HiSPEC HSA-BH-RF10-PRO Longlife Battery Operated Heat Alarm Instruction Manual
- June 9, 2024
- HiSPEC
Table of Contents
- MAIN FEATURES
- SPECIFICATION
- LOCATING THE HEAT ALARM
- POSITIONING THE HEAT ALARM
- INSTALLING THE HEAT ALARM
- OPERATING YOUR HEAT ALARM
- TESTING YOUR HEAT ALARM
- BATTERY SEALED-IN NOT FOR REPLACEMENT
- IN THE EVENT OF FIRE
- MAINTAINING YOUR HEAT ALARM
- IMPORTANT SAFEGUARDS
- LIMITATIONS OF THE HEAT ALARM
- HEAT ALARM LIMITED WARRANTY
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
HSA-BH-RF10-PRO Longlife Battery Operated Heat Alarm
Instruction Manual
LONGLIFE BATTERY OPERATED HEAT ALARM WITH WIRELESS INTERCONNECT
MAIN FEATURES
- Wireless Interconnection Using Radio Links (Self Learn pairing)
- 10 year Lithium Battery
- Hush Feature
- Power & Alarm Test Button
- Low Battery Warning
- Loud 85db alarm signal
- Supplied with wall plugs & screws
- Pre-warning fault signal
- Compatible with Control Unit HSSA/CU/RF10-PRO
This instruction leaflet contains important information on the correct installation and operation of your smoke alarm. Read this leaflet fully before attempting installation and retain for future reference.
SPECIFICATION
Power Source: | 3V Lithium Battery |
---|---|
Battery Life: | 10 Year (sealed) |
Transmitting & receiving | max. 80metres (outer space) |
distance: | max. 50metres (indoor) |
Max. Wireless interconnection: | 20 units |
Operation Temperature: | 0°C-40°C |
Ambient Humidity: | 10%-90% |
Coverage Area: | 20m² |
Alarm Sound Level: | 85 Decibels at 3 metres |
Approval: | Certified to BS EN5446-2:2003 |
Maximum Distance from wall: | 7.7m |
Recommended Spacing: | 13.5m |
Activation Temperature: | 60ºC |
Transmit & Receive frequency: | 868MHz |
LOCATING THE HEAT ALARM
Heat Alarms are intended to be supplementary to Smoke Alarms and should only be placed in areas where smoke alarms cannot be used.
This heat alarm has a built-in wireless interconnection. It can transmit and
receive with other smoke alarms and heat alarms. This Heat alarm gives a fire
warning when the temperature at the unit reaches 60ºC. It is ideal for
kitchens, garages, cellars, boiler rooms, attics and other areas where there
are normally high levels of fumes, smoke or dust which preclude the use of
Smoke Alarms due to the risk of false alarms.
All the Heat Alarms and Smoke Alarms should be interconnected to ensure the
early warning will be heard, particularly by somebody sleeping. A properly
designed early warning fire system ensures the alarm is given before the
escape routes become blocked with smoke. Therefore there must be Smoke Alarms
along the escape routes as Heat Alarms would not give sufficient warning.
However, a fire in a closed room (e.g. kitchen) adjoining the escape route,
can eventually cause the corridor to become smoke-logged due to smoke leaking
out from around the door before adequate warning can be given by detectors in
the corridor. A heat alarm in the closed room may give early warning of fire
in that room.
If your dwelling is on a single storey, for minimum protection you should fit
a Smoke Alarm in a corridor or hallway between the sleeping and living areas.
Place it as near to the living areas as possible and ensure the audible alarm
can be heard when the bedrooms are occupied. See Figure 1 for examples.
If your dwelling is multi-storey, for minimum protection one Smoke Alarm
should be fitted at the bottom of the staircase with further alarms fitted on
each upstairs landing. This includes basements but excludes crawl spaces and
unfinished attics. See Figure 2 for examples.
NOTE: For maximum protection Smoke Alarms should be fitted in every room
(except kitchen, bathroom and garage). Heat Alarms located in kitchens,
garages, boiler rooms etc. within 5.3m (17ft) of potential fire sources. DO
NOT FIT THE HEAT ALARM IN THE BATHROOM, SHOWER ROOMS or other room where the
unit may be triggered by steam or condensation.
FIGURE 1 – SINGLE STORE DWELLING
FIGURE 2 – 2/3 STOREY DWELLING POSITIONING
POSITIONING THE HEAT ALARM
Ceiling Mounting
As hot air rises and spread out, it is advisable to mount on a ceiling in a
central position. Avoid areas where there is no air circulation, e.g. corners
of rooms and keep away from items which may prevent the free flow of air.
Place the unit at least 300mm from and light fitting or decorative object
which might obstruct smoke / heat entering the alarm. Keep at least 300mm away
from walls. See Figure 3i.
Wall Mounting
Do not mount tight into the corners. Put the top edge of your smoke alarm
between 150 and 300mm below the ceiling. Keep at least 300mm from room
corners. See Figure 3i (Wall mounting is not recommended for Heat Alarms)
On a Sloping Ceiling
In areas with sloping or peaked ceilings install your Heat Alarm 900mm from
the highest point measured horizontally because “dead air” at the apex may
prevent smoke / heat from reaching the unit. See Figure 3ii.
Figure 3i – Positioning the smoke / heat detector Figure 3ii
Areas to be avoided include the following:
- Situations where the temperature may fall below 0°C or rise above 40°C for extended periods of time
- Humid areas such as bathrooms, kitchens, shower rooms where the relative humidity may exceed 90%
- Near a decorative object, door, light fitting, window moulding etc., that may prevent heat from entering the alarm.
- Adjacent to or directly above hot components such as radiators or wall vents that can affect the direction of air currents.
- In very dusty or dirty environments such as workshops.
- Locate unit at least 1.5m and route wiring at least 1m away for fluorescent light fittings as electrical “noise” and/or flickering may affect the unit. Do not wire into the same circuit as fluorescent lights or dimmers.
- Do not locate in insect infested areas. Insects and contamination on the Heat Alarm sensor can increase its response time.
PAIRING THE HEAT ALARM
This heat alarm is powered by battery and requires no additional wiring.
On First Alarm
- Attach the mounting plate to the alarm. (This is done by lining up the tab on the mounting plate with the arrow on the smoke alarm)
- Turn clockwise to activate battery.
- Press black button and hold for approx 5 seconds.
(LED will go RED for 30 seconds) Alarm is now in paring mode.
On all additional alarms
- Press black button twice (LED will FLASH RED 5 times
- The alarms are now paired
IMPORTANT!
The Wireless Pairing Button is only used for wireless interconnection.
INSTALLING THE HEAT ALARM
- Attach the upper Heat alarm unit firmly into the mounting plate
- Place the mounting plate on the ceiling, and use the screws to secure the mounting plate.
- Having established the mounting location ensure that there are no electrical wiring or pipe work in the area adjacent to the mounting surface.
- Take the mounting plate and mark the two mounting holes’ locations.
- Drill holes in the positions marked.
- Insert wall plugs into the drilled holes.
- Screw mounting plate to mounting surface using a screwdriver not an impact driver. DO NOT OVER TIGHTEN.
Once mounting plate is secured to ceiling line up the alarm with mounting
plate and twist clockwise to attach mounting plate to alarm. This should now
be secured to the ceiling.
Lock in position by giving a clockwise quarter turn. This clockwise turn can
switch on the sealed-in battery in same time. i.e. power on the device
simultaneously
Test the alarm for correct operation by holding test button down for 20
seconds, once the alarm is integrated and installed.
OPERATING YOUR HEAT ALARM
Once the heat alarm has been installed a small indicator light (LED), positioned beside the test button, and should flash approximately once a minute in normal operation. If high temperature (60ºC) has been detected, the unit will emit a load pulsating alarm until the air is clear.
TESTING YOUR HEAT ALARM
It is recommended that you test your heat alarm once a week to ensure the
detector is working correctly. Push and hold the test button for up to 20
seconds to trigger all interconnectable alarms. A pulsating alarm should sound
to indicate the correct function. During the alarm condition the indicator
light will flash quickly.
After installation and after reoccupation of the dwelling following a vacation
etc, check all your alarms.
LOW BATTERY WARNING
If the heat alarm emits a short ‘beep’ once every 40 seconds the battery is at
the end of its life and this detector should be replaced immediately. This low
voltage warning will be given for at least 30 days. If the red indicator light
(LED) does not flash every 40 seconds then replace the whole heat alarm unit.
In this case, the other interconnected units in the system which are not in
low battery condition will chirps for a few seconds once an hour as long as
the detector with the “dead” battery beeps.
BATTERY SEALED-IN NOT FOR REPLACEMENT
ACTION IN THE EVENT OF A FALSE ALARM
- If there is a false alarm, simply press the test / hush button on the cover to mute the unit for 10 minutes.
- Leave the building as quickly as possible. Check room doors for heat or smoke. Do not open a hot door. Use an alternate escape route. Crawl along the floor, if possible, through a wet cloth or hold your breath. Do not stop to collect anything.
- If there are frequent nuisance/ false alarms it may be necessary to re-locate the device. If for some reasons the alarm continues to give false alarm, clean the alarm unit, see Section – MAINTAINING YOUR SMOKE ALARM). If cleaning the alarm does not correct the problem it can be returned to the place where you bought it.
IN THE EVENT OF FIRE
- Leave the building as quickly as possible. Check room doors for heat or smoke. Do not open a hot door. Use an alternate escape route. Crawl along the floor, if possible, through a wet cloth or hold your breath. Do not stop to collect anything.
- Meet at a pre-arranged meeting place outside the dwelling and check everybody is there.
- Call the Fire Brigade from outside the building immediately. The brigade should be summoned regardless of the size of the fire and regardless of whether there is a facility for transmission of alarms to a remote manned centre.
- Do not go back inside a burning building and wait for the Fire Brigade to arrive.
MAINTAINING YOUR HEAT ALARM
Clean your heat alarm regularly to prevent dust build up. This can be done
using a vacuum cleaner with the brush attachment. Clean gently around the
front grilled section and sides. Never use water, cleaners or solvents since
they may damage the smoke alarm.
When the battery is low, replace with a new heat alarm.
If the alarm fails to operate properly, please return to the wholesaler you
purchased it from.
NOTE: THE APPARATUS SHALL NOT BE EXPOSED TO DRIPPING OR SPLASHING.
PRE-WARNING FAULT SIGNAL (YELLOW LED)
When there is no fire or smoke accident, if the LED on front cover light is on
yellow, it means there may be dust inside or the unit cannot function
properly. This is a pre-warning signal that the user should replace the unit
with a new heat alarm.
IMPORTANT SAFEGUARDS
Installation of your heat alarm is only one step in your safety plan. Other important steps should be taken to further improve your safety:
- Install the heat alarm properly, following this instruction leaflet
- Test your heat alarm weekly
- Replace with a new heat alarm immediately once depleted
- Keep matches & lighters away from children
- Store flammable materials in a proper manner and never use them near naked flames or sparks
- Maintain emergency equipment such as Fire Extinguishers, escape ladders etc and ensure all occupants know how to use them correctly.
- Plan an escape route/s from your building in advance and ensure all occupants are aware of them. Re-enforce this awareness periodically through-out the year.
- Make sure escape routes remain free of any obstructions.
- A warning that batteries (battery pack or batteries installed) shall not be exposed to excessive heat such as sunshine, fire or the like.
WARNING! If THERE IS ANY QUESTION AS TO THE CAUSE OF AN ALARM IT SHOULD
BE ASSUMED THAT THE ALARM IS DUE TO AN ACTUAL FIRE AND THE DWELLING SHOULD BE
EVACUATED IMMEDIATELY.
THIS PRODUCT IS A SEALED UNIT AND CANNOT BE REPAIRED – IF THE UNIT IS TAMPERED
WITH IT WILL INVALIDATE THE WARRANTY. IF THE UNIT IS FAULTY PLEASE RETURN IT
TO YOUR ORIGINAL SUPPLIER WITH YOUR PROOF OF PURCHASE.
LIMITATIONS OF THE HEAT ALARM
- Heat alarms are not designed to protect life safety against fire and smoke. In most fires, hazardous levels of toxics gases and smoke can build up before the Heat Alarm will operate. In cases where life safety is an issue, Heat Alarms should only be used to provide an added source of protection.
- Heat alarms cannot provide an alarm if heat does not reach the alarm. Therefore, Heat Alarms may not sense fires starting in chimneys, walls, on roofs, on the other side of a closed door or on a different floor. It should be installed in each sleeping area, on every level of a home and be interconnected with each other and the heat alarms.
- Home fires develop in different ways and are often unpredictable. No one type of alarm is always best, and a given alarm may not always provide warning of a fire.
HEAT ALARM LIMITED WARRANTY
These alarms are warranty to be free from defects in materials and
workmanships under normal use and service for a period of 5 years (exclude
battery) from date of purchase. The company will not be obligated to repair or
replace parts which are found to be in need of repair because of misuse,
damage or alterations occur after the date of purchase. Send the alarm with
proof of purchase, postage and return postage prepaid, to local distributor.
The liability of the company arising from the sale of this alarm shall not in
any case exceed the cost of replacement of alarm and in no case shall the
company be liable for consequential loss or damages resulting from the failure
of the alarm.
HISPEC ELECTRICAL PRODUCTS LTD. SHALL HAVE NO LIABILITY FOR ANY PERSONAL
INJURY OR PROPERTY DAMAGE, OR ANY SPECIAL INCIDENTAL, CONTINGENT OR
CONSEQUENTIAL DAMAGE OF ANY KIND RESULTING FROM A FIRE. THE EXCLUSIVE REMEDY
FOR BREACH OF THE LIMITED WARRANTY CONTAINED HEREIN IS THE REPAIR OR
REPLACEMENT OF THE DETECTIVE PRODUCT AT HISPEC ELECTRICAL PRODUCTS LTD.
OPTION. IN NO CASE SHALL HISPEC ELECTRICAL PRODUCTS LTD.’S LIABILITY UNDER ANY
OTHER REMEDY PRESCRIBED BY LAW EXCEED THE PURCHASE PRICE. YOUR HEAT ALARMS IS
NOT A SUBSTITUTE FOR PROPERTY, DISABILITY, LIFE OR OTHER INSURANCE OF ANY
KIND. APPROPRIATE COVERAGE IS YOUR RESPONSIBILITY. CONSULT YOUR INSURANCE
AGENT.
This does not affect your statutory rights. This alarm is only suitable for
residential dwellings and is not suitable for commercial or industrial use.
Waste electrical products should not be disposed of with normal household
waste. Please recycle where facilities exist. Check with your Local Authority
or retailer for recycling advice. New regulation will encourage the recycling
of Waste from Electrical and Electronic Equipment (European “WEEE Directive”
effective August 2005).
HISPEC ELECTRICAL PRODUCTS LTD UNIT 21 CHORLEY NORTH BUSINESS PARK,
CHORLEY, LANCASHIRE PR6 7BX
WWW.HISPEC.CO.UK
VERSION 090322