INSTALLATION & MAINTENANCE MANUAL
BTxxACTEMS
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following products: BT9ACTEMS / BT14ACTEMS / BT2OACTEMS
SAFETY
- This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
- Please isolate mains prior to installation or maintenance
- Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
- Please note the IP (Ingress Protection) rating of this luminaire when deciding the location for installation
- This product is Class II double insulated
- This product is IP65 rated
INSTALLATION
Note – Microwave sensors may not be suitable for all installations, for example enclosed spaces, as they are able to detect movement through non- metallic surfaces like plasterboard and thin doors
- Provide power to the required point of installation. Suitable IP rated junction boxes should be used where required
- Remove the diffuser by rotating bezel anti-clockwise (see Fig. 1)
- Remove the fastening screw securing the LED plate and open the LED plate (see Fig. 2)
- Mark the location of the fixing holes, and drill the holes ensuring not to infringe with any gas/water pipes or electrical cables
- Feed the cable via the rubber grommet to retain IP rating, and secure the baseplate to the surface
- Connect the Live (brown). Emergency Live (L1) and Neutral (blue) to the terminals on the terminal block (see Fig. 3)
- The additional terminal called Slave Live (12) is available to enable the sensor to power on additional luminaires. A max. LED load of 400W can be controlled by the sensor
- Please see DIP Switch Layout to set up sensor
- Connect the battery to the inverter
- Refasten the LED plate screw
- Choose the required colour temperature by means of the DIP switch (see Fig. 4)
- Reattach the diffuser by rotating clockwise
- Switch on and check for correct operation, ensuring the green indicator LED is illuminated
- We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test
Note: this fitting shuts off power to the Lithium Ion battery periodically to prevent overcharging. Therefore, the green LED indicator has been set up to indicate that the emergency inverter is in good condition, not to indicate that the battery is charging. The installer must ensure that the battery is connected.
SENSOR LAYOUT
DIP SWITCH LAYOUT
*This is the time period the lamp remains at 100% after no motion is detected
Clean with a soft dry cloth only.
do not use aggressive cleaning products or solvents which may damage the
product. Do not use any source of high-pressure washers to maintain or clean
this luminaire.
This product is non-dimmable.
This product should be dismantled for disposal when it reaches the end of its
life. Please see website for dismantling instructions.
This product should be recycled in the correct manner when it reaches the end
of its life.
Check local authorities for where facilities exist. The batteries in this
luminaire are Lithium Ion and must be disposed of correctly. Please contact
the local authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 5 years (excluding battery) from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations. improper use. or removal of the batch codes will invalidate the warranty. If this product should fail within its warranty period. it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with 855266
- Daily check — check LED charge indicator is illuminated
- Monthly functional test — simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- Annual 3-hour duration test – simulate a mains supply failure for a 3-hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- If the luminaire fails any of the above tests. please contact a qualified electrician
ML Accessories Limited
LU5 4LTwww.mlaccessories.co.uk
Supplied By:
(UK) Manufacturer
ML Accessories Ltd, Unit E Chiltern Park, Boscombe Road,
Dunstable LU5 4LT, www.mlaccessories.co.uk
(EU) Authorised Representative nnuks Holding GmbH, Niederkasse-ler Lohweg 18,
40547 Dusseldorf, Germany,
Email: eprel@nnuks.com
DCJUL22_V3
Manufacturers Declaration of Conformity
For ML Accessories (Knightsbridge)
Electrical products in accordance with CE marking
ML Accessories Ltd. Declare that all products have been designed, manufactured, and tested in accordance with the requirements of the relevant legislation CE marking legislation In Accordance with the following Directives:
2014/35/EU | Low Voltage Directive |
---|---|
2014/30/EU | EMC Directive |
2014/53/EU | Radio Equipment Directive |
Including Legislation
1907/2006 | REACH |
---|---|
2015/863 | RoHS |
2021/341 | ERP |
Safety Standards
Full individual declarations and specific safety standards applicable to
relevant product series can be found on our website
www.mlaccessories.co.uk
We hereby declare that the equipment named above has been designed to comply
with the relevant sections of the above referenced specifications. The product
complies with all essential requirements of the directives.
ML Accessories Ltd. Unit E Chiltern Park, Boscombe Road, Dunstable.
Bedfordshire, LU5 4LT
This declaration becomes invalid if technical or operational modifications are
introduced without ML Accessories Ltd. written consent.
ML Accessories Ltd. declare that all products have been designed,
manufactured, and tested in accordance with the requirements of the relevant
legislation
UKCA marking legislation
UK SI 2016 No. 1091 | Electro Magnetic Compatibility Regulations 2016 |
---|---|
UK SI 2016 No. 1101 | The Electrical Equipment (Safety) Regulations 2016 |
UK SI 2012 No. 3032 | Restriction of the use of Certain Hazardous Substances in |
Electrical and
Electronic Equipment Regulations 2012
UK SI 2017 No. 1206| Radio Equipment regulations 2017
UK SI 2021 No. 1095| The Ecodesign for Energy-Related Products and Energy
Information (Lighting Products) Regulations 2021
Included Legislation
UK SI 2008 No. 2852 | UK REACH |
---|---|
UK SI 2013 No. 3113 | WEEE |
Safety Standards
Full individual declarations and specific safety standards applicable to
relevant product series can be found on our website
www.mlaccessories.co.uk
We hereby declare that the equipment named above has been designed to comply
with the relevant sections of the above referenced specifications. The
products comply with all essential requirements of the directives.
ML Accessories Ltd. Unit E Chiltern Park, Boscombe Road, Dunstable.
Bedfordshire, LU5 4LT
This declaration becomes invalid if technical or operational modifications are
introduced without ML Accessories Ltd. written consent.
TEST RECORD SHEET
INITIAL COMMISSIONING
3 HOUR TEST| SIGNED| DATE
|
MONTH| TEST| FIRST YEAR| SECOND YEAR| THIRD YEAR|
FOURTH YEAR| FIFTH YEAR
SIGNED| DATE| SIGNED| DATE| SIGNED| DATE|
SIGNED| DATE| SIGNED| DATE
1| FUNCTIONAL| | | | | | | | | |
2| FUNCTIONAL| | | | | | | | | |
3| FUNCTIONAL| | | | | | | | | |
4| FUNCTIONAL| | | | | | | | | |
5| FUNCTIONAL| | | | | | | | | |
6| FUNCTIONAL| | | | | | | | | |
7| FUNCTIONAL| | | | | | | | | |
8| FUNCTIONAL| | | | | | | | | |
9| FUNCTIONAL| | | | | | | | | |
10| FUNCTIONAL| | | | | | | | | |
11| FUNCTIONAL| | | | | | | | | |
12| 3 HOUR| | | | | | | | | |
Installed by:
Installation date:
Contact number:
Daylight sensor
When set to Disable, the daylight sensor will switch the lamp on when motion is detected regardless of the ambient light level
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains a light source of energy efficiency class D (BT9ACTEMS) / E (BTI4ACTEMS. BT2OACTEMS) to Regulation (EU) No. 2019/2015. This product contains an LED light source which can be replaced by the end user and a control gear which can be replaced by a professional.