Function and area of use

This document provides guidelines on How to enter the X2 terminals Service menu, furter manouver to the diafnostics page, and finally enter the settings, where disabling the flash wear warning can be utilized

About this Startup document

This Startup document should not be considered as a complete manual. It is an aid to be able to Startup a normal application quickly and easily.

Copyright © Beijer Electronics, 2020 This documentation (below referred to as ‘the material’) is the property of Beijer Electronics. The holder or user has a non-exclusive right to use the material. The holder is not allowed to distribute the material to anyone outside his/her organization except in cases where the material is part of a system that is supplied by the holder to his/her customer. The material may only be used with products or software supplied by Beijer Electronics. Beijer Electronics assumes no responsibility for any defects in the material, or for any consequences that might arise from the use of the material. It is the responsibility of the holder to ensure that any systems, for whatever applications, which is based on or includes the material (whether in its entirety or in parts), meets the expected properties or functional requirements. Beijer Electronics has no obligation to supply the holder with updated versions.

Use the following hardware, software, drivers and utilities in order to obtain a stable application:

In this document we have used following software and hardware
X2 terminals

For further information refer to

  • Manual name/number
  • Beijer Electronics knowledge database, HelpOnline

This document and other Startup documents can be obtained from our homepage. Please use the address [email protected] for feedback about our Quick Start documents.

General

The teminals internal disk, is an electronic flash memory, and those types of memory have a certain lifetime, based on the number of write cycles to each memory cell. Normal use is not antisipated to wear out the memory within what are considered to be normal lifetime of such equipement. However extensive datalogging and other write intensive operations, could change this situation. In such cases the recomandation is to insert an industrial SD card, and move the database to this location instead. In this way one can easily replace the SD card IF memory wearout or other memory failure occurs. In the X2 terminals image we have two types of Flash Wear Warnings:

Wear level warning

Beijer-ELECTRONICS-SUEN00411-Disable-Flash-Wear-Warning-in-X2-Terminals-
FIG-1

It is evaluated by every 10% wear level

Flash Pre-EoL warning

Beijer-ELECTRONICS-SUEN00411-Disable-Flash-Wear-Warning-in-X2-Terminals-
FIG-2

  • Warning if the flash has been utilized more than 80%.
  • Warnings are visual 1 min after boot up & once a day at 09:00 (local time) unless suppressed
  • The service warning message can be suppressed for 7 days by checking the checkbox and press ok.
  • The warning message can be furter suppressed via settings menu in the terminals Service menu / Diagnostics / Settings
  • This suppression will be active until next warning message is calculated (evaluated every 10% wear level)

Entering the Service Menu

Perform the following steps to enter the service menu:

  1. Apply power to the panel.
  2. When the hourglass symbol disappears, press a finger on the screen and hold it (aprox 10-20 sec),until the touch calibration screen displays the following message: “Tap anywhere on screen or touch calibrate will start in 10 seconds.” (The screen goes all grey at this point)
  3. Now lift the finger and press once again to enter the service menu.

Beijer-ELECTRONICS-SUEN00411-Disable-Flash-Wear-Warning-in-X2-Terminals-
FIG-3

Diagnostics Menu

To enter Diagnostics press the Diagnostics button shown above:

Beijer-ELECTRONICS-SUEN00411-Disable-Flash-Wear-Warning-in-X2-Terminals-
FIG-4

Suppress flash\disk wear warning
Now press the “settings” button in the low left corner of the diagnostics page:

Beijer-ELECTRONICS-SUEN00411-Disable-Flash-Wear-Warning-in-X2-Terminals-
FIG-5

Set the Suppress disk wear warning to ON Then close the dialogues. Doned The warning dialogue is now suppressed until the next 10% wear level is reached. If the time to reach this next 10% level is still to fast to secure a reasonable lifetime, the wear warning will reoccure. If the time is within what is considered normal wear, the warning will not appear any more.

About Beijer Electronics

Beijer Electronics is a multinational, cross-industry innovator that connects people and technologies to optimize processes for business-critical applications. Our offer includes operator communication, automation solutions, digitalization, display solutions and support. As experts in user-friendly software, hardware
and services for the Industrial Internet of Things, we empower you to meet your challenges through leading-edge solutions. Beijer Electronics is a Beijer Group company. Beijer Group has a sale over 1.6 billion SEK in 2019 and is listed on the NASDAQ OMX Nordic Stockholm Small Cap list under the ticker BELE. www.beijergroup.com

China
Shanghai

USA
Salt Lake City

Contact us

Global offices and distributors
Optional details if one wants to add local contact information in the document!

Local office Telephone E- mail
Sweden +4640358600

[email protected]

Head Office Subsidiaries Beijer Electronics AB Click here for details P.O. Box 426, Stora Varvsgatan 13a SE-201 24 Malmö, SWEDEN Telephone +46 40 35 86 00

Reg no. 556701-4328 VAT no SE556701432801 www.beijerelectronics.com [email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Beijer ELECTRONICS User Manuals

Related Manuals