GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by
the end user for future reference and maintenance.
These instructions should be used to aid installation of the following
product:
TPR14LEDEM
SAFETY
- This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
- Please isolate mains prior to installation or maintenance
- Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
- Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
- This product is Class II double insulated
- This product is IP65 rated
INSTALLATION
Note – If this product is being used in conjunction with an external PIR or sensor, please confirm with the manufacturer of the sensors that they are compatible with LED luminaires.
- Provide power to the required point of installation (refer to BS7671 for correct cabling methods). Suitable IP rated junction boxes should be used where required
- Remove the diffuser by unfastening the three screws on the front
- Open the hinged LED plate by releasing the tab labelled “OPEN” (see Fig. 1)
Fig. 1
- Drill the fixing holes in the rear of the fitting. Mark the location of the fixing holes and drill ensuring not to infringe with any gas/water pipes or electrical cables
- Feed the mains cable through the rubber grommet to retain IP rating, or alternatively, drill out one of the two 20mm drilling guides on the sides of the fitting (see Fig. 2)
Fig. 2
- Secure the baseplate to the surface using the fixings provided
- Connect the luminaire to the mains supply ensuring the correct polarity is observed: L – Live, K – Switched Live (brown), N – Neutral (blue) (see Fig. 3)
Fig. 3
- Connect the battery to the socket on the emergency inverter
- Close the hinged gear tray until the tab clicks into position
- Reattach the diffuser and secure with the three screws, ensuring the seal is in place and not damaged
- Switch on and check for correct operation ensuring the green indicator LED is illuminated
- We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test
- If the batteries have been left in a discharged state for an extended period, we Recommend one or more charge and discharge cycles are completed which should help to restore the battery capacity
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
- Daily check – check LED charge indicator is illuminated
- Monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- Annual 3-hour duration test – simulate a mains supply failure for 3-hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
- If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record sheet
WARNING
This product must be disconnected from the circuit if subjected to any high
voltage or insulation resistance testing. Irreparable damage will occur if
this instruction is not followed.
GENERAL
This product contains a light source of energy efficiency class E to Regulation (EU) No. 2019/2015. and (UK) 2021 No. 1095.
This product contains an LED light source which can be replaced by the end
user and a control gear which can be replaced by a professional.
Clean with a soft dry cloth only, do not use aggressive
cleaning products or solvents which may damage the product.
Do not use any source of high-pressure washers to maintain or clean this
luminaire.
This product is non-dimmable.
This product should be dismantled for disposal when it reaches the end of its
life. Please see website for dismantling instructions.
This product should be recycled in the correct manner when it reaches the end
of its life. Check local authorities for where facilities exist.
The batteries in this luminaire are Nickel Cadmium and must be disposed of
correctly. Please contact the local authorities for the disposal of this toxic
waste.
TEST RECORD SHEET
WARRANTY
This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.
ML Accessories Limited LU5 4LT www.mlaccessories.co.uk
DCOCT21_V2
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>