wilo Helix V Documentation User Manual
- June 9, 2024
- wilo
Table of Contents
- Helix V Documentation
- General
- Safety
- Transport and interim storage
- Application
- Technical data
- Description and function
- Installation and electrical connection
- Commissioning
- Maintenance
- Faults, causes and remedies
- Spare parts
- Disposal
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Pioneering for You
Wilo-Helix V, FIRST V, 2.0-VE 2-4-6-10-16
Installation and operating instructions
Helix V Documentation
Fig. 1
| Fig. 2
---|---
Fig. 3|
Fig. 4
Type | (mm) |
---|---|
A | |
Helix V(F), 2.0-VE 2… | PN16 |
4xØ13
Helix V(F), 2.0-VE 4…| PN16| 100| 212| 180| 162| 160| 50| D32| 75| 2xMlO|
4xØ13
Helix V(F), 2.0-VE 6…| PN16| 100| 212| 180| 162| 160| 50| D32| 75| 2xMl0|
4xØ13
Helix V(F), 2.0-VE 10…| PN16| 130| 251| 215| 181| 200| 80| D50| 100| 2xM12|
4xØ13
Helix V(F) 2.0-VE 16…| PN16| 130| 251| 215| 181| 200| 90| D50| 100| 2xM12|
4xØ13
Type| (mm)
---|---
A| B| C| D| E| F| G| H| J| K
Helix V(F), 2.0-VE 2…| PN25/PN30| 100| 212| 180| 172| 250| 75| D25| 85| 4xM12|
4xØ13
Helix V(F), 2.0-VE 4…| PN25/PN30| 100| 212| 180| 172| 250| 75| D25| 85| 4xM12|
4xØ13
Helix V(F), 2.0-VE 6…| PN25/PN30| 100| 212| 180| 172| 250| 75| D32| 100|
4xM16| 4xØ13
Helix V(F), 2.0-VE 10…| PN25/PN30| 130| 252| 215| 187| 280| 80| D40| 110|
4xM16| 4xØ13
Helix V(F), 2.0-VE 16…| PN25/PN30| 130| 252| 215| 187| 300| 90| D50| 125|
4xM16| 4xØ13
Fig. 5
| Fig. 6
---|---
Fig. 7
General
1.1 About this document
The language of the original operating instructions is English. All other
languages of these instructions are translations of the original operating
instructions.
These installation and operating instructions are an integral part of the
product. They must be kept readily available at the place where the product is
installed. Strict adherence to these instructions is a precondition for the
proper use and correct operation of the product.
These installation and operating instructions correspond to the relevant
version of the product and the underlying safety standards valid at the time
of going to print.
Safety
These operating instructions contain basic information which must be adhered
to during installation, operation and maintenance. For this reason, these
operating instructions must, without fail, be read by the service technician
and the responsible specialist/operator before installation and commissioning.
It is not only the general safety instructions listed under the main point
“safety” that must be adhered to but also the special safety instructions with
danger symbols included under the following main points.
- Injuries due to electrical, mechanical and bacteriological factors and electromagnetic fields.
- Damage to the environment due to leakage of hazardous materials.
- Damage to the installation.
- Failure of important product functions.
2.1 Symbols and signal words in the operating instructions
Symbols:
WARNING
General safety symbol
WARNING
Electrical risks
NOTICE
Notes
Signal words
DANGER
Imminent danger.
May result in death or severe injuries if the hazard is not prevented.
WARNING
Non-observance may result in (very) severe injury.
CAUTION
The product risks becoming damaged. “Caution” is used when there is a risk to
the product if the user does not observe procedures.
NOTICE
Note containing useful information for the user about the product. It assists
the user in the case of an issue;
2.2 Personnel qualification
The installation, operating and maintenance personnel must have the
appropriate qualifications for this work. Area of responsibility, terms of
reference and monitoring of the personnel are to be ensured by the operator.
If the personnel are not in possession of the necessary knowledge, they are to
be trained and instructed. This can be accomplished if necessary by the
manufacturer of the product at the request of the operator.
2.3 Danger in the event of non-observance of the safety instructions
Non-observance of the safety instructions can result in risk of injury to
persons and damage to the environment and the product/unit. Nonobservance of
the safety instructions results in the loss for any claims to damages. In
particular, non-observance can, for example, result in the following risks:
- Danger to persons due to electrical, mechanical and bacteriological factors
- Damage to the environment due to leakage of hazardous materials
- Property damage
- Failure of important product/unit functions
- Failure of required maintenance and repair procedures
2.4 Safety consciousness on the job
The safety instructions included in these installation and operating
instructions, the existing national regulations for accident prevention
together with any internal working, operating and safety regulations of the
operator are to be complied with.
2.5 Safety instructions for the user
This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience and
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should
be supervised to ensure that they do not play with the appliance.
- If hot or cold components on the product/unit lead to hazards, local measures must be taken to guard them against touching.
- Guards which protect personnel from coming into contact with moving components (e.g. the coupling) must not be removed while the product is in operation.
- Leakages (e.g. from the shaft seals) of hazardous fluids (which are explosive, toxic or hot) must be led away so that no danger to persons or to the environment arises. National statutory provisions are to be complied with.
- Highly flammable materials are always to be kept at a safe distance from the product.
- Danger from electrical current must be eliminated. Local directives or general directives [e.g. IEC, VDE etc.] and local power supply companies must be adhered to.
2.6 Safety instructions for installation and maintenance work
The operator must ensure that all installation and maintenance work is
carried out by authorised and qualified personnel, who are sufficiently
informed from their own detailed study of the operating instructions
Work on the product/unit must only be carried out when at a standstill. It is
mandatory that the procedure described in the installation and operating
instructions for shutting
down the product/unit be complied with.
Immediately on conclusion of the work, all safety and protective devices must
be put back in position and/or recommissioned.
2.7 Unauthorised modification and manufacture of spare parts
Unauthorised modification and manufacture of spare parts will impair the
safety of the product/ personnel and will make void the manufacturer’s
declarations regarding safety.
Modifications to the product are only permissible after consultation with the
manufacturer. Original spare parts and accessories authorised by the
manufacturer ensure safety. The use of other parts will absolve us of
liability for consequential events.
2.8 Improper use
The operating safety of the supplied product is only guaranteed for
conventional use in accordance with Section 4 of the operating instructions.
The limit values must on no account fall under or exceed those values
specified in the catalogue/data sheet.
Transport and interim storage
When receiving the material, check that there has been no damage during the
transport. If shipping damage has occurred, take all necessary steps with the
carrier within the allowed time.
CAUTION
Outside influences may cause damages. If the delivered material is to be
installed later on, store it in a dry place and protect it from impacts and
any outside influences (humidity, frost etc.).
The product should be cleaned thoroughly before it is put into temporary
storage.
The product can be stored for at least one year.
Handle the pump carefully so as not to damage the unit prior to installation.
Application
This pump’s basic function is to pump hot or cold water, water with glycol or
other low viscosity fluids that contain no mineral oil, solid or abrasive
substances, or materials having long fibres. The manufacturer’s approval is
required for use to pump corrosive chemicals.
WARNING
Risk of explosion
Do not use this pump to handle flammable or explosive liquids.
4.1 Applications areas
- water distribution and pressure boosting
- industrial circulation systems
- process fluids
- cooling-water circuits
- firefighting and washing stations
- irrigation systems, etc.
Technical data
5.1 Type key
Example: Helix V1605 or Helix2.0-VE1602-1/16/E/KS/400-50xxxx
Helix V(F)
Helix FIRST V(F)
Helix2.0-VE| Vertical high-pressure multistage centrifugal pump in in-line
design
(F) = VdS certified pump version
With frequency converter
---|---
16| Nominal volume flow in m³/h
5| Number of impellers
1| Pump material code
1 = Pump housing stainless steel 1.4301 (AISI 304) + hydraulics 1.4307 (AISI
304)
2 = Pump housing stainless steel 1.4404 (AISI 316L) + hydraulics 1.4404 (AISI
316L)
5 = Pump housing cast Iron EN-GJL-250 (standard coating) + hydraulics 1.4307
(AISI 304)
16| Pipe connection
16 = oval flanges PN16
25 = round flanges PN25
30 = round flanges PN40
E| Seal type code
E = EPDM
V = FKM
KS| K = Cartridge seal, versions without “K” are equipped with simple
mechanical seal
S = Lantern orientation align with suction pipe
X = X-Care version
1| 1 = Single-phase motor – None or 3 = Triphase motor
(With motor) 400 – 460| Motor electrical voltage (V)
50 – 60 = Motor frequency (Hz)
(Without motor) Bare-shaft pump| -38FF265 = Ø motor shaft – lantern size
XXXX| Option code (if any)
5.2 Data table
Maximum operating pressure
Pump casing| 16, 25 or 30 bars depend on the model
Maximum suction pressure| 10 bars
Note : real inlet pressure (Pinlet)+ pressure at 0 flow delivered by the pump
must be below the maximum operating pressure of the pump. In case of exceeding
maximum operating pressure, the ball bearing and the mechanical seal could be
damaged or lifetime could decrease.
P Inlet + P at 0 flow ≤ Pmax pump
See pump rating plate to know the maximum operating pressure: Pmax
Temperature range
Liquid temperatures| to +120°C
-15°C to +90°C (wiht FKM seal)
-20°C to + 120°C (with cast iron casing)
Ambient tempereature| -15° to +40°C (other temperature on request)
Electrical data
Motor efficiency| Motor according to IEC 60034-30
Motor Protection index| IP55
Insulation class| 155 (F)
Frequency| See pump rating plate
Electrical voltage
Capacitor value (μF) in single-phase version
Other data
Humidity| < 90% without condensation
Altitude| < 1000 m (> 1000m on request)
Maximum suction head| According to pump’s NPSH
Sound pressure level dB(A) 0/+3 dB(A)
| Power (kW)
---|---
0.37| 0.55| 0.75| 1.1| 1.5| 2.2| 3| Ł| 5.5| 7.5| 11| 15| 18.5| 22| 30| 37| Ł5
50H z| 56| 57| 57| 58| 58| 62| 6Ł| 68| 69| 69| 71| 71| 7Ł| 7Ł| 76|
76| 76
60H z| 60| 61| 61| 63| 63| 67| 71| 72| 7Ł| 7Ł| 78| 78| 81| 81| 8Ł|
8Ł| 8Ł
5.3 Scope of delivery
Complete unit
- Multistage pump
- Installation and operating instructions
- Counter flanges with the corresponding screws, nuts and gaskets for PN16 configuration with oval flanges
- Installation and operating instructions for drive
5.4 Accessories
Original accessories are available for HELIX range:
Designation | Article n° | |
---|---|---|
2x oval counterflanges, stainless steel 1.4301 (screwing) | PN16 – 1” | 4016168 |
2x round counterflanges in stainless steel 1.4404 (screwing) | PN40 – DN25 |
4016165
2x round counterflanges in steel (welding)| PN40 – DN25| 4016162
2x oval counterflanges in stainless steel 1.4301 (screwing)| PN16 – 1” 1/4|
4016169
2x round counterflanges in stainless steel 1.4404 (screwing)| PN40 – DN32|
4016166
2x round counterflanges in steel (welding)| PN40 – DN32| 4016163
2x oval counterflanges in stainless steel 1.4301 (screwing)| PN16 – 1”|
4016170
2x round counterflanges in stainless steel 1.4404 (screwing)| PN40 – DN40|
4016167
2x round counterflanges in steel (welding)| PN40 – DN40| 4016164
2x oval counterflanges in stainless steel 1.4301 (screwing)| PN16 – 2”|
4055063
2x round counterflanges in stainless steel 1.4404 (screwing)| PN40 – DN50|
4038589
2x round counterflanges in steel (welding)| PN40 – DN50| 4038588
Bypass kit 25 bar| | 4146786
Bypass kit (with pressure gauge 25 bar)| | 4146788
Baseplate with dampers for pumps up to 5.5 kW| | 4157154
The use of new accessories is recommended.
Please contact your Wilo sales office for full accessories list.
Description and function
6.1 Product description
Fig. 1
- Motor connection bolt
- Coupling gard
- Mechanical seal
- Hydraulic stage casing
- Impeller
- Pump shaft
- Motor
- Coupling
- Lantern
- Liner
- Flange
- Pump housing
- Base plate
Fig. 2, 3
- Strainer
- Pump suction valve
- Pump discharge valve
- Check valve
- Drain + priming plug
- Air bleed screw + Filling plug
- Tank
- Foundation block
- Grease
- Lifting hook
6.2 Design of product
- The Helix pumps are vertical high pressure non self-priming pumps with in-line connection based on multistage design.
- The Helix pumps combine use of both high efficiency hydraulics and motors.
- All metallic parts in contact with water are made of stainless steel.
- For models equipped with heaviest motor (>40 kgs), a specific coupling allows to change the seal without removing the motor. A cartridge seal is then used in order to ease maintenance.
- Special handling devices are integrated in order to facilitate pump installation (Fig. 7).
Installation and electrical connection
Installation and electrical work in compliance with any local codes and by
qualified personnel only.
WARNING
Bodily injury!
Existing regulations for the prevention of accidents must be observed.
WARNING
Electrical shock hazard
Dangers caused by electrical energy must be excluded.
7.1 Commissioning
Unpack the pump and dispose of the packaging in an environmentally-
responsible manner.
7.2 Installation
The pump must be installed in a dry, well-ventilated and frost-free place.
CAUTION
Possible damage of the pump!
Dirt and solder drops in to the pump body can effect the pump operation.
- It is recommended that any welding and soldering work be done before installing the pump.
- Thoroughly flush the system out before installing the pump.
⇒ The pump must be installed in an easily accessible position to facilitate
inspection or replacement.
⇒ For heavy pumps, install a lifting hook (Fig. 2, item 10) above the pump in
order to ease its disassembly.
WARNING
Risk of accident by hot surfaces!
The pump must be positioned so that someone cannot come into contact with the
hot pump surfaces while operation.
- Install the pump in a dry place protected from frost, on a flat concrete block using appropriate accessories. If possible, use an insulating material under the concrete block (cork or reinforced rubber) to avoid any noise and vibration transmission into the installation.
WARNING
Risk of fall!
The pump must be correctly screwed to the ground.
- Place the pump where it will be easy to reach, to facilitate inspection and removal work. The pump must always be installed perfectly upright on a sufficiently heavy concrete base.
WARNING
Risk of parts inside the pump!
Take care to remove closure members of the pump housing before installation.
NOTICE
Each pumps could be tested regarding hydraulic features in factory, some water
may remain in them. It is recommended for hygienic purposes, to carry out a
rinsing of the pump before any using with potable water supply.
- The installation and connection dimensions are given Fig. 4.
- Lift the pump carefully by using the integrated hooks rings, if necessary with a hoist and suitable slings according to the current hoist guidelines.
WARNING
Risk of fall!
Take care to pump fixations especially for the highest pumps whose centre of
gravity may lead to risk during pump handling.
WARNING
Risk of fall!
Use integrated rings only if they are not damaged (no corrosion …). Replace
them if needed.
WARNING
Risk of fall!
The pump must be never carried by using motor hooks: these are only designed
to lift the motor alone.
7.3 Pipe connection
- Connect the pump to the pipes by using appropriate counterflanges, bolts, nuts and gaskets.
CAUTION
Tightening of screws or bolts must not exceed.
Configuration PN16 / PN25
M10 – 20 N.m – M12 – 30 N.m
Configuration PN40
M12 – 50 N.m – M16 – 80 N.m
Use of impact wrench is prohibited.
- The circulation sense of the fluid is indicated on the identification label of the pump.
- Pump must be installed in such a way that it is not stressed by the pipework. The pipes must be attached so that the pump does not bear their weight.
- It is recommended that isolation valves be installed on the suction and discharge side of the pump.
- Use of expansion joints may mitigate noise and vibration of the pump.
- As regards the nominal cross-section of the suction pipe, we recommend a crosssection at least as large as that of the pump connection.
- A check valve could be placed on the discharge pipe in order to protect the pump against hammer shock.
- For direct connection to a public drinking water system, the suction pipe must also have a check valve and a guard valve.
- For indirect connection via a tank, the suction pipe must have a strainer to keep any impurities out of the pump and a check valve.
7.4 Motor connection for bare-shaft pump (without motor)
- Remove coupling guards.
NOTICE
Coupling guards can be removed without entirely unscrewing screws.
- Install the motor on the pump by using screws (FT lantern size – see product designation) or bolts, nuts and handling devices (FF lantern size – see product designation) provided with the pump : check motor power and dimension in Wilo catalogue.
NOTICE
Depending on fluid characteristics, motor power could be modified. Contact The
Wilo Customer Services if necessary.
- Close the coupling guards by screwing all screws provided with the pump.
7.5 Electrical connection
WARNING
Electrical shock hazard!
Dangers caused by electrical energy must be excluded.
⇒ Electrical work by a qualified electrician only!
⇒ All electrical connections must be performed after the electrical supply has
been switched off and secured against unauthorized switching.
⇒ For safe installation and operation a proper grounding of the pump to the
power supply’s grounding terminals is required.
-
Check that operating current, voltage and frequency used comply with motor plating data.
-
The pump must be connected to the power supply by a solid cable equipped with a grounded plug-connection or a main power switch.
-
Three-phase motors must be connected to an approved motor starter. The set nominal current must correspond to the electrical data on the pump motor name plate.
-
Single-phase motors have integrated thermal protection, which ensures that the pump shuts down if the allowable winding temperature is exceeded and restarts automatically once it is cooled.
-
The supply cable must be laid so that it never touches the pipework and/or the pump and motor casing.
-
The pump/installation should be grounded in compliance with local regulations. A ground fault interrupter can be used as extra protection.
-
The mains connection must be in accordance with the connection plan (Fig. 5 for three-phase motor), (for single-phase motor see connection plan in the motor terminal
box). -
Three-phase motors should be protected by a circuit-breaker for the IE class of the motors. Current setting should be adapted to the pump usage, without exceeding the value Imax written on the motor nameplate.
7.6 Operation with frequency converter
- Motors used can be connected to a frequency converter in order to adapt pump performance to duty point.
- The converter must not generate voltage peaks at motor terminals higher than 850V and dU/dt slope higher than 2500 V/μs.
- In case of higher value, an appropriate filter must be used: contact converter manufacturer for this filter definition and selection.
- Strictly follow instructions provided by the converter manufacturer data sheet for installation.
- Minimum variable speed should not be set below 40% of pump nominal speed.
Commissioning
Unpack the pump and dispose of the packaging in an environmentally-responsible
manner.
8.1 System filling – Venting
**CAUTION
Possible damage of the pump!
Never operate the pump dry.
The system must be filled before starting the pump.
Air evacuation process – Pump with sufficient supply pressure (Fig. 3)**
- Close the two guard valves (2, 3).
- Unscrew the venting screw from filling plug (6a).
- Slowly open the guard valve on the suction side (2).
- Retighten the venting screw when air escapes at the venting screw and the pumped liquid flows (6a).
WARNING
Risk of scalding!
When the pumped liquid is hot and the pressure high, the stream escaping at
the venting screw may cause burns or other injuries.
- Open the guard valve on the suction side completely (2).
- Start the pump and check if direction of rotation matches the one printed on pump plating. If this is not the case, interchange two phases in the terminal box.
CAUTION
Possible damage of the pump
A wrong direction of rotation will cause bad pump performances and possibly
coupling damage.
- Open the guard valve on the discharge side (3).
Air evacuation process – Pump in suction (Fig. 2)
-
Close the guard valve on the discharge side (3).
Open the guard valve on the suction side (2). -
Remove the filling plug (6b).
-
Open the drain-priming plug not completely (5b).
-
Fill the pump and the suction pipe with water.
-
Make sure that there is no air in the pump and in the suction pipe : refilling until complete removal of air is required.
-
Close the filling plug with air bleed screw (6b).
-
Start the pump and check if direction of rotation matches the one printed on pump plating. If this is not the case, interchange two phases in the terminal box.
CAUTION
Possible damage of the pump
A wrong direction of rotation will cause bad pump performances and possibly
coupling damage.
- Open the guard valve on the discharge side a little (3).
- Unscrew the air bleed screw from filling plug for air venting (6a).
- Retighten the air-bleed screw when air escapes at the air bleed screw and the pumped liquid flows.
WARNING
Risk of scalding
When the pumped liquid is hot and the pressure high, the stream escaping at
the air bleed screw may cause burns or other injuries.
- Open the guard valve on the discharge side completely (3).
- Close the drain-priming plug (5a).
8.2 Starting up
CAUTION
Possible damage of the pump
The pump must not operate at zero flow (closed discharge valve).
WARNING
Risk of injury!
When the pump runs, coupling guards must be in place, tightened with all
appropriate screws.
WARNING
important noise
Noise emitted by most powerful pumps could be very high : protection must be
used in case of long stay close to the pump.
**CAUTION
Possible damage of the pump**
Installation must be designed in order that no one could be hurt in case of
fluid leakage (mechanical seal failure…).
Maintenance
All servicing should be performed by an authorized service
representative!
DANGER
Electrical shock hazard!
Dangers caused by electrical energy must be excluded.
All electrical work must be performed after the electrical supply has been
switched off and secured against unauthorized switching.
WARNING
Risk of scalding!
At high water temperatures and system pressure close isolating valves before
and after the pump. First, allow pump to cool down.
- These pumps are maintenance free. Nevertheless a regular check is recommended every 15 000 hours.
- In option, mechanical seal could be easily replace on some models thanks to its cartridge seal design. Insert its adjusting wedge in its housing (Fig. 6) once mechanical seal position is set.
- Always keep the pump perfectly clean.
- Pumps which are not being used during periods of frost should be drained to avoid damage: Close the guard valves, open completely the drain-priming plug and the air bleed screw.
- Service life: 10 years depending on the operating conditions and whether all requirements described in the operation manual have been met.
Faults, causes and remedies
DANGER
Electrical shock hazard!
Dangers caused by electrical energy must be excluded.
All electrical work must be performed after the electrical supply has been
switched off and secured against unauthorized switching.
WARNING
Risk of scalding!
At high water temperatures and system pressure close isolating valves before
and after the pump. First, allow pump to cool down.
Faults | Cause | Remedies |
---|---|---|
Pump does not run | No current | Check the fuses, the wiring, and the connectors |
The thermistor tripping device has tripped out, cutting off power | Eliminate |
any cause of overloading of the motor
Pump runs but delivers too little| Wrong direction of rotation| Check the
direction of rotation of the motor and correct it if necessary
| Parts of the pump are ob- structed by foreign bodies| Check and clean the
pipe
| Air in suction pipe| Make the suction pipe airtight
| Suction pipe too narrow| Install a larger suction pipe
| The valve is not open far enough| Open the valve properly
Pump delivers unevenly| Air in pump| Evacuate the air in the pump; check that
the suction pipe is airtight. If required, start the pump 20-30s — open the
air bleed screw in order to move air away — close the air bleed screw and
repeat it several times until no more air is going out of the pump
Pump vibrates or is noisy| Foreign bodies in pump| Remove the foreign bodies
| Pump not properly attached to ground| Retighten the screws
| Bearing damaged| Call the Wilo Customer Service
Motor overheats, its protec- tion trips out| A phase is open-circuit| Check
the fuses, the wiring, and the connectors
| Ambient temperature too high| Provide cooling
Mechanical seal is leaking| Mechanical seal is damaged| Replace the mechanical
seal
If the fault cannot be solved, please contact the Wilo customer services.
Spare parts
All spare parts should be ordered directly from the Wilo customer service. To prevent errors, always quote the data on the pump’s rating plate when making an order. The spare parts catalogue is available at www.wilo.com
Disposal
Information on the collection of used electrical and electronic products.
Proper disposal and appropriate recycling of this product prevents damage to
the environment and dangers to your personal health.
NOTICE
Disposal as domestic waste is forbidden!
In the European Union, this symbol can appear on the product, the packaging or
the accompanying documentation. It means that the electrical and electronic
products in question must not be disposed of along with domestic waste.
To ensure proper handling, recycling and disposal of the used products in
question, please note the following points:
- Only hand over these products at designated, certified collecting points.
- Observe the locally applicable regulations! Please consult your local municipality, the nearest waste disposal site, or the dealer who sold the product to you for information on proper disposal. For further information on recycling, go to www.wilo-recycling.com.
Subject to change without prior notice.
Pioneering for You
Local contact at www.wilo.com/contact
WILO SE
Wilopark 1
44263 Dortmund
Germany
T +49 (0)231 4102-0
F +49 (0)231 4102-7363
wilo@wilo.com
www.wilo.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>