Danfoss CO2 Module Controller Universal Gateway User Guide
- June 9, 2024
- Danfoss
Table of Contents
CO2 Module Controller Universal Gateway
User Guide
Electric Installation
Below is an illustration of the external connections that can be made in the remote control assembly.
Power supply to CDU
230V AC 1,2m cable for this is included.
Connect Module controller power supply cable to L1 (left terminal) and N
(right terminal) of the condensing unit control panel – power
supply terminal block
Caution: If the cable needs to be replaced, it must either be short-
circuit proof or it must be protected by a fuse on the other end.
RS485-1
Modbus interface for connection to the System Manager
RS485-2
Modbus interface for connection to the CDU.
1,8 m cable for this is included.
Connect this RS485-2 Modbus cable to terminal A and B of the condensing unit
control panel – Modbus interface terminal block. Do not connect insulated
shield to ground
RS485-3
Modbus interface for connection to the evaporator controllers
3x LED Function explanation
- Blue led is ON when the CDU is connected and polled operation is complete
- Red led is flashing when there is a communication fault with an evaporator controller
- Green led is flashing during communication with an evaporator controller The green LED next to the 12V power supply terminals indicates “Power OK”.
Electric noise
Cables for data communication must be kept separate from other electric
cables:
– Use separate cable trays
– Keep a distance between cables of at least 10 cm.
Mechanical Installation
- Installation in the backside of the unit / backside of e-panel with provided rivets or screws (3 mounting holes provided)
Procedure:
-
Remove CDU panel
-
Mount the bracket with provided screws or rivets
-
Fix the e-Box to the bracket (4 screws provided)
-
Route and connect the provided Modbus and power supply cables to the CDU control panel
-
Route and connect the evaporator controller Modbus cable to the Module controller
-
Option: Route and connect the System Manager Modbus cable to the Module controller
Optional installation on the frontside (only for 10HP unit, just beside the
CDU control panel, holes to be drilled)
Procedure:
-
Remove CDU panel
-
Mount the bracket with provided screws or rivets
-
Fix the e-Box to the bracket (4 screws provided)
-
Route and connect the provided Modbus and power supply cables to the CDU control panel
-
Route and connect the evaporator controller Modbus cable to the Module controller
-
Option: Route and connect the System Manager Modbus cable to the Module controller
Module Controller wiring
Please wire the communication cable from the top of the control bord to the left side. The cable comes along with the module controller.
Please pass the power cable through the insulation at the bottom of the control box.
Note:
The cables should be fixed with the cable ties and should not touch the
baseplate to avoid water ingress.
Technical data
Supply voltage | 110-240 V AC. 5 VA, 50 / 60 Hz |
---|---|
Display | LED |
Electrical connection | Power supply: Max.2.5 mm2 Communication: Max 1.5 mm2 |
-25 — 55 °C, During operations -40 — 70 °C, During transport
20 – 80% RH, not condensed
No shock influence
Protection| IP65
Mounting| Wall or with included bracket
Weight| TBD
Included in the package| 1 x Remote control assembly
1 x Mounting bracket
4 x M4 screws
5 x Inox rivets
5 x Sheet metal screws
Approvals| EC Low Voltage Directive (2014/35/EU) – EN 60335-1
EMC (2014/30/EU)
– EN 61000-6-2 and 6-3
Dimensions
Units in mm
Spare parts
| | Danfoss Requirements| | |
---|---|---|---|---|---
Parts Name| Parts No| Gross
weight| Unit Dimension (mm)| Packing Style| Remarks
| | Kg| Length| Width| Height| |
CO2 MODULE CONTROLLER UNIVERSAL GATEWAY
MODULE CONTROLLER | 118U5498 | TBD | 182 | 90 | 180 | Carton box |
---|
Operation
Display
The values will be shown with three digits.
| Active alarm (red triangle)
---|---
Scan for Evap. controller is in progress (yellow clock)
When you want to change a setting, the upper and the lower button will give you a higher or lower value depending on the button you are pushing. But before you change the value, you must have access to the menu. You obtain this by pushing the upper button for a couple of seconds – you will then enter the column with parameter codes. Find the parameter code you want to change and push the middle buttons until value for the parameter is shown. When you have changed the value, save the new value by once more pushing the middle button. (If not operated for 10 seconds, the display will change back to showing the suction pressure in temperature).
Examples:
Set menu
- Push the upper button until parameter code r01 is shown
- Push the upper or the lower button and find that parameter you want to change
- Push the middle button until the parameter value is shown
- Push the upper or the lower button and select the new value
- Push the middle button again to freeze the value.
See alarm code
A short press of the upper button
If there are several alarm codes they are found in a rolling stack.
Push the uppermost or lowermost button to scan the rolling stack.
Set point
- Push upper button until display shows parameter menu code r01
- Select and change par. r28 to 1, which defines the MMILDS UI as the reference set device
- Select and change par. r01 to the required lower pressure setpoint target in bar(g)
- Select and change par. r02 to the required upper pressure setpoint target in bar(g)
Remark: The arithmetic middle of r01 and r02 is the target suction
pressure.
Get a good start
With the following procedure you can start regulation as soon as possible.
- Connect the modbus communication to CDU.
- Connect the modbus communication to evaporator controllers.
- Configure the address in each evaporator controller.
- Perform a network scan in the module controller (n01).
- Verify that all evap. controllers have been found (Io01-Io08).
- Open parameter r12 and start the regulation.
- For connection to a Danfoss System Manager
– Connect the modbus communication
– Set the address with parameter o03
– Perform a scan in the System Manager.
Survey of functions
Function | Parameter | Remarks |
---|---|---|
Normal display | ||
The display shows the suction pressure in temperature. | ||
Regulation |
Min. Pressure
The lower setpoint for suction pressure. See instructions for CDU.| r01|
Max. Pressure
The upper set point for suction pressure. See instructions for CDU.| r02|
Demand Operation
Limits the compressor speed of the CDU. See instructions for CDU.| r03|
Silent Mode
Enable/disable silent mode.
Operating noise is suppressed by limiting the speed of the outdoor fan and
compressor.| r04|
Snow Protection
Enable/disable snow protection functionality.
To prevent snow from building up on the outdoor fan during winter shutdown,
the outdoor fan is operated at regular intervals to blow off the snow.| r05|
Main Switch Start/stop the CDU| r12|
Reference source
The CDU can either use a reference that is configured with rotary switches in
the CDU, or it can use the reference as defined by parameter r01 and r02. This
parameter configures which reference to use.| r28|
For Danfoss Only| |
SH Guard ALC
Cut-out limit for ALC control (oil recovery)| r20|
SH Start ALC
Cut-in limit for ALC control (oil recovery)| r21|
011 ALC setpol M LBP (AK-CCSS parameter P87,P86)| r22|
SH Close
(AK-CC55 parameter —)| r23|
SH Setpolnt
(AK-CCSS parameter n10, n09)| r24|
EEV force low OD after oil recovery (AK-CCSS AFidentForce =1.0)| r25|
011 ALC setpol M MBP (AK-CCSS parameter P87,P86)| r26|
011 ALC setpoint HBP (AK-CC55 parameter P87,P86)| r27|
Miscellaneous| |
If the controller is built into a network with data communication, it must
have an address, and the system unit of the data communication must then know
this address.| |
The address is set between 0 and 240, depending on the system unit and the
selected data communication.| 3|
Evaporator controller addressing| |
Node 1 Address
Address of the first evaporator controller
Will only be shown if a controller has been found during scan.| lo01|
Node 2 Address See parameter lo01| 1002|
Node 3 Address See parameter lo01| lo03|
Node 4 Address See parameter lo01| 1004|
Node 5 Address See parameter 1001| 1005|
Node 6 Address See parameter lo01| 1006|
Node 7 Address See parameter 1001| 1007|
Node 8 Address
See parameter lo01
Ion| |
Node 9 Address See parameter 1001| 1009|
Function| Parameter| Remarks
---|---|---
Node 10 Address See parameter lo01| 1010|
Node 11 Address See parameter lo01| lol 1|
Node 12 Address See parameter 1001| 1012|
Node 13 Address See parameter 1001| 1013|
Node 14 Address See parameter lo01| 1014|
Node 15 Address See parameter 1001| lo15|
Node 16 Address See parameter 1001| 1016|
Scan Network
Initiates a scan for evaporator controllers| nO1|
Clear Network List
Clears the list of evaporator controllers, may be used when one or several
controllers are removed, proceed with a new network scan (n01) after this.|
n02|
Service| |
Read discharge pressure| u01| Pc
Read gascooler outlet temp.| U05| Sgc
Read receiver pressure| U08| Prec
Read receiver pressure in temperature| U09| Trec
Read discharge pressure in temperature| U22| Tc
Read suction pressure| U23| Po
Read suction pressure in temperature| U24| To
Read discharge temperature| U26| Sd
Read suction temperature| U27| Ss
Read controller software version| u99|
Operating status| | (Measurement)
---|---|---
Push briefly (Is) the upper button. A status code will be shown on the
display. The individual status codes have the following meanings:| | Ctrl.
state
CDU not operational| SO| 0
CDU operational| Si| 1
| |
Other displays| |
Oil recovery| Oil|
No communication with CDU| —|
Fault message
In an error situation an alarm symbol will flash..
If you push the top button in this situation you can see the alarm report in
the display.
Here are the messages that may appear:
Code/Alarm text via data communkation | Description | Action |
---|---|---|
E01 / COD offline | Communication lost with CV | Check CDU connection and |
configuration (SW1-2)
E02 / CDU communication error| Bad response from CDU| Check CDU configuration
(SW3-4)
Al7 /CDU alarm| An alarm has occurred in the CDU| See instructions for CDU
A01 / Evap. controller 1 offline| Communication lost with evap. controller 1|
Check Evap. controller controller and connection
A02 / Evap. controller 2 offline| Communication lost with evap. controller 2|
See A01
A03 / Evap. controller 3 offline| Communication lost with evap. controller 3|
See A01
A04 / Evap. controller 4 offline| Communication lost with evap. controller 4|
See A01
A05 / Evap. controller 5 offline| Communication lost with evap. controller 5|
See A01
A06/ Evap. controller 6 offline| Communication lost with evap. controller 6|
See A01
A07 / Evap. controller 7 offline| Communication lost with evap. controller 7|
See A01
A08/ Evap. controller 8 offline| Communication lost with evap. controller 8|
See A01
A09/ Evap. controller 9 offline| Communication lost with evap. controller 9|
See A01
A10 / Evap. controller 10 offline| Communication lost with evap. controller
10| See A01
All / Evap. controller 11 offline| Communication lost with evap. controller
11| See A01
Al2 / Evap. controller 12 offline| Communication lost with evap. controller
12| See A01
A13 /Evap. controller 13 offline| Communication lost with evap. controller 13|
See A01
A14 /Evap. controller 14 offline| Communication lost with evap. controller 14|
See A01
A15 /Evapt controller 15 offline| Communication lost with evap. controller 15|
See A01
A16 / Evapt controller 16 offline| Communication lost with evap. controller
16| See A01
Menu survey
Function | Code | Min | Max | Factory | User-Setting |
---|---|---|---|---|---|
Regulation | |||||
Min. Pressure | r01 | 0 bar | 126 bar | CDU | |
Max. Pressure | r02 | 0 bar | 126 bar | CDU | |
Demand Operation | r03 | 0 | 3 | 0 | |
Silent Mode | r04 | 0 | 4 | 0 | |
Snow Protection | r05 | 0 (OFF) | 1 (ON) | 0 (OFF) | |
Main Switch Start/stop the CDU | r12 | 0 (OFF) | 1 (ON) | 0 (OFF) | |
Reference source | r28 | 0 | 1 | 1 | |
For Da nfoss Only | |||||
SH Guard ALC | r20 | 1.0K | 10.0K | 2.0K | |
SH Start ALC | r21 | 2.0K | 15.0K | 4.0 K | |
011 ALC setpoint LBP | r22 | -6.0K | 6.0 K | -2.0 K | |
SH Close | r23 | 0.0K | 5.0 K | 25 K | |
SH Setpoint | r24 | 4.0K | 14.0K | 6.0 K | |
EEV force low OD after oil recovery | r25 | 0 min | 60 min | 20 min | |
Oil ALC setpoint MBP | r26 | -6.0K | 6.0 K | 0.0 K | |
011 ALC setpoint HBP | r27 | -6.0K | 6.0K | 3.0K | |
Miscellaneous | |||||
CDU Address | o03 | 0 | 240 | 0 | |
Evap. controller Addressing | |||||
Node 1 Address | lo01 | 0 | 240 | 0 | |
Node 2 Address | lo02 | 0 | 240 | 0 | |
Node 3 Address | lo03 | 0 | 240 | 0 | |
Node 4 Address | lo04 | 0 | 240 | 0 | |
Node 5 Address | lo05 | 0 | 240 | 0 | |
Node 6 Address | 106 | 0 | 240 | 0 | |
Node 7 Address | lo07 | 0 | 240 | 0 | |
Node 8 Address | lo08 | 0 | 240 | 0 | |
Node 9 Address | loO8 | 0 | 240 | 0 | |
Node 10 Address | lo10 | 0 | 240 | 0 | |
Node 11 Address | loll | 0 | 240 | 0 | |
Node 12 Address | lo12 | 0 | 240 | 0 | |
Node 13 Address | lo13 | 0 | 240 | 0 | |
Node 14 Address | 1o14 | 0 | 240 | 0 | |
Node 15 Address | lo15 | 0 | 240 | 0 | |
Node 16 Address | 1o16 | 0 | 240 | 0 |
Scan Network
Initiates a scan for evaporator controllers| nO1| 0 OF| 1 ON| 0 (OFF)|
Clear Network List
Clears the list of evaporator controllers, may be used when one or several
controllers are removed, proceed with a new network scan (n01) after this.|
n02| 0 (OFF)| 1 (ON)| 0 (OFF)|
Service| | | | |
Read discharge pressure| u01| bar|
Read gascooler outlet temp.| UOS| °C|
Read receiver pressure| U08| bar|
Read receiver pressure in temperature| U09| °C|
Read discharge pressure in temperature| 1122| °C|
Read suction pressure| 1123| bar|
Read suction pressure in temperature| U24| °C|
Read discharge temperature| U26| °C|
Read suction temperature| U27| °C|
Read controller software version| u99| |
Danfoss A/S Climate Solutions danfoss.com • +45 7488 2222
Any information, including, but not limited to information on selection of
product, its application or use, product design, weight, dimensions, capacity
or any other technical data in product manuals, catalogues descriptions,
advertisements, etc. and whether made available in writing, orally,
electronically, online or via download, shall be considered informative, and
is only binding if and to the extent, explicit reference is made in a
quotation or order confirmation. Danfoss cannot accept any responsibility for
possible errors in catalogues, brochures, videos and other material. Danfoss
reserves the right to alter its products without notice. This also applies to
products ordered but not delivered provided that such alterations can be made
without changes to form, fit or function of the product.
All trademarks in this material are property of Danfoss A/S or Danfoss group
companies. Danfoss and the Danfoss logo are trademarks of Danfoss A/S. All
rights reserved.
© Danfoss | Climate Solutions | 2023.01
Documents / Resources
|
Danfoss CO2 Module Controller Universal
Gateway
[pdf] User Guide
CO2 Module Controller Universal Gateway, CO2, Module Controller Universal
Gateway, Module Controller, Controller, Universal Gateway, Gateway
---|---
|
Danfoss CO2 Module Controller Universal
Gateway
[pdf] User Guide
SW version 1.7, CO2 Module Controller Universal Gateway, CO2, Module
Controller Universal Gateway, Controller Universal Gateway, Universal Gateway,
Gateway
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>