HALCYON R945 LED Recessed Luminaire Instruction Manual

June 10, 2024
HALCYON

LED Recessed Luminaire
Instruction Manual

R945 Installation

RISK OF FIRE — Required clearance from structural members and building elements

Side Clearance to building element (eg timber, joist or Batten) (SCB): Omm
Height Clearance to building element (eg timber, joist or Batten) (HCB): Omm
Minimum Insulation Clearance to building element (MIC): Omm

Approved clearances
Note:
Omm required but 25mm always recommended for optimum product lifespan through effective heat dissipation.
DO NOT INSTALL THROUGH JOIST, BEAM, RAFTER OR CEILING BATTEN
Note: Side/Height Clearance is measured from heat sink.

Recessed Luminaire Classification:

IC-F — building insulation that can safely be continuously exposed to 90°C allowed to abut and cover the luminaire.

For indoor use.
Luminaire must be installed by a Registered Electrician.

CONSTANT CURRENT WIRE IN SERIES.
CHECK MINIMUM LOAD OF DRIVER.

  1. Switch off mains power supply

  2. Cut out 035mm
    Cutting of holes prior to receiving goods is entirely at the risk of the installer.

  3. Connect driver to mains voltage cable (L, N). Do not connect light to driver if driver is live. Inrush current from live driver will cause instant light failure. Do not switch secondary side.
    Halcyon UID driver can be utilized and are able to be installed under insulation, if using a standard driver install above insulation.
    NOTE: if using one driver per R948 we do have a range of mini drivers available that are designed to fit through the cut out. Their codes begin with
    DRMACC or DRDMACC, please refer to our website for options.

  4. Carefully install light into pre-cut 035mm hole.

    1. Turn on mains power and switch on lighting circuit.

CLASSIFICATION SHEET / IC-F

Manufacturer / Supplier Halcyon Lighting Ltd
Product Code R945
Product Type LED Recessed Luminaire
Secondary Voltage 350mA Constant Current
Wattage 1.05W
Ingress Protection Rating IP40

Classification

IC-F — building insulation that can safely be continuously exposed to 90°C allowed to abut and cover the luminaire.

In the vicinity of the recessed luminaire, use an insulation product that:

(a) Maintains its dimensions and structural integrity when exposed to a temperature of 90°C; and
(b) Withstands a 30-second needle flame test carried out in accordance with AS/NZS 60695.11.5 with the flame applied to all surfaces of the sample.

Rear of fitting may abut structural members and building elements.
Do not install through or directly into joist, beam, rafter or ceiling batten.

Side Clearance from heatsink to building element (e.g. timber, joist or batten)| SCB: 0mm
---|---
Height Clearance from heatsink to building element (e.g. timber, joist or batten)| HCB: 0mm
Minimum insulation clearance to building element| MIC: 0mm

Recessed luminaires and their associated equipment may pose a risk of fire or damage to property if not installed and maintained correctly. Halcyon recommends a clearance of 25mm to building elements for optimum lifespan.

Halcyon IC rated luminaires are completely safe to install in sarked timber ceiling linings.
Halcyon accepts no responsibility if the timber used is not treated correctly and dries out, crack or warps over time due to the constant low heat from the aforementioned “IC Rated” LED recessed lighting.

This data sheet contains information necessary to ensure compliance with the New Zealand
Electrical Code of Practice for Installation and Maintenance of Recessed Luminaires and
Associated Equipment AS/NZS 60598.2.2:2001

10 Basalt Place, East Tamaki, Auckland,
PO Box 58-501, Botany, Manukau 2163, Auckland, New Zealand
Ph (0064 9) 273-9177 Fax (0064 9) 273 9155
Email: sales@halcyon.co.nz Web: www.halcyonlights.co.nz