Knightsbridge EMSUR 230V 3W LED Surface Emergency Downlight Instruction Manual

June 8, 2024
Knightsbridge

Knightsbridge EMSUR 230V 3W LED Surface Emergency Downlight

GENERAL INSTRUCTIONS

These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following product: EMSUR

SAFETY

  • This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
  • Please isolate mains prior to installation or maintenance
  • Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
  • Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
  • This product is for indoor use only
  • This product is Class II double insulated
  • This product is IP20 rated

INSTALLATION

  • Provide power to the required point of installation
  • Remove the baseplate by pressing the two retaining tabs on either side of the fitting (see Fig. 1)Knightsbridge-EMSUR-230V-3W-LED-Surface-Emergency-Downlight-fig1
  • Using the baseplate as a template, mark the location for, and drill the fixing holes ensuring not to infringe with any gas / water pipes or electrical cables
  • Feed the mains cable into the luminaire and secure the baseplate to the surface
  • Ensuring correct polarity is observed, carefully wire as shown in Fig. 2
  • Connect the battery via the plug and socket to the PCB
  • Refasten the cover to the baseplate
  • Switch on and check for correct operation, ensuring the green indicator LED Is illuminated
  • We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test
  • If the batteries have been left in a discharged state for an extended period, we recommend that one or more charge and discharge cycles are completed which should help to restore the battery capacity

WARNING

This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.

GENERAL

The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire should be replaced. Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product. Installing in areas where the temperature consistently drops below 0°C may shorten the battery life. This product is for non- maintained emergency use only. This product is non-dimmable. This product should be recycled in the correct manner when it reaches the end of its life. Check local authoritiesfor where facilities exist. The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local authorities for the disposal of this toxic waste.

WARRANTY

This product has a warranty of 3 years (excluding battery) from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.

TESTING FOR EMERGENCY LUMINAIRES

Recommended routine test procedure in accordance with BS5266

  • Daily check – check LED charge indicator is illuminated
  • Monthly functional test – simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
  • Annual 3-hour duration test – simulate a mains supply failure for 3-hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
  • If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record sheet

ML Accessories Limited LU5 4LT
www.mlaccessories.co.uk

INTERNATIONAL CONTACT DETAILS

Knightsbridge-EMSUR-230V-3W-LED-Surface-Emergency-Downlight-
fig4

Installed by:
Contact number:
Installation date:

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>