Stream Stream EC
PLASTIC SOUND-INSULATED FAN
User’s manual
Stream EC Plastic Sound Insulated Fan
This user’s manual is a main operating document intended for technical,
maintenance, and operating staff.
The manual contains information about purpose, technical details, operating
principle, design, and installation of the Stream unit and all its
modifications.
Technical and maintenance staff must have theoretical and practical training
in the field of ventilation systems and should be able to work in accordance
with workplace safety rules as well as construction norms and standards
applicable in the territory of the country.
This unit is not intended for use by persons (including children) with reduced
physical, sensory or mental capabilities, or lack of experience and knowledge,
unless they have been given supervision or instruction concerning use of the
unit by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the unit.
This appliance can be used by children aged from 8 years and above and persons
with reduced physical, sensory or mental capabilities or lack of experience
and knowledge if they have been given supervision or instruction concerning
use of the appliance in a safe way and understand the hazards involved.
Cleaning and user maintenance shall not be made by children without
supervision.
Children shall not play with the appliance.
Connection to the mains must be made through a disconnecting device, which is
integrated into the fixed wiring system in accordance with the wiring rules
for design of electrical units, and has a contact separation in all poles that
allows for full disconnection under overvoltage category III conditions.
If the supply cord is damaged, it must be replaced by the manufacturer, its
service agent, or similarly qualified persons in order to avoid a safety
hazard.
Ensure that the unit is switched off from the supply mains before removing the
guard.
Precautions must be taken to avoid the back-flow of gases into the room from
the open flue of gas or other fuel-burning appliances.
The appliance may adversely affect the safe operation of appliances burning
gas or other fuels (including those in other rooms) due to back flow of
combustion gases. These gases can potentially result in carbon monoxide
poisoning. After installation of the unit the operation of flued gas
appliances should be tested by a competent person to ensure that back flow of
combustion gases does not occur.
Do not attach the product to the support using glue or adhesives. Use only the
fastening method specified in the «User’s manual».
All operations described in this manual must be performed by qualified
personnel only, properly trained and qualified to install, make electrical
connections and maintain ventilation units.
Do not attempt to install the product, connect it to the mains, or perform
maintenance yourself.
This is unsafe and impossible without special knowledge.
Disconnect the power supply prior to any operations with the unit.
All user’s manual requirements as well as the provisions of all the applicable
local and national construction, electrical, and technical norms and standards
must be observed when installing and operating the unit.
Disconnect the unit from the power supply prior to any connection, servicing,
maintenance, and repair operations.
Only qualified electricians with a work permit for electrical units up to 1000
V are allowed for installation. The present user’s manual should be carefully
read before beginning works.
Check the unit for any visible damage of the impeller, the casing, and the
grille before starting installation. The casing internals must be free of any
foreign objects that can damage the impeller blades.
While mounting the unit, avoid compression of the casing!
Deformation of the casing may result in motor jam and excessive noise.
Misuse of the unit and any unauthorised modifications are not allowed.
Do not expose the unit to adverse atmospheric agents (rain, sun, etc.).
Transported air must not contain any dust or other solid impurities, sticky
substances, or fibrous materials.
Do not use the unit in a hazardous or explosive environment containing
spirits, gasoline, insecticides, etc.
Do not close or block the intake or extract vents in order to ensure the
efficient air flow.
Do not sit on the unit and do not put objects on it. The information in this
user’s manual was correct at the time of the document’s preparation.
The Company reserves the right to modify the technical characteristics,
design, or configuration of its products at any time in order to incorporate
the latest technological developments.
Never touch the unit with wet or damp hands.
Never touch the unit when barefoot.
BEFORE INSTALLING ADDITIONAL EXTERNAL DEVICES, READ THE RELEVANT USER MANUALS.
**** THE PRODUCT MUST BE DISPOSED SEPARATELY AT THE END OF ITS SERVICE LIFE.
DO NOT DISPOSE THE UNIT AS UNSORTED DOMESTIC WASTE.
OVERALL DIMENSIONS
| ØD| L| B| H| M
---|---|---|---|---|---
Stream 100/125| 100| 752| 253| 273| 148
125| 679
Stream 150| 150| 606
160
Stream 100/125 (spigot ø100 mm)
Stream 100/125 (spigot ø125 mm)
Stream 150 (spigot ø150 mm)
Stream 160 (spigot ø150 mm with a rubber seal)
DELIVERY SET
Fan – 1 pc.
Screws and dowels – 4 pcs.
User’s manual – 1 pc.
Packing box – 1 pc.
Rubber seal (for the Stream 150/160 model) – 2 pcs.
BRIEF DESCRIPTION
The product described herein is a plastic sound-insulated fan for supply or
extract ventilation of premises.
The fan is connected to the ø 100, 125, 150 and 160 mm air ducts.
OPERATION GUIDELINES
The unit is designed for connection to power mains with the parameters
specified in the «Technical data» section.
The fan is rated for continuous operation.
Air motion direction in the system must match the pointer on the fan casing.
The Stream unit is rated as a Class II and Stream EC as Class I electrical
appliance.
Ingress protection rating against access to hazardous parts and water ingress
is IPХ4.
The fan is rated for operation at the ambient temperature ranging from +1 °C
up to +40 °C.
DESIGNATION KEY
TECHNICAL DATA
To comply with the ErP 2018 regulation, a local demand controller and speed controller must be used.
MOUNTING
The fan is suitable both for horizontal or vertical mounting on the floor, on the wall or on the ceiling. The fan can be installed independently or as part of a set with parallel or in-series connection.
The diameter of the spigots in the Stream 100/125 model can be changed using
adapters, and in the Stream 150/160 model using the rubber seal.
On outlet (discharge) spigot side it is necessary to install:
- in case of horizontal installation – a duct with a length of at least 1 m;
- in case of vertical installation – a canopy preventing moisture from getting into the fan.
The outlet spigot must always be connected to the air duct.
The fan wiring diagrams
Designations on diagrams:
L – line; N – neutral; LT – external switch terminal; L1 – minimum speed
terminal; High – maximum speed terminal; Med – medium speed terminal; Low –
minimum speed terminal; QF – automatic circuit breaker; S – external speed
controller; ST – external switch (for example, a light switch); X – input
terminal.
Designations on diagrams:
N — neutral
L — line
**** — grounding
R1 — internal speed controller
R2 — external speed controller
SW — DIP switch
ELECTRONICS OPERATION ALGORITHM
The fan speed without options can be controlled by voltage, as well as by
thyristor controllers.
A speed controller can be purchased separately.
Warning! When adjusting the voltage, ensure that there is no unusual noise or
vibration at reduced motor speed.
When adjusting the voltage, the motor current may exceed the rated current.
The fan is equipped with a thermal switch without self-reset.
Probable causes of the thermal switch tripping:
- non-compliance with the operating rules
- impeller jamming (clean the impeller)
- motor malfunction (turn off the unit, contact the Seller)
To reset the thermostat:
- Switch off the power supply.
- Find and eliminate the cause of overheating.
- Switch the power back on.
The Stream …T fan activates upon control voltage application to the LT input
terminal by the external switch (e.g. indoor light switch). After the control
voltage is off, the fan continues to operate within the set time period
adjustable from 2 to 30 min by the timer.
To adjust the fan turn-on delay time, turn the control knob T clockwise to
increase and counter-clockwise to decrease the turn-on delay time
respectively.
WARNING! The timer circuit is live! Disconnect the fan from power supply
prior to any adjustment operations.
The fan delivery set includes a specially designed plastic screwdriver for fan
settings adjustments.
Use it to change the turn-off delay time and the humidity set point.
Do not use a metal screwdriver, knife, etc. for adjustment operations not to
damage the circuit board.
The Stream …U/Un fan is equipped with a TSC electronic module (speed
controller with an electronic thermostat) for automatic speed control (air
flow) depending on the air temperature.
The terminal compartment incorporates 2 control knobs:
- presetting speed;
- setting electric thermostat threshold value.
This indicator lights when the air temperature exceeds the set value.
To set the thermostat threshold, rotate the thermostat control knob clockwise
to increase or counter-clockwise to decrease
the temperature set point accordingly.
To set the fan speed (air capacity), rotate the speed control knob in the same
way.
The fan operating logic may be based on temperature or timer indications:
As the air temperature drops 2 °C below the set point or if the initial
temperature is below the set point, the fan operates with the set speed.
The Stream …P fan is equipped with a speed controller that enables switching
the fan on/off and smooth speed (air flow) regulation from minimum to maximum
value.
Stream EC
The EC motor is controlled by sending of an external control signal from 0 to
10 V to the X2 terminal block or by the R1 internal speed controller. Control
method selection is carried out by means of the SW DIP switch:
- DIP switch in IN position. The control signal is set by the R1 internal speed controller that enables switching the fan on/off and smooth speed (air flow) regulation from minimum to maximum value. Rotations are controlled from the minimum (extreme right position) to the maximum (extreme left position). When rotating counter-clockwise, the rotations increase.
- DIP switch in EXT position. The control signal is set by the R2 external control unit.
DO NOT USE A METAL SCREWDRIVER, KNIFE, ETC. FOR ADJUSTMENT OPERATIONS NOT TO DAMAGE THE CIRCUIT BOARD
TECHNICAL MAINTENANCE
The fan surfaces must be regularly cleaned (once in 6 months) from dirt and
dust.
Disconnect the fan from power mains prior to any maintenance operations.
To clean the fan, use a soft cloth or a brush wetted in a mild detergent
solution.
Do not allow water or liquid come into contact with electric components.
Wipe the surfaces dry after cleaning.
TROUBLESHOOTING
Problem | Possible reasons | Troubleshooting |
---|
When the unit is connected to power
mains, the fan does not rotate and does not respond to any controls.| No power
supply.| Make sure the power supply line is connected correctly, otherwise
troubleshoot a connection error.
Internal connection fault.| Contact the Seller.
Low air flow.| The ventilation system is clogged.| Clean the ventilation
system.
Increased noise, vibration.| The impeller is clogged.| Clean the impeller.
The fan is not secured well or is not mounted properly.| Troubleshoot the
installation error.
The ventilation system is clogged.| Clean the ventilation system.
STORAGE AND TRANSPORTATION REGULATIONS
- Store the unit in the manufacturer’s original packaging box in a dry closed ventilated premise with temperature range from +5 ˚С to +40 ˚С and relative humidity up to 70 %.
- Storage environment must not contain aggressive vapors and chemical mixtures provoking corrosion, insulation, and sealing deformation.
- Use suitable hoist machinery for handling and storage operations to prevent possible damage to the unit.
- Follow the handling requirements applicable for the particular type of cargo.
- The unit can be carried in the original packaging by any mode of transport provided proper protection against precipitation and mechanical damage. The unit must be transported only in the working position.
- Avoid sharp blows, scratches, or rough handling during loading and unloading.
- Prior to the initial power-up after transportation at low temperatures, allow the unit to warm up at operating temperature for at least 3-4 hours.
MANUFACTURER’S WARRANTY
The product is in compliance with EU norms and standards on low voltage
guidelines and electromagnetic compatibility.
We hereby declare that the product complies with the provisions of
Electromagnetic Compatibility (EMC) Directive 2014/30/ EU of the European
Parliament and of the Council, Low Voltage Directive (LVD) 2014/35/EU of the
European Parliament and of the Council and CE-marking Council Directive
93/68/EEC. This certificate is issued following test carried out on samples of
the product referred to above.
The manufacturer hereby warrants normal operation of the unit for 24 months
after the retail sale date provided the user’s observance of the
transportation, storage, installation, and operation regulations. Should any
malfunctions occur in the course of the unit operation through the
Manufacturer’s fault during the guaranteed period of operation, the user is
entitled to get all the faults eliminated by the manufacturer by means of
warranty repair at the factory free of charge. The warranty repair includes
work specific to elimination of faults in the unit operation to ensure its
intended use by the user within the guaranteed period of operation. The faults
are eliminated by means of replacement or repair of the unit components or a
specific part of such unit component.
The warranty repair does not include:
- routine technical maintenance
- unit installation/dismantling
- unit setup
To benefit from warranty repair, the user must provide the unit, the user’s manual with the purchase date stamp, and the payment paperwork certifying the purchase. The unit model must comply with the one stated in the user’s manual. Contact the Seller for warranty service.
The manufacturer’s warranty does not apply to the following cases:
- User’s failure to submit the unit with the entire delivery package as stated in the user’s manual including submission with missing component parts previously dismounted by the user.
- Mismatch of the unit model and the brand name with the information stated on the unit packaging and in the user’s manual.
- User’s failure to ensure timely technical maintenance of the unit.
- External damage to the unit casing (excluding external modifications as required for installation) and internal components caused by the user.
- Redesign or engineering changes to the unit.
- Replacement and use of any assemblies, parts and components not approved by the manufacturer.
- Unit misuse.
- Violation of the unit installation regulations by the user.
- Violation of the unit control regulations by the user.
- Unit connection to power mains with a voltage different from the one stated in the user’s manual.
- Unit breakdown due to voltage surges in power mains.
- Discretionary repair of the unit by the user.
- Unit repair by any persons without the manufacturer’s authorization.
- Expiration of the unit warranty period.
- Violation of the unit transportation regulations by the user.
- Violation of the unit storage regulations by the user.
- Wrongful actions against the unit committed by third parties.
- Unit breakdown due to circumstances of insuperable force (fire, flood, earthquake, war, hostilities of any kind, blockades).
- Missing seals if provided by the user’s manual.
- Failure to submit the user’s manual with the unit purchase date stamp.
- Missing payment paperwork certifying the unit purchase.
FOLLOWING THE REGULATIONS STIPULATED HEREIN WILL ENSURE A LONG AND TROUBLE-
FREE OPERATION OF THE UNIT.
USER’S WARRANTY CLAIMS SHALL BE SUBJECT TO REVIEW ONLY UPON PRESENTATION OF
THE UNIT, THE PAYMENT DOCUMENT AND THE USER’S MANUAL WITH THE PURCHASE DATE
STAMP.
Certificate of acceptance
Stream____
The fan is recognized as serviceable.