the terminals and  products due to terminal block overheating caused by loose connection;

● The insulation resistance of the electrical appliance selected for the discharge device in the power factor  compensation equipment shall be greater than √2Ue;

● Power on the control circuit and conduct the no-load operation test, and then connect the load after no  abnormality is found during test;

● Prevent foreign matters falling into the product;

● It is recommended to select SCPD according to type 1 coordinated protection; the model of fuse is shown in  Table below.

Table 4 Model of matching fuse

Product model

|

---|---

Model of

matching fuse  of main circuit

Model of

matching fuse  of auxiliary

circuit

● The recommended sectional area and tightening torque of the wire of the terminal block are listed in Table 5.

Table 5 Recommended sectional area and tightening torque of the wire of the terminal block

Product model

|

CDC19s

25

|

CDC19s

32/43

|

CDC19s

-63

|

CDC19s

95/115

|

CDC19s

150/170

---|---|---|---|---|---

Main circuit wiring

Soft wire without terminal  block

|

One wire

|

mm2

|

1…4

|

1.5…10

|

4…25

|

6…50

|

95mm2

Two wires

|

mm2

|

1…4

|

1.5…6

|

4…16

|

6…25

|

/

Soft wire with terminal block

|

One wire

|

mm2

|

1…4

|

1…6

|

4…25

|

6…50

|

/

Two wires

|

mm2

|

1…2.5

|

1…4

|

4…10

|

6…16

|

/

Hard wire without terminal  block

|

One wire

|

mm2

|

1…4

|

1.5…6

|

4…25

|

6…50

|

/

Two wires

|

mm2

|

1…4

|

1.5…6

|

4…10

|

6…25

|

/

Tightenin torque

|

N.m

|

1.2

|

1.8

|

5

|

9

|

12

Control and aux. loop wiring

Soft wire without terminal  block

|

One wire

|

mm2

|

1…4

Two wires

|

mm2

Soft wire with terminal block

|

One wire

|

mm2

|

1…2.5

Two wires

|

mm2

Hard wire without terminal  block

|

One wire

|

mm2

|

1…4

Two wires

|

mm2

Tightenin torque

|

N.m

|

1.2

Maintenance and Service

● Tighten the terminal blocks of contractor firmly on a regular basis, and remove the deposited dust, otherwise the  risk of fire or short circuit may occur;

● Small metal particles sprayed around the contactor or on the arc hood should be removed, and the contactor  shall stop when the contact surface is burnt until the base material is exposed.

Fault Analysis and Solution

The common fault analysis and solution see Table 6.

Table 6 Common fault analysis and solution

Fault

|

Cause

|

Solution

---|---|---

The iron core cannot  be pulled in or the  suciton force is  insufficient (that is,  the contact is closed  but the iron core is  not completed pulled in)

|

1. The power supply voltage is too low or  fluctuates too much;

2. The power capacity of the operating circuit is  insufficient or the wire is broken, wiring is  incorrect and the control contact has poor contact; 3. The technical parameters of coil are inconsistent  with the working conditions;

4. The product itself is damaged (such as coil  broken or burnt, and mechanical movable part  blocked).

|

1. Incease the power voltage;

2. Increase the power capacity;  replace the line; repair the control contact;

3. Replace the contactor;

4. Eliminate the blockage fault, and  replace the contactor.

No release or slow  release

|

1. Contact fusion welding;

2. The mechanical movable part is blocked; 3. There is oil strin or dust sticking to the pole face  of the iron core.

|

1. Eliminate the fuse welding fault,  and repair or replace contactor; 2. Eliminate the blockage fault; 3. Clean the pole face of the iron  core.

Coils are overheated  or burnt

|

1. The power voltage is too high or too low; 2. The technical parameters (such as rated voltage,  frequency, on-load factore and applicable working system) of the coil are inconsistent with the actual  operation;

3. The moving part is blocked;

4. The pole face of iron core is unfatted or stuck  with dust.

|

1. Adjust the power voltage;

2. Replace the contactor;

3. Eliminate the mechancial  blockage fault;

4. Clean the pole face.

Large noise issued  from the

electromagnets (AC)

|

1. The power voltage is too low;

2. The magnetic system is skewed or mechanically  blocked, making that the iron core cannot be pulled  in flattly;

3. The pole face of iron core is rusted or intruded  by foreign matter;

4. The short-circuit ring is broken or the pole face  of iron core is worn excessively and uneven.

|

1. Increase the operating loop  voltage;

2. Adjust the magnetic system or  eliminate the mechanical blockage  fault;

3. Clean the pole face;

4. Replace the contactor.

Contact fusion

welding

|

1. The operating frequency is too high or the  product is overloaded;

2. Short circuit at the load side;

|

1. Replaced by an appropriate  contactor:

2. Eliminate short circuit fault.

Resistance wire burnt

|

The resistance will be burnt if the closing current is  too large beyond the suppression capacity of this  switching capacitor contactor when the contactor is  closed.

|

Replaced by an appropriate  contactor

Company Commitment

Under the condition that users follow the use and storage conditions and the product are well sealed, within 24  months from the production date, our company will provide repair and replacement service free of charge for any damage or abnormal operation due to poor manufacture quality. A paid repair will be provided if the warranty  period expires. For any damage due to one of the following situations, a paid repair will be given even if within  the warranty period:

(1) Improper operation, maintenance, or storage;

(2) Modified without permission or improper repair;

(3) Damage due to falling off or caused during installation after purchase;

(4) Force majeure such as earthquakes, fires, lightning strikes, abnormal voltages, and secondary disasters; If  you have any question, please contact the dealer or our company’s customer service department. Customer service hotline: 400-826-8008

Name: Capacitor changeover contactor

Model: CDC19s Series

This product passes the inspection and is allowed to be

shipped.

Certificate

Standard: GB/T 14048.4

Inspector: Check 06

DELIXI ELECTRIC LTD

Production date: See label on inner box


DELIXI ELECTRIC LTD

Address: Delixi High-Tech Industrial Park, Liushi Town, Leqing City, Zhejiang P/C: 325604 Tel: (86-577) 6177 8888

Fax: (86-577) 6177 8000

Customer Service hotline: 400-826-8008

www.delixi-electric.com